I want to search for...
Permit #2014040974
Permit Details
Status: COED
| Parcel Id: 48-11-31-1710-00000-1280 |
| CONDITIONED SPACE: 3850 sqft |
| GARAGE: 871 sqft |
| OPENED PORCH (WITH ROOF) : 590 sqft |
| OPENED PORCH (WITH ROOF) : 88 sqft |
| Total Square Footage: 5399 sqft |
| Subdivision: 2087 - ESTATES AT GRAND HAVEN PHASE II |
| Job Phone: 386-947-4481 |
| Location Address: 11 TURKEY OAK LN |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 05/29/2014 |
| NOC: RECORDED |
| Applicant name: ERIC CHRISTOPHER OLSEN |
| Owner: POLIZZI, JOHN A & KATHLEEN M |
|
Address 35 BLUE OAK LANE PALM COAST, FL 32137 |
| Lot: 128 |
| Contracted Stated Job Value: ¤550,000.00 |
| Job Description: SINGLE FAMILY RESIDENCE |
| Type: CN |
Contractor
OLSEN CUSTOM HOMES AND CONSULTING INC
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
131 MAGNOLIA AVE DAYTONA BEACH, FL 32114 |
CGC1508852 (Exp: 08/31/2026) | 386-947-4481 | (386)947-4484 |
Sub Contractors
BENJAMIN EDWARD SMITH
| Status | Location Address | State License Number | Phone |
| CANCEL |
131 MAGNOLIA AVE DAYTONA BEACH, FL 32114 |
EC13004288 (Exp: 08/31/2016) | 386-265-2687 |
DANIEL P HUCKS
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
400 N. U.S. 1 Ormond Beach, FL 32174 |
CAC029376 (Exp: 08/31/2024) | 386-672-8494 | 386-673-7856 |
JOHN BRADLEY WINFREY JR
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
1685 S. CLARA AVE Deland, FL 32720 |
CFC054901 (Exp: 08/31/2026) | 386-734-0154 | 386-734-2751 |
SANTOS L HERNANDEZ
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
946 SHADDICK DRIVE ORANGE CITY, FL 32763 |
CCC1328011 (Exp: 08/31/2026) | 386-218-4942 | 386-218-4937 |
KEN DEPRINZIO
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
325 WALKER STREET HOLLY HILL, FL 32117 |
11351 (Exp: 08/31/2026) | 386-672-8494 | 386-673-7856 |
Inspection History
| Type | Request Date | Result | Inspector |
| U -UTILITY RESIDENTIAL FINAL | 01/16/2015 | APPROVED | MKRONENBERG |
| Note: THIS IS A REINSPECTION | |||
| U -UTILITY RESIDENTIAL FINAL | 01/15/2015 | Disapproved - NO FEE | MKRONENBERG |
| Note: Inspection Resulted at 1/15/2015 5:16:28 PM PLEASE LOWER SEWER CLEAN-OUT TO EXISTING GRADE. | |||
| BLD - BUILDING FINAL | 01/14/2015 | FINAL APPROVED | CMINI |
| FINAL APRON (AFTER POUR/DRIVEWAY) | 01/13/2015 | FINAL APPROVED | GLALIMA |
| ROW FINAL | 01/13/2015 | APPROVED | GLALIMA |
| FINAL SURVEY (OFFICE USE ONLY) | 01/09/2015 | APPROVED | JHINDMAN |
| ELECTRIC - EARLY POWER | 12/01/2014 | APPROVED - AS NOTED | CMINI |
| Note: Inspection Resulted at 12/1/2014 11:41:17 AM CALLED FPL TO RELEASE POWER, SPOKE WITH SUSAN | |||
| PRE-APRON (PRE-POUR/DRIVEWAY) | 11/17/2014 | APPROVED - AS NOTED | GLALIMA |
| Note: READY FOR PAVERS | |||
| GRAVITY SEWER TEST | 11/10/2014 | APPROVED | CMINI |
| INSULATION | 10/06/2014 | APPROVED | CMINI |
| LATH/BRICK/ WATER BARRIER | 10/01/2014 | APPROVED | CMINI |
| ALL ROUGH | 10/01/2014 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| ALL ROUGH | 09/29/2014 | Disapproved -FEE REQUIRED | DROCKWELL |
| Note: Inspection Resulted at 9/29/2014 2:52:05 PM SERVICE CABLE PVC NOT STRAPPED TO BLOCK ABOVE SERVICE PANEL/GROUND METAL BOXES/CEILING LIGHT IN GUEST BEDROOM HALLWAY NOT INSTALLED/PROVIDE SMOKE DETECTOR IN MASTER BEDROOM AND WITHIN 10FT OF DOUBLE BEDROOM ENTRY DOORS OUTSIDE/FRAME DRYER DUCT EXPOSED IN LAUNDRY CEILING/FIREBLOCK WALL CHASE WHERE COUNTER TOP MEETS WALL IN KITCHEN AREA/NO PRESSURE ON GAS LINE-IF A SEPARATE INSPECTION CALL IT IN BEFORE INSULATION | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 09/19/2014 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| U - SEWER TIE IN | 09/19/2014 | APPROVED | DSPENCER |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 09/11/2014 | Disapproved -FEE REQUIRED | CMINI |
| Note: THIS IS A REINSPECTION Inspection Resulted at 9/11/2014 3:31:55 PM DID PARTIAL YESTERDAY ON TOWER,TODAY NOT COMPLETED,ANCHOR BOLTS NOT COMPLETE ON KNEE WAL AT LANAI MID WALLL,STRAPING NOT COMPLETE AT LANAI MID WALL | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 09/10/2014 | Disapproved -FEE REQUIRED | CMINI |
| Note: Inspection Resulted at 9/10/2014 2:01:40 PM LOOKED AT FRONT ENTRY TIE DOWN OK TO SHEET(PARTIAL)INSPECTION | |||
| ELECTRIC-TUG | 08/05/2014 | APPROVED | DROCKWELL |
| TIE BEAM / LINTEL | 07/25/2014 | APPROVED | CMINI |
| ELEV CERT-FOUNDATION APPROVAL | 07/23/2014 | APPROVED | DBEVAN |
| Note: Per Denise Bevan BUC Elevation Certificate with a BFE of 9 is approved. | |||
| FOUND SURVEY APPROVED (OFFICE) | 07/17/2014 | APPROVED | JHINDMAN |
| MONOLITHIC SLAB | 07/03/2014 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| MONOLITHIC SLAB | 07/02/2014 | Disapproved -FEE REQUIRED | CMINI |
| Note: Inspection Resulted at 7/2/2014 2:04:08 PM FRONT FOOTER STILL NOT AT 16" DEPTH PER PLAN ON BD RM SIDE...STILL MISSING RELIEVING ARCH OVER THRU PIPES AT GARAGE AREA AND BACK FOOTER STILL EXTENDED TO END OF HOUSE,IF THAT IS TO REMAIN NEED TO HAVE APPROVED BY CITY | |||
| MONOLITHIC SLAB | 07/01/2014 | Disapproved -FEE REQUIRED | CMINI |
| Note: Inspection Resulted at 7/1/2014 3:48:18 PM RELIEVING ARCHES NEEDED OVER PIPES THRU FOOTERS....P2603.5 FOOTERS AND SLAB ADDED AT BACK PORCH NOT SHOWN ON PLAN..COLUMN FOOTERS AT FRONT PLAN CALLING FOR 16" DEPTH ALL CIRCLED ON PLAN | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 06/27/2014 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 06/26/2014 | Disapproved -FEE REQUIRED | JCOLASANTI |
| Note: Inspection Resulted at 6/26/2014 3:50:55 PM NEED TO HAVE 5`` HEAD PRESSURE ON DWV ..FBC P 2503.2 |
Review History
| Department | Status | Date In | Date Out |
| PLFM | COMPLETE | 01/07/2015 | 01/08/2015 |
| SW1 | COMPLETE | 01/07/2015 | 01/09/2015 |
| Note: Released By: JHINDMAN final survey | |||
| PLFM | COMPLETE | 07/17/2014 | 07/23/2014 |
| SW1 | COMPLETE | 07/17/2014 | 07/17/2014 |
| Note: Released By: JHINDMAN foundation s | |||
| BLD | COMPLETE | 06/16/2014 | 06/16/2014 |
| PLFM | COMPLETE | 06/16/2014 | 06/18/2014 |
| SW1 | COMPLETE | 06/16/2014 | 06/16/2014 |
| ZON | COMPLETE | 06/16/2014 | 06/17/2014 |
| PLFM | COMPLETE | 05/21/2014 | 05/22/2014 |
| PLFM | HOLD | 05/14/2014 | 05/16/2014 |
| Note: The original comment was not addressed as the elvation certificate provided still has the same elevations but different datums than the site plan. The elevation submitted did not include a new site plan with corrected elevations. 1. The survey shows propose elevation at 10.5 feet with 1988 datum and the elevation certificate shows 10.5 for top of bottom floor with 1929 datum. Please correct survey or elevatin certificate to show correct elevation for the datum being used. | |||
| PLUM | COMPLETE | 05/09/2014 | 05/12/2014 |
| PLFM | HOLD | 05/09/2014 | 05/12/2014 |
| Note: The original comment was not addressed. The elevation submitted did not include a new site plan with corrected elevations. 1. The survey shows propose elevation at 10.5 feet with 1988 datum and the elevation certificate shows 10.5 for top of bottom floor with 1929 datum. Please correct survey or elevatin certificate to show correct elevation for the datum being used. | |||
| PLFM | HOLD | 05/05/2014 | 05/07/2014 |
| Note: 1. The survey shows propose elevation at 10.5 feet with 1988 datum and the elevation certificate shows 10.5 for top of bottom floor with 1929 datum. Please correct survey or elevatin certificate to show correct elevation for the datum being used. | |||
| PLUM | HOLD | 05/02/2014 | 05/05/2014 |
| Note: Provide the size of gas tank as previously requested and for clarity show the it on gas riser diagram in relation to all piping connections including delivery pressure per 2010 FBC 107.2.1/ FBC Fuel Gas 402. | |||
| ZON | COMPLETE | 05/02/2014 | 05/05/2014 |
| UD1 | COMPLETE | 05/02/2014 | 05/05/2014 |
| Note: See comments in the general notes Keith King 386-9318009 | |||
| BLD | COMPLETE | 04/30/2014 | 04/30/2014 |
| ELEC | COMPLETE | 04/30/2014 | 04/30/2014 |
| ENGIN1 | COMPLETE | 04/30/2014 | 04/30/2014 |
| Note: No swale plan required. | |||
| MECH | COMPLETE | 04/30/2014 | 04/30/2014 |
| PLUM | HOLD | 04/30/2014 | 04/30/2014 |
| Note: Provide plumbing riser detail and Provide size and location of LP tank FBC 107.2.1 J McGowen | |||
| SW1 | COMPLETE | 04/30/2014 | 04/30/2014 |
| UD1 | HOLD | 04/30/2014 | 05/01/2014 |
| Note: the elec plans need to show the PEP panel location Keith King 386-9318009 | |||
| URB | COMPLETE | 04/30/2014 | 05/01/2014 |
| ZON | HOLD | 04/30/2014 | 04/30/2014 |
| Note: Site plan must show all platted easements. This lot has an emergency access easement that must be shown. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 01/14/2015 |
| REINSPECTION FEE | ¤40.00 | 01/14/2015 |
| REINSPECTION FEE | ¤40.00 | 01/14/2015 |
| REINSPECTION FEE | ¤40.00 | 01/14/2015 |
| REINSPECTION FEE | ¤40.00 | 01/14/2015 |
| REINSPECTION FEE | ¤40.00 | 01/14/2015 |
| REVISION | ¤40.00 | 01/14/2015 |
| SITE PLAN 20 | ¤20.00 | 05/29/2014 |
| SURCHARGE FS 533.721 | ¤37.65 | 05/29/2014 |
| SURCHARGE - FS 468.631 | ¤37.65 | 05/29/2014 |
| STORM WATER PERMIT FEES | ¤80.00 | 05/29/2014 |
| 3% TRANS IMPACT FEE CREDIT | (¤90.51) | 05/29/2014 |
| NEW RESIDENTIAL INSPECTIONS | ¤1,100.00 | 05/29/2014 |
| ADMIN FEE | ¤20.00 | 05/29/2014 |
| ELECTRIC FEE | ¤390.00 | 05/29/2014 |
| 3% FIRE IMPACT FEE CREDIT | (¤6.33) | 05/29/2014 |
| IMPACT FEE FIRE NONRESIDENTIAL | ¤211.11 | 05/29/2014 |
| IMPACT FEE PARKS | ¤894.24 | 05/29/2014 |
| IMPACT FEE SCHOOL | ¤3,600.00 | 05/29/2014 |
| IMPACT FEE TRANSPORTATION | ¤3,017.05 | 05/29/2014 |
| MECHANICAL FEE | ¤390.00 | 05/29/2014 |
| 3% PARKS IMPACT FEE CREDIT | (¤26.83) | 05/29/2014 |
| PLAN CHECK FEE | ¤220.00 | 05/29/2014 |
| PLUMBING FEE | ¤390.00 | 05/29/2014 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤10,564.03 |