I want to search for...

Permit #2015070829

Permit Details

Status: FINAL

Subdivision: -
Job Phone: 904-529-5200
Location Address: 6960 U S HWY 1 N
Type: TA - TELECOMMUNICATION TOWER ALTERATION
Issue Date: 09/04/2015
NOC: RECORDED
Applicant name: TERRY LEE KNIGHT
Owner: STATE OF FLORIDA DEPARTMENT OF TRANSPORTATION

Address

719 S WOODLAND BLVD

DELAND, FL 32720

Contracted Stated Job Value: ¤30,000.00
Job Description: ADD ATENNA AND RELATED EQUIPMENT
Type: CN

Contractor

FLORIDA TEL-CON, INC
Status Location Address State License Number Phone
ACTIVE

6800 CATHEDRAL OAK PARKWAY

GREEN COVE SPRINGS, FL 32043

CGC059354 (Exp: 08/31/2026) 904-529-5210

Sub Contractors

CHARLES WILLIAM BERLINGHOFF
Status Location Address State License Number Phone
ACTIVE

6800 CATHERDRAL OAK PARKWAY

GREEN COVE, FL 32043

EC0001722 (Exp: 08/31/2026) 904-529-5200

Inspection History

Type Request Date Result Inspector
LDSC- LANDSCAPE FINAL 12/29/2015 APPROVED WBUTLER
Note: Due to this being an FDOT site, no landscaping can be required by the City
FINAL 12/28/2015 FINAL APPROVED CMINI
ELECTRIC FINAL 12/21/2015 FINAL APPROVED RMARTIN
Note: THIS IS A REINSPECTION
ELECTRIC FINAL 11/03/2015 PARTIALLY APPROVED RMARTIN
Note: Inspection Resulted at 11/3/2015 3:37:23 PM STILL NEED TO START UP GENERATOR, NO TANK SET YET POWER OK CALLING FPL FOR E.P FOR GEN. START UP
ELECTRIC FINAL 10/30/2015 CANCELLED BY APPLICANT AIRS WEB
FOOTER 10/29/2015 APPROVED JCOLASANTI
Note: THIS IS A REINSPECTION
ELECTRIC 1ST ROUGH 10/15/2015 APPROVED - AS NOTED RMARTIN
Note: Inspection Resulted at 10/15/2015 1:04:58 PM NEED REVISION ON SERVICE LOCATION OK TO COVER DITCH
FOOTER 10/09/2015 PARTIALLY APPROVED JCOLASANTI
Note: Inspection Resulted at 10/9/2015 9:49:05 AM OK TO POUR SLAB, NEED TO CALL IN WHEN FORM WALLS ARE COMPLETE.
FOOTER 10/08/2015 Disapproved -FEE REQUIRED JCOLASANTI
Note: Inspection Resulted at 10/8/2015 2:38:15 PM PROPANE TANK SLAB NEEDS TO HAE WIRE MESH TIED TO STEEL PER PLAN.

Review History

Department Status Date In Date Out
ELEC COMPLETE 10/29/2015 10/29/2015
BLD COMPLETE 09/04/2015 09/04/2015
ITC COMPLETE 09/02/2015 09/02/2015
Note: Released By: SZAPATA OK to proceed all items have been addressed.
PLENV COMPLETE 09/01/2015 09/03/2015
Note: No additional comments.
BLD HOLD 09/01/2015 09/02/2015
Note: 1. Provide a separate permit for the gas tank and line. 2nd request. J. Hindman 986-3784.
ZON COMPLETE 09/01/2015 09/09/2015
PLLA COMPLETE 08/31/2015 08/31/2015
Note: Released By: WBUTLER No comments.
PLLA HOLD 08/21/2015 08/21/2015
Note: Held By: WBUTLER 8-21-15 WMB 1) The applicant states that they feel this site is exempt from our City landscape requirements. Need to prove why it is exempt, as the property is not owned by the Florida Department of Transportation, who would be exempt. Requirements for landscape and irrigation still stand.
ENGIN1 COMPLETE 08/07/2015 08/10/2015
PLENV HOLD 08/07/2015 08/11/2015
Note: Verify if the tower supports an active osprey nest. Ospreys are known to inhabit the project tower structure. In the event a nest exists, provide an overview of proposed actions to ensure compliance with the Migratory Bird Treaty Act.
PLLA HOLD 08/07/2015 08/10/2015
Note: Need a landscape and irrigation plan to provide required landscaping around the outside fence of this facility. Must meet the current mechanical equipment screening requirements. Need 7-gallon shrubs a minimum of 30" tall at time of planting around the entire fence perimeter.
UD1 COMPLETE 08/07/2015 08/10/2015
BLD HOLD 07/30/2015 08/03/2015
Note: 1. Provide a separate permit for the gas tank and line
ZON HOLD 07/30/2015 08/07/2015
Note: Application is deemed incomplete for the following reason to include comments from other departments: Provide a site plan showing the dimensions and setbacks from property line for new pad extension. Reviews conducted within 20 days of submission.
ITC HOLD 07/30/2015 08/28/2015
Note: Held By: SZAPATA The application be approved with the following conditions: 1. The Applicant shall certify the propane fuel tank shall be maintained in accordance with all applicable rules specific to storage and ignition of this type of service 2. Prior to approval, the Applicant shall submit a statement that it will comply with all Federal Communications Commission (FCC) guidelines regarding Radio Frequency (RF) energy exposure limits AND RF interference with other radio services; and, 3. The newly proposed emergency power backup generator noise level shall not exceed 65dBa at the property edge. Testing shall be limited to the hours between 9:00 A.M. and 4:00 P.M., (Monday through Friday).

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REVISION ¤40.00 12/24/2015
REINSPECTION FEE ¤40.00 10/29/2015
SITE PLAN 20 ¤20.00 09/04/2015
SURCHARGE FS 533.721 ¤6.05 09/04/2015
SURCHARGE - FS 468.631 ¤6.05 09/04/2015
ADMIN COMMERCIAL ¤60.00 09/04/2015
ELECTRIC FEE ¤78.00 09/04/2015
THIRD PARTY REVIEW ¤3,500.00 09/04/2015
PERMIT FEE ¤165.00 09/04/2015
PLAN CHECK FEE ¤100.00 09/04/2015
Fees Total Due: ¤0.00 Total Paid: ¤4,015.10