Status: CANCEL

Block: 000A0
Subdivision: 1034 - PALM HARBOR OFFICE PARK
Job Phone: 386-585-0958
Location Address: 4 OFFICE PARK DR
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
NOC: RECORDED
Applicant name: JEFFREY G SPRAGUE
Owner: RM 5 FIFTH AVENUE LLC

Address

2561 MOODY BLVD UNIT A

FLAGLER BEACH, FL 32136

Lot: 002A
Contracted Stated Job Value: ¤2,000.00
Job Description: POD 3-- BUILDOUT FOR 3'N MOTION DANCE STUDIO LLC"
Type: CN

Contractor

JGS DESIGN ASSOCIATES, LLC
Status Location Address State License Number Phone
INACTIVE

8 INDIAN MOUND CT

FLAGLER BEACH, FL 32136

CBC1260630 (Exp: 08/31/2026) 386-585-0958

Sub Contractors

JOHN FREDERICK WANERKA JR
Status Location Address State License Number Phone Fax
CANCEL

P.O. BOX 350214

BUNNELL, FL 32110

EC13003318 (Exp: 08/31/2022) (386)446-9626 (386)445-3131
CHARLES WEYANT
Status Location Address State License Number Phone
ACTIVE

PO BOX 1261

FLAGLER BEACH, FL 32136

CAC1815058 (Exp: 08/31/2026) (386)246-7745
DAVID L MILLER
Status Location Address State License Number Phone
CANCEL

170 OLD MOODY BLVD

BUNNELL, FL 32110

CFC1425948 (Exp: 08/31/2022) (386) 439-2169

Inspection History

Type Request Date Result Inspector
HVAC ROUGH
HVAC FINAL
ELECTRIC 2ND ROUGH
ELECTRIC FINAL
FRAMING
ABOVE CEILING
BUILDING FINAL
FIRE FINAL
U - UTILITY COMMERCIAL FINAL

Review History

Department Status Date In Date Out
FI1 COMPLETE 10/12/2015 10/13/2015
BLD COMPLETE 10/12/2015 10/13/2015
MECH COMPLETE 10/12/2015 10/13/2015
MECH HOLD 10/07/2015 10/08/2015
Note: Review comments on submitted corrections dated 10-7-15: 1. Heating and cooling load calculations show the total cooling load of 18 tons but the capacity of selected hvac units show (2)-5 tons only. Coordinate to comply with FBCEC 5th ed. C-403.2.1/C-403.2.2. (Previous comment) New comment: Coordinate the fresh air intake (outdoor air) on revised hvac plan (1124 CFM) versus revised calculation ( 781 CFM) for clarity FBC 5th ed. 107.2.1. F.N. Reodica - 386-986-4734.
FI1 HOLD 10/07/2015 10/08/2015
Note: 1. Platinum fire rated glass requires a rated frame per the manufacturers specifications. It is not a complete window unit. Provide complete specifications or product approval for the rated view windows. 2nd request. J. Hindman 986-3784.
BLD HOLD 10/07/2015 10/08/2015
Note: 1. Platinum fire rated glass requires a rated frame per the manufacturers specifications. It is not a complete window unit. Provide complete specifications or product approval for the rated view windows. 5th ed.fbc 107.2.1. J. Hindman 986-3784 2nd request.
MECH HOLD 10/01/2015 10/02/2015
Note: Previous comments items 1,2, and 4 shall be addressed. Review comments on submitted corrections dated 9-23-15: 1. Heating and cooling load calculations show the total cooling load of 18 tons but the capacity of selected hvac units show (2)-5 tons only. Coordinate to comply with FBCEC 5th ed. C-403.2.1/C-403.2.2. 2. Provide fire dampers on ducts penetrating fire rated corridor walls per FBCM 5th ed. 607.5.3. 4. Provide balanced return air from dressing room per FBCM 5th ed. 601.5
BLD HOLD 10/01/2015 10/02/2015
Note: 1. Platinum fire rated glass requires a rated frame per the manufacturers specifications. It is not a complete window unit. Provide complete specifications or product approval for the rated view windows. 5th ed.fbc 107.2.1. J. Hindman 986-3784.
FI1 HOLD 10/01/2015 10/02/2015
Note: 1. Platinum fire rated glass requires a rated frame per the manufacturers specifications. It is not a complete window unit. Provide complete specifications or product approval for the rated view windows.
BLD HOLD 09/23/2015 09/28/2015
Note: 1. page 1/4 calls for rated doors in corridor. Page 2/4 door schedule shows hollow core doors which are not rated. Revise door schedule to show rated doors. 2. Provide view window Product approval number or manufacturers specifications that show the rating of the window. 5th ed. FBC 107.2.1.
FI1 HOLD 09/23/2015 09/28/2015
Note: 1. page 1/4 calls for rated doors in corridor. Page 2/4 door schedule shows hollow core doors which are not rated. Revise door schedule to show rated doors. 2. Provide view window Product approval number or manufacturers specifications that show the rating of the window. 5th ed. FFPC.
PLUM COMPLETE 09/23/2015 09/25/2015
MECH HOLD 09/23/2015 09/25/2015
Note: Review comments on submitted corrections dated 9-23-15: 1. Heating and cooling load calculations show the total cooling load of 18 tons but the capacity of selected hvac units show (2)-5 tons only. Coordinate to comply with FBCEC 5th ed. C-403.2.1/C-403.2.2. 2. Provide fire dampers on ducts penetrating fire rated corridor walls per FBCM 5th ed. 607.5.3. 3. Provide fire damper detail and manufacturer's installation instructions per FBCM 5th ed. 607.2. 4. Provide balanced return air from dressing room per FBCM 5th ed. 601.5
MECH HOLD 09/16/2015 09/22/2015
Note: Previous comments 1 and 2 shall be addressed. 1. Provide existing and proposed hvac plan suitable for review, construction and inspection per FBC 5th ed. 107.2.1/ 107.3.5. 2. Provide heating and load calculation due to change in occupancy use and occupant load per FBC 5th ed existing code 1009.
PLUM HOLD 09/16/2015 09/22/2015
Note: Previous comments shall be addressed. 2. Provide drinking fountain and service sink per FBCP 5th ed. 403. 3. Provide plumbing riser diagrams per FBC 5th ed. 107.3.5. 4. Provide water heater location, manufacturer's specification and installation instructions per FBCP 5th ed. 501.4/502.1. 5. Provide piping material specification for DWV and domestic water (hot and cold) per FBCP 5th ed. 702/502/605.4. F.N. Reodica-386-986-4734.
BLD HOLD 09/16/2015 09/21/2015
Note: 1. Provide new door opening details for the alteration of the opening. 2. Provide Florida Product approvals for the new exterior doors. 3. revise pages 1,2 and 3 to show the new configuration of the rooms. 4. Identify the corridor door ratings. 5. Provide and identify the rated glass in the one hour corridor. 5th edition FBC 107.2.1. J. Hindman 986-3784.
FI1 HOLD 09/16/2015 09/21/2015
Note: 1. Revise pages 1,2 and 3 to show the new configuration of the rooms. 4. Identify the corridor door ratings. 5. Provide and identify the rated glass in the one hour corridor. 5th ed FFPC. J. Hindman 986-3784.
BLD HOLD 08/21/2015 08/24/2015
Note: 1. Provide a second exit per 5th edition FBC 1015.1. 2. Provide a second exit from dance rooms two and three per 5th ed. FBC 1015.1. 3. Provide or identify a two hour separation of occupancies per 5th ed. FBC Table 508.4. 4. Provide a one hour rated corridor per 5th ed. FBC 1018.1. J. Hindman 986-3784.
FI1 HOLD 08/21/2015 08/24/2015
Note: 1. Provide a second exit per 5th edition FFPC 704.1.1. 2. Provide a second exit from dance rooms two and three per 5th ed. FFPC 704.1.1. 3. Provide or identify a two hour separation of occupancies per 5th ed. FFPC Table 6.1.14.1(a). 4. Provide a one hour rated corridor per 5th ed. FFPC 7.1.3.1. J. Hindman 986-3784.
PLUM HOLD 08/21/2015 08/24/2015
Note: 1.Provide separate restroom facilities for men and women per FBCP 5th ed. 403.2. 2. Provide drinking fountain and service sink per FBCP 5th ed. 403. 3. Provide plumbing riser diagrams per FBC 5th ed. 107.3.5. 4. Provide water heater location, manufacturer's specification and installation instructions per FBCP 5th ed. 501.4/502.1. 5. Provide piping material specification for DWV and domestic water (hot and cold) per FBCP 5th ed. 702/502/605.4. F.N. Reodica-386-986-4734.
MECH HOLD 08/21/2015 08/21/2015
Note: Previous comments 1 and 2 shall be addressed. 1. Provide existing and proposed hvac plan suitable for review, construction and inspection per FBC 5th ed. 107.2.1/ 107.3.5. 2. Provide heating and load calculation due to change in occupancy use and occupant load per FBC 5th ed existing code 1009.
BLD HOLD 08/11/2015 08/14/2015
Note: 303.1 Assembly Group A. Assembly Group A occupancy includes, among others, the use of a building or structure, or a portion thereof, for the gathering of persons for purposes such as civic, social or religious functions; recreation, food or drink consumption or awaiting transportation. Provide the correct occupancy and design plans for that occupancy use. 5th ed, FBC 302.
ELEC COMPLETE 08/11/2015 08/14/2015
FI1 HOLD 08/11/2015 08/14/2015
Note: 1. Provide plans that are designed for the correct occupancy type and load. 5th ed. FFPC ch. 6 and 7.
MECH HOLD 08/11/2015 08/14/2015
Note: 1. Provide existing and proposed hvac plan suitable for review, construction and inspection per FBC 5th ed. 2. Provide heating and load calculation due to change in occupancy use and occupant load per FBC 5th ed existing code 1009. 3. Provide outdoor air ventilation requirement per FBCM 5th ed. 403.
PLUM HOLD 08/11/2015 08/14/2015
Note: Provide the correct occupancy classification and occupant load calculation prior to plumbing review of the required plumbing facilities per FBC 5th ed. 302/1004/107.2.1.
UD1 COMPLETE 08/11/2015 08/12/2015
ZON COMPLETE 08/11/2015 08/11/2015
SW1 COMPLETE 08/11/2015 08/11/2015

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADMIN COMMERCIAL ¤60.00
INSPECTION - COMMERCIAL ADD ¤50.00
ELECTRIC FEE ¤61.20
FIRE PLANS REVIEW ¤25.00
MECHANICAL FEE ¤61.20
PLAN CHECK FEE ¤100.00
PLUMBING FEE ¤61.20
SITE PLAN 20 ¤20.00
SURCHARGE FS 533.721 ¤5.15
SURCHARGE - FS 468.631 ¤5.15
Fees Total Due: ¤448.90 Total Paid: ¤0.00