I want to search for...
Permit #2015080274
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7010-00090-0260 |
| Block: 00090 |
| Subdivision: 2137 - SECTION 10-FLORIDA PARK |
| Job Phone: 904-777-4300 |
| Location Address: 2 FIELDING PL |
| Type: ME - MECHANICAL |
| Issue Date: 08/31/2015 |
| NOC: Unknown |
| Applicant name: DENNIS M BROWN |
| Owner: ALCANTARA, RAFAEL F & SANDRA J |
|
Address 2 FIELDING PL PALM COAST, FL 32137 |
| Lot: 0260 |
| Contracted Stated Job Value: ¤5,300.00 |
| Job Description: 4 TON, 14 SEER HVAC SYSTEM |
| Type: CN |
Contractor
FLORIDA HOME AIR CONDITIONING AND PLUMBING
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
4211 EMERSON ST JACKSONVILLE, FL 32207 |
CMC1249939 (Exp: 08/31/2018) | 904-777-4300 | 904-777-9599 |
Sub Contractors
EARL W FRICK
| Status | Location Address | State License Number | Phone |
| CANCEL |
5065-3 ST AUGUSTINE ROAD JACKSONVILLE, FL 32207 |
ER0015316 (Exp: 08/31/2016) | (904) 737-7770 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 03/18/2016 | FINAL APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| HVAC FINAL | 03/15/2016 | Disapproved -FEE REQUIRED | LMILLER |
| Note: THIS IS A REINSPECTION Inspection Resulted at 3/15/2016 12:29:02 PM UNIT LABELING..FBC.R. M1303.1 MUST IDENTIFY MAXIMUM OVER CURRENT BREAKER SIZE ON AIR HANDLER AND OR CONDENSOR UNIT. (NO LABEL ON UNIT FOR MOCP)... AIR HANDLER MODEL NUMBER DOES NOT MATCXH PAPERWORK.... CONDENSTAE DRAIN R318.5 PROTECTION AGAINST DECAY AND TRERMITES, MUST DISCHARGE AT LEAST 1FT- AWAY FROM STRUCTURE SIDEWALL.... MODEL NUMBER ON AIR HANDLER SUBMITTED AND APPROVED DOES NOT MATCH UNIT INSTALLED | |||
| HVAC FINAL | 02/29/2016 | Disapproved -FEE REQUIRED | LMILLER |
| Note: Inspection Resulted at 2/29/2016 10:11:40 AM KNOCKED AND RANG BELL (NO ANSWER), ACCESS NEEDED FOR INSPECTION. |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 03/16/2016 | 03/17/2016 |
| Note: Released By: FREODICA revision - changed indoor unit model number. | |||
| MECH | COMPLETE | 08/11/2015 | 08/12/2015 |
| Note: Released By: FREODICA |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REVISION | ¤40.00 | 03/18/2016 |
| REINSPECTION FEE | ¤40.00 | 03/16/2016 |
| REINSPECTION FEE | ¤40.00 | 03/04/2016 |
| SURCHARGE FS 533.721 | ¤2.00 | 08/31/2015 |
| SURCHARGE FS 533.721 | (¤2.00) | 08/31/2015 |
| SURCHARGE FS 533.721 | ¤2.00 | 08/31/2015 |
| SURCHARGE - FS 468.631 | (¤2.00) | 08/31/2015 |
| SURCHARGE - FS 468.631 | ¤2.00 | 08/31/2015 |
| SURCHARGE - FS 468.631 | ¤2.00 | 08/31/2015 |
| ADMIN FEE | (¤20.00) | 08/31/2015 |
| ADMIN FEE | ¤20.00 | 08/31/2015 |
| ADMIN FEE | ¤20.00 | 08/31/2015 |
| MECHANICAL FEE | ¤63.60 | 08/31/2015 |
| MECHANICAL FEE | (¤63.60) | 08/31/2015 |
| MECHANICAL FEE | ¤63.60 | 08/31/2015 |
| PLAN REVIEW 25 | (¤25.00) | 08/31/2015 |
| PLAN REVIEW 25 | ¤25.00 | 08/31/2015 |
| PLAN REVIEW 25 | ¤25.00 | 08/31/2015 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤232.60 |