I want to search for...
Permit #2015090120
Permit Details
Status: COED
| Parcel Id: 07-11-31-7003-000A0-001A |
| Block: 000A0 |
| Subdivision: 2190 - SECTION 3-COUNTRY CLUB COVE |
| Job Phone: 386-943-9433 |
| Location Address: 2 OFFICE PARK DR |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 10/01/2015 |
| NOC: RECORDED |
| Applicant name: RONALD E WILSON |
| Owner: NOLARA, LLC |
|
Address 2 OFFICE PARK DR PALM COAST, FL 32137 |
| Lot: 001A |
| Contracted Stated Job Value: ¤39,500.00 |
| Job Description: STORE FRONT GLASS/COMMON AREA & REPLACE WINDOWS, BATHROOMS ADA COMPLIANT |
| Type: CN |
Contractor
MCNEAL & WHITE CONTRACTORS INC
| Status | Location Address | Mailing Address | State License Number | Phone | Fax |
| CANCEL |
4867 PALM COAST PKWY NW PALM COAST, FL 32137 |
#15 PALM COAST, FL 32137 |
CGC1523365 (Exp: 08/31/2016) | 386-943-9433 | 386-943-9434 |
Sub Contractors
JOHN FREDERICK WANERKA JR
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
P.O. BOX 350214 BUNNELL, FL 32110 |
EC13003318 (Exp: 08/31/2022) | (386)446-9626 | (386)445-3131 |
LEONARD JOSEPH BRIAND
| Status | Location Address | State License Number | Phone |
| CANCEL |
580 GLEASON ST ORANGE CITY, FL 32763 |
CFC057108 (Exp: 08/31/2016) | 386-228-7512 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE FINAL | 06/24/2016 | FINAL APPROVED | LMILLER |
| Note: THIS IS A REINSPECTION | |||
| FIRE FINAL | 06/21/2016 | CANCELLED BY APPLICANT | AIRS WEB |
| Note: THIS IS A REINSPECTION | |||
| PLUMBING FINAL | 06/21/2016 | CANCELLED BY APPLICANT | AIRS WEB |
| Note: THIS IS A REINSPECTION | |||
| PLUMBING FINAL | 06/21/2016 | CANCELLED BY APPLICANT | AIRS WEB |
| Note: THIS IS A REINSPECTION | |||
| PLUMBING FINAL | 06/21/2016 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| HVAC ROUGH | 05/02/2016 | APPROVED - AS NOTED | CMINI |
| Note: Inspection Resulted at 5/2/2016 9:40:38 AM N/A | |||
| HVAC FINAL | 05/02/2016 | APPROVED - AS NOTED | CMINI |
| Note: Inspection Resulted at 5/2/2016 9:40:39 AM N/A | |||
| ELECTRIC 2ND ROUGH | 05/02/2016 | APPROVED | CMINI |
| ELECTRIC FINAL | 05/02/2016 | APPROVED | CMINI |
| PLUMBING FINAL | 05/02/2016 | CANCELLED BY APPLICANT | CMINI |
| FIRE FINAL | 05/02/2016 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: The exit sign at the rear left exit door cannot be seen by the rear left tenants. 5th ed. FFPC 101 7.10.1.2.1. | |||
| ABOVE CEILING | 05/02/2016 | APPROVED | CMINI |
| BUILDING FINAL | 05/02/2016 | APPROVED - AS NOTED | CMINI |
| Note: Inspection Resulted at 5/2/2016 9:40:37 AM NEED PLUMBING FINAL | |||
| U - UTILITY COMMERCIAL FINAL | 05/02/2016 | FINAL APPROVED | JNICHOLS |
| FINAL COMPLETION | 04/29/2016 | Disapproved - NO FEE | CMINI |
| Note: THIS IS A REINSPECTION Inspection Resulted at 4/29/2016 11:20:09 AM THIS WAS NOT A REQUIRED INSPECTION PER THIS PERMIT, NEED TO CALL ALL THE MISSED INSPECTIONS TO FINAL OUT PERMIT, AND BUILDING FINAL WILL BE THE FINAL INSPECTION ON BUILDING PART | |||
| FINAL COMPLETION | 03/24/2016 | Disapproved - NO FEE | JHINDMAN |
| Note: final cannot pass until HVAC is completed. | |||
| LATH/BRICK/WATER BARRIER | 11/20/2015 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| LATH/BRICK/WATER BARRIER | 11/05/2015 | PARTIALLY APPROVED | CMINI |
| Note: Inspection Resulted at 11/5/2015 11:56:01 AM PARTIAL SOUTH BUILDING ONLY | |||
| PLUMBING 1ST ROUGH | 11/04/2015 | CANCELLED BY INSPECTOR | CMINI |
| Note: not needed | |||
| PLUMBING 2ND ROUGH | 11/04/2015 | APPROVED | CMINI |
| WINDOW NAILING | 11/04/2015 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| WINDOW NAILING | 11/03/2015 | PARTIALLY APPROVED | DROCKWELL |
| Note: Inspection Resulted at 11/3/2015 2:32:34 PM ONLY WINDOWS WITH EXPOSED SCREWED FINS HAVE BEEN INSPECTED.WINDOWS WITH 2X CEDAR TRIM HAVE NOT BEEN INSPECTED FOR FASTENERS. | |||
| FRAMING | 10/29/2015 | APPROVED - AS NOTED | CMINI |
| Note: THIS IS A REINSPECTION Inspection Resulted at 10/29/2015 10:02:26 AM OK PER REVISION ON COLUMN | |||
| FRAMING | 10/26/2015 | Disapproved -FEE REQUIRED | CMINI |
| Note: THIS IS A REINSPECTION Inspection Resulted at 10/26/2015 11:21:41 AM NEED TO HAVE REVISION APPROVD BY CITY OF P.C. B.D FOR INSPECTION OF COLUMNS | |||
| WINDOW NAILING | 10/22/2015 | APPROVED | CMINI |
| Note: THIS IS A REINSPECTION | |||
| FRAMING | 10/21/2015 | CANCELLED BY APPLICANT | CMINI |
| WINDOW NAILING | 10/21/2015 | CANCELLED BY APPLICANT | CMINI |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 06/23/2016 | 06/23/2016 |
| Note: Completed and finaled separate permit 2016020039 for hvac at this space. | |||
| MECH | HOLD | 01/22/2016 | 01/26/2016 |
| Note: For clarification, a separate permit for hvac at habitable space can be applied but it will be a sub-permit to the original permit 2015090120 per FBC 5th ed. 107.2.1. F.N. Reodica -386-986-4734. | |||
| MECH | HOLD | 12/09/2015 | 12/16/2015 |
| Note: Revision - deletion of mechanical work. Deletion of mechanical work in this reconfigured or converted spaces for occupancy does not comply with FBC Existing Building 5th ed. 809.1/FBCM 5th ed. 403. F.N.Reodica-386-986-4734. | |||
| BLD | COMPLETE | 10/27/2015 | 10/27/2015 |
| PLUM | COMPLETE | 09/28/2015 | 09/29/2015 |
| BLD | COMPLETE | 09/21/2015 | 09/22/2015 |
| ELEC | COMPLETE | 09/21/2015 | 09/22/2015 |
| PLUM | HOLD | 09/21/2015 | 09/23/2015 |
| Note: Revise the occupant load calculation to comply with FBC 5th ed. Table 1004.1.2 for business occupancy. | |||
| MECH | COMPLETE | 09/21/2015 | 09/23/2015 |
| ZON | COMPLETE | 09/21/2015 | 09/22/2015 |
| BLD | HOLD | 09/04/2015 | 09/04/2015 |
| Note: 1. Provide a detail for the column changes. 5th ed. FBC 107.3.2. J. Hindman 986-3784. | |||
| ELEC | HOLD | 09/04/2015 | 09/04/2015 |
| Note: Please update to NEC 2011. Added emergency lighting needed for bathrooms: NEC 2011 Article 700.17. Florida Fire Prevention Code fifth edition Life Safety 7.9.1.2 -DC. Rewis 9864736 | |||
| FI1 | COMPLETE | 09/04/2015 | 09/04/2015 |
| MECH | HOLD | 09/04/2015 | 09/04/2015 |
| Note: Held By: FREODICA Provide mechanical contractor and hvac plan per FS 489/FBC 5th ed. 107.2.1. | |||
| PLUM | HOLD | 09/04/2015 | 09/04/2015 |
| Note: Provide occupancy classification of each tenant space and occupant load calculations to justify the reduction of plumbing fixtures of proposed modification of common restroom facilities per FBC 5th ed. chapter 3/chapter10 sec.1004/FBCP 5th ed. 403. F.N.Reodica-386-986-4734. | |||
| UD1 | COMPLETE | 09/04/2015 | 09/10/2015 |
| ZON | HOLD | 09/04/2015 | 09/04/2015 |
| Note: D. Ramirez Provide an elevation plan for the side of the building wall that will be replaced with glass windows. | |||
| ELEC | HOLD | 09/04/2015 | |
| Note: Please update to NEC 2011. -DC. Rewis 9864736 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 06/20/2016 |
| REVISION | ¤40.00 | 03/23/2016 |
| REINSPECTION FEE | ¤40.00 | 03/23/2016 |
| SITE PLAN 20 | ¤20.00 | 10/01/2015 |
| SURCHARGE FS 533.721 | ¤4.92 | 10/01/2015 |
| SURCHARGE - FS 468.631 | ¤4.92 | 10/01/2015 |
| ADMIN COMMERCIAL | ¤60.00 | 10/01/2015 |
| INSPECTION - COMMERCIAL ADD | ¤280.00 | 10/01/2015 |
| ELECTRIC FEE | ¤84.00 | 10/01/2015 |
| FIRE PLANS REVIEW | ¤25.00 | 10/01/2015 |
| PLAN CHECK FEE | ¤100.00 | 10/01/2015 |
| PLUMBING FEE | ¤84.00 | 10/01/2015 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤782.84 |