Permit #2015120068
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7081-00820-0470 |
| Block: 00820 |
| Subdivision: 2183 - SECTION 81-BERNARD MEADOWS-PALM HARBOR |
| Job Phone: 386-248-0033 |
| Location Address: 2 BLACKBERRY PL |
| Type: BIA - BUILDING INTERIOR EXTERIOR ALTERATION |
| Issue Date: 12/11/2015 |
| NOC: RECORDED |
| Applicant name: JEFFREY T WISE |
| Owner: PHILLIPS, FRANCES H |
|
Address 2 BALCKBERRY PL PALM COAST, FL 32137 |
| Lot: 0470 |
| Contracted Stated Job Value: ¤29,000.00 |
| Job Description: A/C- 4 TON, 15 SEER, WINDOWS, ELECTRIC |
| Type: CN |
Contractor
WISE BUILDERS LLC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
120 CARSWELL AVE HOLLY HILL, FL 32117 |
CGC055237 (Exp: 08/31/2026) | 386-248-0033 |
Sub Contractors
JAMES R DOOLEY
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
1550 GARDEN AVENUE HOLLY HILL, FL 32117 |
EC13005817 (Exp: 08/31/2026) | 386-672-4433 | 386-672-9793 |
KEVIN HENRY BEHRENS
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
1200 SOUTH NOVA ROAD DAYTONA BEACH, FL 32114 |
CAC054733 (Exp: 08/31/2026) | (386)761-7751 | (386) 258-0058 |
Inspection History
| Type | Request Date | Result | Inspector |
| BLD - BUILDING FINAL | 02/09/2016 | FINAL APPROVED | LMILLER |
| Note: THIS IS A REINSPECTION | |||
| BLD - BUILDING FINAL | 02/05/2016 | Disapproved - NO FEE | LMILLER |
| Note: THIS IS A REINSPECTION Inspection Resulted at 2/5/2016 1:06:52 PM GFCI``S IN GARAGE DO NOT TRIP WHEN TESTED. ALL RECEPTACLES IN GARAGES NEED TO BE ON GFCI NEC 210.8 (A) | |||
| BLD - BUILDING FINAL | 02/01/2016 | Disapproved -FEE REQUIRED | LMILLER |
| Note: Inspection Resulted at 2/1/2016 10:07:56 AM JOB SCOPE CALLS FOR INSTALLATION OF NEW GFCI CIRCUIT BREAKERS. NONE WE INSTALLED. COMPLETE JOB SCOPE PER APPROVED PAPERWORK. | |||
| ALL ROUGH | 01/27/2016 | APPROVED - AS NOTED | LMILLER |
| Note: Inspection Resulted at 1/27/2016 1:00:44 PM WILL LOOK AT OCTAGON WINDOWS IN MASTER BEDROOM AND MASTER BATH FOR FASTENERS AT FINAL |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 12/10/2015 | 12/10/2015 |
| Note: Released By: DREWIS | |||
| BLD | COMPLETE | 12/09/2015 | 12/09/2015 |
| Note: Released By: FREODICA Hold comments | |||
| BLD | HOLD | 12/02/2015 | 12/02/2015 |
| Note: Held By: FREODICA Held By: FREODICA Provide separate permit application for roof replacement per FBC 5th edi. 107.2.1. The permit application shall have Florida product approval of roofing material to be used and Roofing Worksheets. | |||
| ELEC | HOLD | 12/02/2015 | 12/02/2015 |
| Note: Held By: DREWIS Please provide floor plan depicting ADDITIONAL electrical being done per NEC 2011 Articles 210.52 & 440.14 signed by licensed electrical contractor being used. -DC. Rewis 986-4736 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 02/03/2016 |
| REMODEL/ADDITION/ACCES INSPECT | ¤40.00 | 12/11/2015 |
| SITE PLAN 20 | ¤20.00 | 12/11/2015 |
| SURCHARGE FS 533.721 | ¤3.82 | 12/11/2015 |
| SURCHARGE - FS 468.631 | ¤3.82 | 12/11/2015 |
| ADMIN FEE | ¤20.00 | 12/11/2015 |
| ELECTRIC FEE | ¤77.40 | 12/11/2015 |
| MECHANICAL FEE | ¤77.40 | 12/11/2015 |
| PLAN CHECK FEE | ¤40.00 | 12/11/2015 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤322.44 |