Permit #2016010683

Permit Details

Status: FINAL

Parcel Id: 07-11-31-5112-00000-0100
Block: 00000
Subdivision: 1164 - PINE LAKES INDUSTRIAL PARK
Job Phone: 386-238-1570
Location Address: 6 COMMERCE BLVD
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 02/29/2016
NOC: RECORDED
Applicant name: GARY LYNN ROBERTS
Owner: DESIGNS FOR HEALTH INC

Address

980 SOUTH STREET

SUFFELD, CT 06078

Lot: 0100
Contracted Stated Job Value: ¤125,000.00
Job Description: RAISE ELECTRICAL & HVAC
Type: CN

Contractor

COMMERCIAL CONSTRUCTION INC.
Status Location Address State License Number Phone Fax
ACTIVE

7 SUNSHINE BLVD

ORMOND BEACH, FL 32174

CGC059441 (Exp: 08/31/2026) 386-238-1570 386-238-1571

Sub Contractors

MIKE F WHALEY
Status Location Address State License Number Phone Fax
ACTIVE

804 Root Street

Daytona Beach, FL 32114

EC0001334 (Exp: 08/31/2026) (386) 252-2287 (386)257-1920
STEVEN KEITH JONES
Status Mailing Address State License Number Phone Fax
ACTIVE

345 MADISON AVE

DAYTONA BEACH, FL 32114

CMC057027 (Exp: 08/31/2026) (386)253-7774 (386)255-9431

Inspection History

Type Request Date Result Inspector
BUILDING FINAL 04/22/2016 FINAL APPROVED CMINI
ELECTRIC FINAL 04/21/2016 FINAL APPROVED RMARTIN
Note: THIS IS A REINSPECTION
FIRE FINAL 04/20/2016 APPROVED JHINDMAN
ELECTRIC FINAL 04/20/2016 CANCELLED BY APPLICANT RMARTIN
Note: THIS IS A REINSPECTION
ELECTRIC FINAL 04/19/2016 Disapproved -FEE REQUIRED RMARTIN
Note: Inspection Resulted at 4/19/2016 10:47:01 AM NEED APPROVED REVISION ON SITE FOR CKT CHANGE TO DIFF. PANEL AND ALSO NEED EXIT LIGHTS WORKING AND SAFED OFF
HVAC FINAL 04/18/2016 APPROVED - AS NOTED CMINI
Note: Inspection Resulted at 4/18/2016 3:25:14 PM CHECK BREAKER IN PANEL 15 MAX PER MOCP RATING ON ELEC. FINAL
ABOVE CEILING 04/18/2016 APPROVED CMINI
U - UTILITY COMMERCIAL FINAL 04/15/2016 FINAL APPROVED MBACON
MONOLITHIC SLAB 04/07/2016 APPROVED JCOLASANTI
Note: THIS IS A REINSPECTION
MONOLITHIC SLAB 04/06/2016 Disapproved -FEE REQUIRED CMINI
Note: Inspection Resulted at 4/6/2016 12:19:24 PM SUPER NOT ON JOB, DO NOT KNOW WHAT INSPECTION IS NEEDED ON
ELECTRIC 2ND ROUGH 04/01/2016 APPROVED - AS NOTED RMARTIN
Note: THIS IS A REINSPECTION Inspection Resulted at 4/1/2016 11:24:36 AM MARKED ON PLAN ALL CEILING BOXES GROUNDED
ELECTRIC 2ND ROUGH 03/10/2016 PARTIALLY APPROVED RMARTIN
Note: Inspection Resulted at 3/10/2016 11:51:27 AM WALLS ONLY MARKED ON PLAN,NEED REVISION BY FINAL ON OUTLET NEMBER AND RELOCATION
FRAMING 03/10/2016 APPROVED CMINI

Review History

Department Status Date In Date Out
ELEC COMPLETE 04/20/2016 04/20/2016
ELEC COMPLETE 03/23/2016 03/24/2016
MECH COMPLETE 02/24/2016 02/25/2016
BLD COMPLETE 02/24/2016 02/29/2016
ELEC COMPLETE 02/11/2016 02/11/2016
MECH HOLD 02/11/2016 02/15/2016
Note: 1. Identify the condenser unit's number to match with the submitted air handling units (AHUs) as previously requested for clarity per FBC 5th ed. 107.2.1. 2. The submitted existing AHU's capacity does not match with the distributed supply air based on CFMs of each individual unit. Coordinate per FBC 5th ed. 107.2.1. 3. Provide outdoor air supply for ventilation requirement to each existing AHU's 10,11,12,and 17 to comply with FBCM 5th ed. 403.2. 4. Previous comment item 3 shall be addressed. 3. Provide detail on how return air to packaged units would be accomplished as per Mechanical Scope Note 3. (FBC 5th ed.107.2.1.) . F.N.Reodica - 386-986-4734.
FI1 COMPLETE 02/11/2016 02/16/2016
BLD HOLD 02/11/2016 02/16/2016
Note: 1. Provide a detail for the construction of the new ADA ramp (concrete? how thick? any reinforcement?). 2. Provide a site plan that shows the location of the new striped crosswalk and what area is connected to it.. The ADA crosswalk must be Blue.3. Remove the Phase 2 ADA upgrades from sheet TBL from the plan.5th ed. FBC 107.2.1.J. Hindman 986-3784
BLD HOLD 01/29/2016 02/01/2016
Note: 1. Identify the required ADA upgrades or show ADA compliance per the 5th Edition of the Florida Building Code Existing Buildings section 806. and The 5th Edition of the Florida Building Code Accessibility 202.1. 2. Provide a Life Safety plan per the 5th Edition of the Florida Building Code 107.3.5. J. Hindman 986-3784.
ELEC HOLD 01/29/2016 01/29/2016
Note: Please provide specifications of work being done. -DC. Rewis 986-4736
FI1 HOLD 01/29/2016 02/01/2016
Note: 1. Provide a one hour separation between the storage and the business occupancy areas per the 5th edition of the Florida Fire prevention code Table 6.1.14.4.1(b). 2. Identify the materials that are to be stored on the racks.J. Hindman 986-3784.
MECH HOLD 01/29/2016 02/01/2016
Note: 1. Identify the existing hvac units (AHUs and condensers)/package units and their capacities in tons on mechanical plan covered by the scope of work for clarity per FBC 5th ed. 107.2.1. 2. Provide return air from shipping/receiving and break room areas as mentioned on mechanical scope notes 6 and 7 as plan does not show them (107.2.1) 3. Provide detail on how return air to packaged units/AHUs would be accomplished as per scope note 3. (107.2.1.) . F.N.Reodica - 386-986-4734.
PLUM COMPLETE 01/29/2016 02/01/2016
Note: Not applicable.
UD1 COMPLETE 01/29/2016 02/02/2016
ZON COMPLETE 01/29/2016 02/01/2016

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REVISION ¤40.00 04/21/2016
REVISION ¤40.00 04/19/2016
REINSPECTION FEE ¤40.00 04/19/2016
REINSPECTION FEE ¤40.00 04/19/2016
SITE PLAN 20 ¤20.00 02/29/2016
SURCHARGE FS 533.721 ¤7.22 02/29/2016
SURCHARGE - FS 468.631 ¤7.22 02/29/2016
ADMIN COMMERCIAL ¤60.00 02/29/2016
INSPECTION - COMMERCIAL ADD ¤875.00 02/29/2016
ELECTRIC FEE ¤135.00 02/29/2016
FIRE PLANS REVIEW ¤25.00 02/29/2016
MECHANICAL FEE ¤135.00 02/29/2016
PLAN CHECK FEE ¤143.75 02/29/2016
Fees Total Due: ¤0.00 Total Paid: ¤1,568.19