I want to search for...
Permit #2016040067
Permit Details
Status: COED
| Parcel Id: 07-11-31-7019-00240-0010 |
| CONDITIONED SPACE: 2807 sqft |
| GARAGE: 606 sqft |
| OPENED PORCH (WITH ROOF) : 635 sqft |
| OPENED PORCH (WITH ROOF) : 151 sqft |
| Total Square Footage: 4199 sqft |
| Block: 00240 |
| Subdivision: 2214 - SECTION 19-WYNNFIELD |
| Job Phone: (386)931-1917 |
| Location Address: 1 WATERFORD PL |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 04/13/2016 |
| NOC: RECORDED |
| Applicant name: BRAD MICHAEL THOMAS |
| Owner: BERTRAM, GARY & DOROTHY |
|
Address 914 HUDSON AVE PEEKSKILL, NY 10566 |
| Lot: 0010 |
| Contracted Stated Job Value: ¤280,000.00 |
| Job Description: SINGLE FAMILY RESIDENCE |
| Type: CN |
Contractor
AUBURN HOMES INC.
| Status | Location Address | State License Number | Phone |
| HOLD |
1 HARGROVE GRADE STE 1E PALM COAST, FL 32137 |
CGC1506292 (Exp: 08/31/2020) | (386)931-1917 |
Sub Contractors
STEPHEN COURTEAUX
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
85 North Yonge Street Ormond Beach, FL 32174 |
EC13001748 (Exp: 08/31/2026) | (386) 672-4900 | 386-676-7472 |
JOHN ROBERT BLEVINS JR
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
17 PORWYN LANE PALM COAST, FL 32164 |
CAC1816125 (Exp: 08/31/2026) | 386-585-8283 | 386-263-2096 |
HEATH EDWARD SANFORD
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
1351 HAZELNUT ST BUNNELL, FL 32110 |
CFC1427527 (Exp: 08/31/2026) | 386-445-2532 | 386-445-5575 |
YORDANIS GONZALEZ
| Status | Location Address | State License Number | Phone |
| ACTIVE |
33 RICKENBACKER DRIVE PALM COAST, FL 32164 |
CCC1328730 (Exp: 08/31/2026) | 386-804-4109 |
KEN DEPRINZIO
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
325 WALKER STREET HOLLY HILL, FL 32117 |
11351 (Exp: 08/31/2026) | 386-672-8494 | 386-673-7856 |
Inspection History
| Type | Request Date | Result | Inspector |
| U -UTILITY RESIDENTIAL FINAL | 01/06/2017 | FINAL APPROVED | MBACON |
| BLD - BUILDING FINAL | 01/05/2017 | FINAL APPROVED | JCOLASANTI |
| ROW FINAL | 01/04/2017 | APPROVED | CTROHA |
| Note: THIS IS A REINSPECTION WORK COMPLETE | |||
| FINAL APRON (AFTER POUR/DRIVEWAY) | 01/03/2017 | APPROVED | CTROHA |
| Note: THIS IS A REINSPECTION | |||
| ROW FINAL | 01/03/2017 | Disapproved -FEE REQUIRED | CTROHA |
| Note: THIS IS A REINSPECTION PLACE SOD IN ADJ PROPERTY SWALE (BAHIA SOD) PLANTING BEDS ARE IN THE ROW MUST BE BACK TO THE PROPERTY LINE BROKEN MITTERED END OF THE ROAD CROSSING AT THE CORNER NEEDS REPAIRED SEE PHOTOS | |||
| ROW FINAL | 12/28/2016 | CANCELLED BY APPLICANT | CTROHA |
| FINAL APRON (AFTER POUR/DRIVEWAY) | 12/28/2016 | CANCELLED BY APPLICANT | CTROHA |
| FINAL SURVEY (OFFICE USE ONLY) | 12/27/2016 | APPROVED | JHINDMAN |
| PRE-APRON (PRE-POUR/DRIVEWAY) | 12/08/2016 | APPROVED | CTROHA |
| Note: THIS IS A REINSPECTION READY FOR PAVERS | |||
| PRE-APRON (PRE-POUR/DRIVEWAY) | 11/22/2016 | PARTIALLY APPROVED | RGROSS |
| Note: APPROVED FOR CONCRETE POUR OVER PIPE ONLY. PAVER DRIVEWAY | |||
| ELECTRIC - EARLY POWER | 11/10/2016 | APPROVED - AS NOTED | RMARTIN |
| Note: THIS IS A REINSPECTION SPOKE TO DELL FPL RELEASED EARLY POWER 11:20 | |||
| ELECTRIC - EARLY POWER | 11/09/2016 | CANCELLED BY APPLICANT | RMARTIN |
| LATH/BRICK/ WATER BARRIER | 08/31/2016 | APPROVED | LMILLER |
| GRAVITY SEWER TEST | 08/30/2016 | APPROVED | JCOLASANTI |
| U - SEWER TIE IN | 08/30/2016 | APPROVED | JNICHOLS |
| INSULATION | 08/08/2016 | APPROVED | LMILLER |
| INSULATION | 08/05/2016 | Disapproved -FEE REQUIRED | LMILLER |
| Note: FIREBLOCKING R302.11 (4) PIPES, DUCTS, CABLES, AND WIRES AT CEILING AND FLOOR LEVEL (WITH APPROVED MATERIAL) (CIRCLED ON FLOOR PLAN | |||
| ALL ROUGH | 07/29/2016 | APPROVED - AS NOTED | JCOLASANTI |
| Note: need to fireblock chase....nail plate security wire | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 07/12/2016 | APPROVED - AS NOTED | JCOLASANTI |
| Note: THIS IS A REINSPECTION Inspection Resulted at 7/12/2016 10:30:22 AM MISSING STRAP AT REAR VALLEY. BLOCK AND STRAP. WILL CHECK AT ALL ROUGH. | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 06/30/2016 | Disapproved -FEE REQUIRED | JCOLASANTI |
| Note: Inspection Resulted at 6/30/2016 11:57:01 AM CONTINUOUS LOAD PATH FOR UPLIFT RESISTANCE FBC.. 802.1.9 (NEED TO PROVIDE DETAIL FOR VALLEY RAFTER CONNECTIONS.) | |||
| TIE BEAM / LINTEL | 05/31/2016 | APPROVED | LMILLER |
| Note: THIS IS A REINSPECTION | |||
| TIE BEAM / LINTEL | 05/27/2016 | Disapproved -FEE REQUIRED | LMILLER |
| Note: Inspection Resulted at 5/27/2016 10:14:51 AM OVERBEND DOWEL BAR FBC R606.13.3 EXCEPTION (MARKED IN 2 PLACES WITH GREEN PAINT, 1 INTERIOR 1 EXTERIOR OPPOSITE SIDES OF STRUCTURE) | |||
| FOUND SURVEY APPROVED (OFFICE) | 05/19/2016 | APPROVED | FREODICA |
| MONOLITHIC SLAB | 05/12/2016 | APPROVED | JCOLASANTI |
| Note: THIS IS A REINSPECTION | |||
| MONOLITHIC SLAB | 05/11/2016 | Disapproved -FEE REQUIRED | JCOLASANTI |
| Note: Inspection Resulted at 5/11/2016 9:46:18 AM FRONT AREA FOOTING NEEDS THREE VERTICAL BARS AND FOOTING NEEDS TO BE CORRECT DEPTH PER PLAN. FOOTING AT REAR PORCH AREA NEEDS TO BE CORRECT DEPTH PER PLAN DETAIL. MISSING DETAIL NUMBER 9 INTERIOR FOOTING ALL CIRCLED ON PLANS. DENSITY TEST CERTIFICATE MUST BE IN BOX BY NEXT INSPECTION. | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 05/10/2016 | APPROVED | JCOLASANTI |
Review History
| Department | Status | Date In | Date Out |
| SW1 | COMPLETE | 12/27/2016 | 12/27/2016 |
| Note: Released By: JHINDMAN final s | |||
| ZON | COMPLETE | 07/08/2016 | 07/08/2016 |
| BLD | COMPLETE | 07/07/2016 | 07/08/2016 |
| SW1 | COMPLETE | 05/19/2016 | 05/19/2016 |
| Note: Released By: FREODICA foundation survey | |||
| ZON | COMPLETE | 04/11/2016 | 04/12/2016 |
| BLD | COMPLETE | 04/04/2016 | 04/05/2016 |
| ELEC | COMPLETE | 04/04/2016 | 04/04/2016 |
| ENGIN1 | COMPLETE | 04/04/2016 | 04/06/2016 |
| MECH | COMPLETE | 04/04/2016 | 04/05/2016 |
| PLUM | COMPLETE | 04/04/2016 | 04/05/2016 |
| SW1 | COMPLETE | 04/04/2016 | 04/04/2016 |
| UD1 | COMPLETE | 04/04/2016 | 04/06/2016 |
| Note: See Notes | |||
| ZON | HOLD | 04/04/2016 | 04/07/2016 |
| Note: 1. Per LDC 5.04.C.5.d - Attached and detached garages must have a driveway extending for a minimum of 20' from the garage door to the property line. 2. Right of Way Utilization Agreement for paver driveway is required. This form must be signed by all persons on deed to property, witnessed and notarized. 3. Provide setback of circular driveway to front and right property lines to ensure it does not encroach into the front 5' easement and the 7.5' side property line. | |||
| URB | COMPLETE | 04/04/2016 | 04/05/2016 |
| Note: Saved trees will require a barricade before clearing. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 01/05/2017 |
| IMPACT FEE FIRE NONRESIDENTIAL | ¤212.80 | 12/09/2016 |
| IMPACT FEE PARKS | ¤849.24 | 12/09/2016 |
| IMPACT FEE SCHOOL | ¤3,600.00 | 12/09/2016 |
| IMPACT FEE TRANSPORTATION | ¤3,124.67 | 12/09/2016 |
| REINSPECTION FEE | ¤40.00 | 12/09/2016 |
| REINSPECTION FEE | ¤40.00 | 12/09/2016 |
| REINSPECTION FEE | ¤40.00 | 12/09/2016 |
| REVISION | ¤40.00 | 12/09/2016 |
| SITE PLAN 20 | ¤20.00 | 04/13/2016 |
| SURCHARGE FS 533.721 | ¤26.95 | 04/13/2016 |
| SURCHARGE - FS 468.631 | ¤26.95 | 04/13/2016 |
| STORM WATER PERMIT FEES | ¤80.00 | 04/13/2016 |
| ADMIN FEE | ¤20.00 | 04/13/2016 |
| ELECTRIC FEE | ¤281.40 | 04/13/2016 |
| MECHANICAL FEE | ¤281.40 | 04/13/2016 |
| PLAN CHECK FEE | ¤147.60 | 04/13/2016 |
| PLUMBING FEE | ¤281.40 | 04/13/2016 |
| RECORDING FEE REIMBURSE DOC | ¤52.50 | 04/13/2016 |
| NEW RESIDENTIAL INSPECTIONS | ¤738.00 | 04/13/2016 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤9,942.91 |