Permit #2016040089

Permit Details

Status: CANCEL

Parcel Id: 16-11-30-4915-00010-05F0
Block: 00010
Subdivision: 1150 - PALM COAST COMMERCIAL & INDUSTRIAL CENTER
Job Phone: 386-445-2532
Location Address: 15 HARGROVE LN
Type: CP - COMMERCIAL PLUMBING
NOC: RECORDED
Applicant name: HEATH EDWARD SANFORD
Owner: DISANTO, LOUIS & VIEIRA, LAUDELINO

Address

42 WESTMOUNT LANE

PALM COAST, FL 32164

Lot: 05F0
Contracted Stated Job Value: ¤3,200.00
Job Description: INSTALL 3-COMPARTMENT SINK, SERVICE SINK, UTILITY SINK, GREASE TRAP, ETC
Type: CN

Contractor

SANFORD PLUMBING INC
Status Location Address State License Number Phone Fax
ACTIVE

1351 HAZELNUT ST

BUNNELL, FL 32110

CFC1427527 (Exp: 08/31/2026) 386-445-2532 386-445-5575

Inspection History

Type Request Date Result Inspector
PLUMBING 1ST ROUGH
PLUMBING 2ND ROUGH
PLUMBING FINAL
U-GREASE INTERCEPTOR PRE-INSTALLATION
U-GREASE INTERCEPTOR INSTALLED/PLUMBED
U-GREASE INTERCEPTOR FLOW/DYE TESTED
U - UTILITY COMMERCIAL FINAL

Review History

Department Status Date In Date Out
ZON HOLD 05/25/2016 05/25/2016
Note: Per the Land Development Code Section 3-Table 3-4 Bakeries are only allowed in COM-1, COM-2, COM-3, OFC-1 and OFC-2. IND-1 areas will need to apply for a Special Exception to allow a bakery use. Please call me at 986-3750 so I can schedule you to meet with staff about the process.
PLUM HOLD 05/25/2016 05/31/2016
Note: Based on submitted plans and scope of work, change the type of permit application from commercial plumbing (CP) to commercial interior alteration (CIA). The new permit application shall be applied by Florida licensed building contractor with Florida licensed mechanical, plumbing and electrical sub-contractors, Similarly, plans shall be submitted either prepared by those subcontractors in each disciple with their signatures and license number or signed and sealed by design professional for review, construction and inspection per FBC 5th ed. 107.2.1./FS 489. F.N.Reodica-386-986-4734.
UD1 HOLD 05/25/2016 05/25/2016
Note: Floor plan and riser does not show the grease trap. Provide the approved grease interceptor exemption form. Provide specifications on the grease trap proposed, exemption form has contact information along with requirements. Contact Chris for the required exemption form 986-2384. Provide completed DBPR form.
UD1 HOLD 04/05/2016 04/06/2016
Note: Provide floor plan showing location of plumbing. Provide information on the use. Based on what is proposed it appears food prep or service may be proposed. If food prep is proposed a grease interceptor exemption form will be required. Provide specifications on the grease trap proposed. CJohnson 986-2384
PLUM HOLD 04/04/2016 04/05/2016
Note: Provide plan showing the location of the plumbing fixtures to be installed to match with submitted riser diagram per FBC 5th ed. 107.2.1. Also, clarify if the fixtures are for replacement of existing or new installation. F.N.Reodica-386-986-4734
ZON CANCEL
UD1 CANCEL
PLUM CANCEL