I want to search for...
Permit #2016040508
Permit Details
Status: CANCEL
| Parcel Id: 07-11-31-7013-RP N -0070 |
| Block: RP N |
| Subdivision: 2249 - ST JOE BUSINESS CENTER |
| Job Phone: (386)986-2224 |
| Location Address: 4982 PALM COAST PKWY NW |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| NOC: NO DOCUMENTATION |
| Applicant name: WILLIAM P WHITLEY III |
| Owner: ST JOE BUSINESS CENTER INC |
|
Address 4 HICKORY DRIVE OLD BROOKVILLE, NY 11545 |
| Lot: 0070 |
| Contracted Stated Job Value: ¤30,000.00 |
| Job Description: UNIT # 8 - 9 "CLUB MIRAGE" |
| Type: CN |
Contractor
WHITLEY BUILDERS LLC
| Status | Location Address | State License Number | Phone |
| CANCEL |
6 BUTTONWELL LANE PALM COAST, FL 32137 |
CBC1255213 (Exp: 08/31/2018) | (386)986-2224 |
Sub Contractors
JOHN EDWARD GAMBONE
| Status | Location Address | Mailing Address | State License Number | Phone |
| ACTIVE |
15 HARGROVE LN PALM COAST, FL 32137 |
1G PALM COAST, FL 32137 |
EC13006037 (Exp: 08/31/2026) | 386-586-9144 |
JOHN ROBERT BLEVINS JR
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
17 PORWYN LANE PALM COAST, FL 32164 |
CAC1816125 (Exp: 08/31/2026) | 386-585-8283 | 386-263-2096 |
LEONARD EDWARD GASPARY
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
400 N US HWY 1 HOLLY HILL , FL 32117 |
CFC057799 (Exp: 08/31/2026) | 386-672-8494 | 386-673-7856 |
Inspection History
| Type | Request Date | Result | Inspector |
| ABOVE CEILING | |||
| BUILDING FINAL | |||
| FIRE FINAL | |||
| U - UTILITY COMMERCIAL FINAL |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 05/18/2016 | 05/18/2016 |
| PLUM | HOLD | 05/18/2016 | 05/18/2016 |
| Note: Repeat comment Previous comment item 2 shall be addressed. 2. Hand sink and lavatories shall be connected and vented per FBCP 5th ed. 905.3/905.4. Please note the comment above refers to 3 lavatories upstream of mop sink and a hand sink downstream of 3- compartment sink. | |||
| ELEC | COMPLETE | 05/05/2016 | 05/06/2016 |
| BLD | COMPLETE | 05/05/2016 | 05/05/2016 |
| FI1 | COMPLETE | 05/05/2016 | 05/05/2016 |
| MECH | HOLD | 05/05/2016 | 05/06/2016 |
| Note: Response to previous comments 2 and 4 need more clarifications. See additional comment. 2. Identify the air handling units (AHU(s) ) on hvac plan clarity per FBC 5th ed. 107.2.1. Comment: Name designation of air handling units shall be indicated on plan to match with those on load calculations. 4. Provide hvac equipment specifications as to cooling capacity, sensible, latent and efficiency to determine if they can handle the calculated loads per FBCEC 5th ed. C403.2.1. F.N.Reodica-386-986-4734. Comment: The capacity of hvac units exceeds the 40% of calculated total cooling load which does not comply with FBCEC 5th ed. C403.2.2. | |||
| PLUM | HOLD | 05/05/2016 | 05/09/2016 |
| Note: Previous comment item 2 shall be addressed. 2. Hand sink and lavatories shall be connected and vented per FBCP 5th ed. 905.3/905.4. | |||
| BLD | HOLD | 04/15/2016 | 04/15/2016 |
| Note: 1.Provide accessibility compliance at the bar and any seating areas per the 5th ed. FBC existing Building 1012.8 and 5th ed. FBC accessibility 202.1. 2.Provide exit doors that comply with the 5th ed. FBC 1008.1.10. J. Hindman 986-3784. | |||
| ELEC | HOLD | 04/15/2016 | 04/15/2016 |
| Note: Please depict existing lighting and provide lighting to storage area, NEC 2011 210.70. -DC. Rewis 986-4736 | |||
| FI1 | HOLD | 04/15/2016 | 04/15/2016 |
| Note: 1. Provide dimensions for the non-fixed seating to comply with The Florida Fire Prevention code 101 12.2.5. for aisle accessways and aisles serving seating at tables. J. Hindman 986-3784. | |||
| MECH | HOLD | 04/15/2016 | 04/20/2016 |
| Note: 1. Provide signature and license number of hvac contractor on hvac plan per FBC 5th ed. 107.2.1 2. Identify the air handling units (AHU(s) ) on hvac plan and indicate if they are existing or new units for clarity per FBC 5th ed. 107.2.1. 3. Provide make up air or outdoor air duct layout including duct sizes for each AHU per FBCM 5th ed. 403.2. 4. Provide hvac equipment specifications as to cooling capacity, sensible, latent and efficiency to determine if they can handle the calculated loads per FBCEC 5th ed. C403.2.1. F.N.Reodica-386-986-4734. | |||
| PLUM | HOLD | 04/15/2016 | 04/20/2016 |
| Note: 1. Provide plumbing plan or layout to determine that the riser diagram matches the plan for clarity per FBC 5th ed. 107.2.1. 2. Hand sink and lavatories shall be connected and vented per FBCP 5th ed. 905.3/905.4. 3. Provide vent for the urinal per FBCP 5th ed. 910.1. F.N.Reodica-386-986-4734. | |||
| UD1 | COMPLETE | 04/15/2016 | 04/18/2016 |
| ZON | COMPLETE | 04/15/2016 | 04/15/2016 |
| SW1 | COMPLETE | 04/15/2016 | 04/15/2016 |
| PLUM | CANCEL |