I want to search for...
Permit #2016070144
Permit Details
Status: COED
| Parcel Id: 16-11-30-4915-00010-05F0 |
| Block: 00010 |
| Subdivision: 1150 - PALM COAST COMMERCIAL & INDUSTRIAL CENTER |
| Job Phone: 386-445-9055 |
| Location Address: 15 HARGROVE LN |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 09/16/2016 |
| NOC: RECORDED |
| Applicant name: LUIS JORGE MEDEIROS |
| Owner: DISANTO, LOUIS & VIEIRA, LAUDELINO |
|
Address 42 WESTMOUNT LANE PALM COAST, FL 32164 |
| Lot: 05F0 |
| Contracted Stated Job Value: ¤10,000.00 |
| Job Description: SUITE 5-F-- BUILDOUT FOR BAKERY OVENS & GREASE TRAP- "LUSO AMERICA CAFE & BAKERY" |
| Type: CN |
Contractor
SUN STATE CUSTOM BUILDERS, LLC
| Status | Location Address | State License Number |
| CANCEL |
946 SHADICH DRIVE ORANGE CITY, FL |
CGC1519145 (Exp: 08/31/2022) |
Sub Contractors
JONATHAN M PEARSON
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
209 N FORSYTH ST BUNNELL, FL 32110 |
CFC1425941 (Exp: 08/31/2026) | 386-597-0944 | 386-437-4996 |
JOHN EDWARD GAMBONE
| Status | Location Address | Mailing Address | State License Number | Phone |
| ACTIVE |
15 HARGROVE LN PALM COAST, FL 32137 |
1G PALM COAST, FL 32137 |
EC13006037 (Exp: 08/31/2026) | 386-586-9144 |
JOHN ROBERT BLEVINS JR
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
17 PORWYN LANE PALM COAST, FL 32164 |
CAC1816125 (Exp: 08/31/2026) | 386-585-8283 | 386-263-2096 |
Inspection History
| Type | Request Date | Result | Inspector |
| U - UTILITY COMMERCIAL FINAL | 01/10/2017 | FINAL APPROVED | JNICHOLS |
| BUILDING FINAL | 12/29/2016 | APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION | |||
| FIRE FINAL | 11/22/2016 | FINAL APPROVED | JHINDMAN |
| Note: THIS IS A REINSPECTION PER CUSTOMERS | |||
| FIRE FINAL | 11/09/2016 | Disapproved -FEE REQUIRED | JHINDMAN |
| Note: 1. batteries in emergency lights do not work. 5th ed. FFPC 101 7.9. 2. seal penetrations in ceiling at electrical cables 5th ed. FFPC 101 8.1 | |||
| BUILDING FINAL | 11/09/2016 | Disapproved - NO FEE | JHINDMAN |
| Note: hood permit has not been issued and inspected for the duct and exhaust fan that has been installed. 5th ed. FBC 105.1. | |||
| ELECTRIC FINAL | 11/08/2016 | FINAL APPROVED | RMARTIN |
| PLUMBING FINAL | 10/17/2016 | APPROVED | CMINI |
| ELECTRIC 2ND ROUGH | 10/11/2016 | APPROVED | JHINDMAN |
| PLUMBING 2ND ROUGH | 10/04/2016 | PARTIALLY APPROVED | CMINI |
| Note: 1st rough | |||
| U-GREASE INTERCEPTOR FLOW/DYE TESTED | 10/04/2016 | APPROVED | JNICHOLS |
| U-GREASE INTERCEPTOR PRE-INSTALLATION | 09/29/2016 | APPROVED | DSPENCER |
| U-GREASE INTERCEPTOR INSTALLED/PLUMBED | 09/29/2016 | APPROVED | DSPENCER |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 09/13/2016 | 09/13/2016 |
| MECH | HOLD | 08/26/2016 | 08/30/2016 |
| Note: Review comment based submitted correction dated 8-26-16: 1. Clarify the location of make up air for the new work area as floor plan shows the air intake opening penetrates through an existing tenant separation wall and not from the outside wall per FBC 5th ed. 107.2.1. 2. Provide heating for the new work area per FBCM 5th ed. 309. 3. Provide gas contractor and gas riser diagram for the oven with signature and license number of gas contractor per FS 489/FBC 5th ed. 107.2.1. 4. Clarify the capacity of the make up air and coordinate with the required ventilation for the gas oven per manufacturer's installation instructions FBC 5th ed. 107.2.1.F.Reodica -386-986-4734. | |||
| PLUM | COMPLETE | 08/04/2016 | 08/09/2016 |
| MECH | HOLD | 08/04/2016 | 08/09/2016 |
| Note: Previous comment item 2 shall be addressed. 2. Provide existing hvac duct layout to comply with FBC existing building 5th ed. 809. F.Reodica-386-986-4734. Note: Additional comments might be added for additional information if existing hvac system can not handle the new converted space. | |||
| ELEC | COMPLETE | 08/04/2016 | 08/05/2016 |
| UD1 | COMPLETE | 08/04/2016 | 08/05/2016 |
| ZON | COMPLETE | 08/04/2016 | 08/08/2016 |
| BLD | COMPLETE | 08/04/2016 | 08/08/2016 |
| FI1 | COMPLETE | 08/04/2016 | 08/08/2016 |
| BLD | HOLD | 07/07/2016 | 07/14/2016 |
| Note: 1. Provide correct occupancy types. (factory-1 and mercantile) per 5th edition Florida building code 306 and 309. 2. Provide a bathroom door that meets 5th edition Florida Building code Accessibility 603.2.3 The door cannot swing into the required clear floor space for a fixture. J. Hindman 986-3784. | |||
| ELEC | HOLD | 07/07/2016 | 07/08/2016 |
| Note: Mixer roller needs a disconnect, NEC 2011 422 part three. -DC. Rewis 986-4736 | |||
| FI1 | HOLD | 07/07/2016 | 07/14/2016 |
| Note: 1.Remove the exit sign at the overhead doo rand relocate it to the bakery side of the office door. The overhead door does not meet the requirements for an Exit door 5th ed. FFPC 7.2.1. J. Hindman 986-3784. | |||
| MECH | HOLD | 07/07/2016 | 07/14/2016 |
| Note: 1. Provide separate permit for oven hood per FBC 5th ed. 107.2.1. 2. Provide existing hvac duct layout to comply with FBC existing building 5th ed. 809. F.Reodica-386-986-4734. | |||
| PLUM | HOLD | 07/07/2016 | 07/14/2016 |
| Note: 1. Provide plumbing riser diagrams (sanitary and domestic hot and cold) water per FBC 5th ed. 107.3.5. F.Reodica -386-986-4734. | |||
| UD1 | HOLD | 07/07/2016 | 07/11/2016 |
| Note: Provide approved grease interceptor exemption form and grease trap specifications. Contact me for exemption form. Provide completed DBPR form. CJohnson 386-986-2384 | |||
| ZON | HOLD | 07/07/2016 | 07/11/2016 |
| Note: Per the Land Development Code this use is allowed by Special Exception. In order to allow this use a Special Exception application must be applied for, reviewed and heard at the next applicable Planning Board hearing. Please call Damaris Ramirez at 986-3750 for an application and a checklist of items that will be needed for review prior to scheduling a public hearing. | |||
| SW1 | COMPLETE | 07/07/2016 | 07/07/2016 |
| PLUM | HOLD | 07/14/2016 | |
| Note: 1. Provide plumbing riser diagrams (sanitary and domestic hot and cold) water either prepared by plumbing contractor with signature and license number or design professional per FBC 5th ed. 107.3.5./ 107.2.1. 2. Provide service sink per FBCP 5th ed. 403. F.Reodica -386-986-4734. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 01/09/2017 |
| SITE PLAN 20 | ¤20.00 | 09/16/2016 |
| SURCHARGE FS 533.721 | ¤5.67 | 09/16/2016 |
| SURCHARGE - FS 468.631 | ¤5.67 | 09/16/2016 |
| ADMIN COMMERCIAL | ¤60.00 | 09/16/2016 |
| INSPECTION - COMMERCIAL ADD | ¤70.00 | 09/16/2016 |
| CONTRACTOR CHANGE | ¤40.00 | 09/16/2016 |
| ELECTRIC FEE | ¤66.00 | 09/16/2016 |
| FIRE PLANS REVIEW | ¤25.00 | 09/16/2016 |
| MECHANICAL FEE | ¤66.00 | 09/16/2016 |
| PLAN CHECK FEE | ¤100.00 | 09/16/2016 |
| PLUMBING FEE | ¤66.00 | 09/16/2016 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤564.34 |