Permit Details
Status: COED
| Parcel Id: 07-11-31-1090-00000-00B0 |
| Block: 00000 |
| Subdivision: 1228 - SOUTHWEST QUADRANT |
| Job Phone: 386-447-1402 |
| Location Address: 160 CYPRESS POINT PKWY |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 11/23/2016 |
| NOC: Unknown |
| Applicant name: RONALD ERIC PHILLIPS |
| Owner: CYPRESS POINT 160 LLC |
|
Address 3920 RCA BOULEVARD PALM BEACH GARDENS, FL 33410 |
|
Address SUITE 2002 PALM BEACH GARDENS, FL 33410 |
| Lot: 00B0 |
| Contracted Stated Job Value: ¤2,000.00 |
| Job Description: C 105 - PLUMBING WORK FOR SERVICE & MAIN SINKS "MARIO'S BAKERY & COFFEE SHOP" |
| Type: CN |
Contractor
PHILLIPS COASTAL CONSTRUCTION, INC
| Status | Location Address | State License Number | Phone |
| CANCEL |
58 BUTTERFIELD DRIVE PALM COAST, FL 32137 |
CGC1506412 (Exp: 08/31/2024) | 386-447-1402 |
Sub Contractors
HEATH EDWARD SANFORD
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
1351 HAZELNUT ST BUNNELL, FL 32110 |
CFC1427527 (Exp: 08/31/2026) | 386-445-2532 | 386-445-5575 |
Inspection History
| Type | Request Date | Result | Inspector |
| U - UTILITY COMMERCIAL FINAL | 01/06/2017 | FINAL APPROVED | JNICHOLS |
| BUILDING FINAL | 01/05/2017 | FINAL APPROVED | CMINI |
| PLUMBING FINAL | 01/05/2017 | APPROVED | CMINI |
| ELECTRIC FINAL | 01/05/2017 | FINAL APPROVED | RMARTIN |
| ABOVE CEILING | 12/19/2016 | APPROVED | CMINI |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 12/21/2016 | 12/27/2016 |
| BLD | COMPLETE | 11/17/2016 | 11/22/2016 |
| PLUM | COMPLETE | 11/17/2016 | 11/22/2016 |
| ELEC | COMPLETE | 11/07/2016 | 11/07/2016 |
| BLD | HOLD | 11/07/2016 | 11/08/2016 |
| Note: 1. Based on the occupant load of 47 this plan meets the exception for an Assembly-2 occupancy and can be classified as a Business occupancy. The plans need to reflect the correct occupancy as an A-2 occupancy will not work for the exit requirements as you cannot exit thru a kitchen. 5th edition Florida building code 303.1.1 and 1014.2. J. Hindman 986-3784.2nd request. (Remove exit sign at kitchen and change Occupancy to Business exception.). | |||
| PLUM | HOLD | 11/07/2016 | 11/08/2016 |
| Note: 1. Provide domestic water riser diagram (hot and cold) per FBC 5th ed. 107.3.5 as previously requested. 2. Revise the occupancy classification to business and occupant load calculation FBC 5th ed. 302 3. Provide vent for the mop sink per FBCP 910.1. F.Reodica-386-986-4734. | |||
| MECH | COMPLETE | 11/07/2016 | 11/08/2016 |
| Note: No change in hvac sytem. | |||
| MECH | HOLD | 10/19/2016 | 10/19/2016 |
| Note: Provide hvac plan and hvac contractor per FS 489. The addition of wall and door with full height up to the existing roof system between kitchen area and customer area create an unbalance return air to the hvac unit per FBCM 5th ed. 601.5. F.Reodica - 386-986-4734. | |||
| ELEC | HOLD | 10/18/2016 | 10/19/2016 |
| Note: 1. Provide electrical load calculations per 2011 NEC art. 220. J. Hindman 986-3784. | |||
| BLD | HOLD | 10/18/2016 | 10/19/2016 |
| Note: 1. Based on the occupant load of 47 this plan meets the exception for an Assembly-2 occupancy and can be classified as a Business occupancy. The plans need to reflect the correct occupancy as an A-2 occupancy will not work for the exit requirements as you cannot exit thru a kitchen. 5th edition Florida building code 303.1.1 and 1014.2. J. Hindman 986-3784. | |||
| PLUM | HOLD | 10/18/2016 | 10/19/2016 |
| Note: 1. Sanitary riser diagram shall include the hand sink adjacent to unisex bathroom and domestic water riser diagram (hot and cold) shall be provided as previously requested per FBC 5th ed. 107.3.5. 2. Provide occupancy classification and occupant load calculation to determine if separate restroom facilities are needed per FBC 5th ed. 302/FBCP 5th ed. 403.2F.Reodica-386-986-4734. | |||
| PLUM | HOLD | 08/25/2016 | 08/26/2016 |
| Note: 1. Provide sanitary and domestic water (hot and cold) riser diagrams per FBC 5th ed. 107.3.5. 2. Provide occupancy classification and occupant load calculation to determine if separate restroom facilities are needed per FBC 5th ed. 302/FBCP 5th ed. 403.2. F.Reodica -386-986-4734. | |||
| BLD | HOLD | 08/25/2016 | 08/25/2016 |
| Note: 1. Provide a complete set of plans for the changes to this unit as already stated under permit application number 2016060705. The floorplan does not match what was existing under the previous tenants permit. 2. the life safety plan must show the occupant load and must show all equipment, fixtures and furnishings. 5th ed. FBC 107.2.1. J. Hindman 986-3784. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REVISION | ¤40.00 | 01/05/2017 |
| SITE PLAN 20 | ¤20.00 | 11/23/2016 |
| SURCHARGE FS 533.721 | ¤3.62 | 11/23/2016 |
| SURCHARGE - FS 468.631 | ¤3.62 | 11/23/2016 |
| ADMIN COMMERCIAL | ¤60.00 | 11/23/2016 |
| INSPECTION - COMMERCIAL ADD | ¤50.00 | 11/23/2016 |
| FIRE PLANS REVIEW | ¤25.00 | 11/23/2016 |
| PLAN CHECK FEE | ¤100.00 | 11/23/2016 |
| PLUMBING FEE | ¤61.20 | 11/23/2016 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤363.44 |