Permit #2016100981

Permit Details

Status: FINAL

Parcel Id: 48-11-31-1700-00000-0200
Block: 00000
Subdivision: 2086 - ESTATES AT GRAND HAVEN PHASE I
Job Phone: (386)445-4747
Location Address: 19 NATIVE OAK CT
Type: PO - POOL
Issue Date: 12/09/2016
NOC: RECORDED
Applicant name: LAWRENCE PATRICK VANDIVIER
Owner: JENNINGS, KAREN K

Address

TRUSTEE

GRATHAM, NH 03753

Address

PO BOX 738

GRATHAM, NH 03753

Lot: 0200
Contracted Stated Job Value: ¤28,000.00
Job Description: IN-GROUND SWIMMING POOL
Type: CN

Contractor

COUNTRY CLUB POOLS & SPAS
Status Location Address State License Number Phone Fax
INACTIVE

4444 N. OCEANSHORE BLVD

PALM COAST, FL 32137

CPC057239 (Exp: 08/31/2024) (386)445-4747 (386)445-5955

Sub Contractors

BRIAN THOMAS KULL
Status Location Address State License Number Phone Fax
ACTIVE

18 STRAFORD PLACE

PORT ORANGE, FL 32128

CGC1504924 (Exp: 08/31/2026) 386-682-9554 (386)258-8042
STEVEN DUANE DENSLOW
Status Location Address State License Number Phone Fax
ACTIVE

317 RIO PINR DR

Ormond Beach, FL 32174

EC0001678 (Exp: 08/31/2026) 386-233-1553 386-673-5994
PATTI MULLIGAN
Status Location Address State License Number Phone Fax
DECEASED

2803 REIS ST

PALATKA, FL 32177

21948 (Exp: 07/10/2021) 386-698-1033 386-698-1077

Inspection History

Type Request Date Result Inspector
POOL FINAL 01/30/2018 FINAL APPROVED CMINI
U -UTILITY RESIDENTIAL FINAL 01/30/2018 FINAL APPROVED LFITZGERALD
FINAL SURVEY (OFFICE USE ONLY) 01/08/2018 APPROVED DREWIS
ROW DAMAGE 11/15/2017 APPROVED RGROSS
ELECTRIC AND ALARM 05/18/2017 APPROVED RMARTIN
Note: THIS IS A REINSPECTION
ELECTRIC AND ALARM 05/17/2017 Disapproved -FEE REQUIRED RMARTIN
Note: FEEDERS SUPPLYING POOL PANEL NEEDS TO BE INSTALLED PER NEC.680.25 1 ALSO THE SCREEN ENCLOSURE NEEDS TO BE BONDED PER NEC. 680.26
POOL DECK 03/06/2017 APPROVED - AS NOTED LMILLER
Note: INSPECTORS NOTE: HANDRAILS AND OR LADDERS WERE ATTACHED TO BONDING AT THIS DECK INSPECTION
POOL DECK 02/15/2017 APPROVED - AS NOTED LMILLER
Note: THIS IS A REINSPECTION INSPECTORS NOTE: NO HANDRAILS OR LADDERS ATTACHED TO BONDING AT POOL DECK INSPECTION
POOL DECK 02/10/2017 Disapproved -FEE REQUIRED LMILLER
Note: 1. INSPECTORS NOTE: NO HANDRAILS OR LADDERS ATTACHED TO BONDING AT POOL DECK INSPECTION 2. EQUIPOTENTIAL BONDING; DISTANCE FROM INSIDE POOL WALL, E4204.2 NUMBER 2, 2.2.4 THE REQUIRED CONDUCTOR SHALL BE 18 TO 24 INCHES FROM THE INSIDE OF THE POOL WALL 3. EQUIPOTENTIAL BONDING; BURIAL DEPTH, E4204.2 NUMBER 2, 2.2.5 4 TO 6 INCHES BELOW SUBGRADE 4.PRESSURE TEST , R4501.12.1 ALL POOL PIPING SHALL BE TESTED AND PROVED TIGHT TO THE ADMINISTRATIVE AUTHORITY, UNDER A STATIC WATER OR AIR PRESSURE TEST OF NOT LESS THAN 35(psi) 5. CLEARANCE FROM EARTH AND WEATHER R606.13.5
STEEL AND GROUND 12/12/2016 APPROVED LMILLER

Review History

Department Status Date In Date Out
SW1 COMPLETE 01/08/2018 01/08/2018
Note: Released By: DREWIS final s
ZON COMPLETE 12/02/2016 12/02/2016
BLD COMPLETE 12/02/2016 12/08/2016
BLD HOLD 10/27/2016 10/28/2016
Note: 1. Provide the correct electrical design code (2011 NEC). 2. On the energy form Provide the correct minimum return pipe size per the pipe size chart (1.5").APSP-15 J. Hindman 986-3784.
SW1 COMPLETE 10/27/2016 10/27/2016
ZON HOLD 10/27/2016 10/27/2016
Note: Site plan must show pool equipment placement, dimensions and setbacks.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 11/14/2017
REINSPECTION FEE ¤40.00 11/14/2017
SITE PLAN 20 ¤20.00 12/09/2016
SURCHARGE FS 533.721 ¤3.60 12/09/2016
SURCHARGE - FS 468.631 ¤3.60 12/09/2016
STORM WATER PERMIT FEES ¤80.00 12/09/2016
ADMIN FEE ¤20.00 12/09/2016
PERMIT FEE ¤160.00 12/09/2016
PLAN CHECK FEE ¤40.00 12/09/2016
Fees Total Due: ¤0.00 Total Paid: ¤407.20