I want to search for...
Permit #2016120760
Permit Details
Status: COED
| Parcel Id: 06-12-31-5825-00010-0303 |
| Block: 00010 |
| Subdivision: 2111 - TOWN CENTER PHASE II |
| Job Phone: (386)677-8736 |
| Location Address: 145 CITY PL BLDG 1 |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 01/23/2017 |
| NOC: RECORDED |
| Applicant name: LEONARD MARINACCO |
| Owner: CITY CENTRE OF PALM COAST INC |
|
Address STE 301 PALM COAST, FL 32164 |
|
Address 145 CITY PL PALM COAST, FL 32164 |
| Lot: 0303 |
| Contracted Stated Job Value: ¤42,000.00 |
| Job Description: SUITE 303- INTERIOR BUILDOUT |
| Type: CN |
Contractor
BOMAR CONSTRUCTION INC
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
27 S ORCHARD STREET ORMOND BEACH, FL 32174 |
CGC015648 (Exp: 08/31/2022) | (386)677-8736 | (386)677-7726 |
Sub Contractors
STEVEN DUANE DENSLOW
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
317 RIO PINR DR Ormond Beach, FL 32174 |
EC0001678 (Exp: 08/31/2026) | 386-233-1553 | 386-673-5994 |
STEVEN KEITH JONES
| Status | Mailing Address | State License Number | Phone | Fax |
| ACTIVE |
345 MADISON AVE DAYTONA BEACH, FL 32114 |
CMC057027 (Exp: 08/31/2026) | (386)253-7774 | (386)255-9431 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC 2ND ROUGH | 03/30/2017 | APPROVED | RMARTIN |
| Note: THIS IS A REINSPECTION | |||
| ELECTRIC FINAL | 03/30/2017 | APPROVED | RMARTIN |
| BUILDING FINAL | 03/30/2017 | FINAL APPROVED | JHINDMAN |
| FIRE FINAL | 03/30/2017 | APPROVED | JHINDMAN |
| U - UTILITY COMMERCIAL FINAL | 03/27/2017 | FINAL APPROVED | LFITZGERALD |
| HVAC FINAL | 03/27/2017 | APPROVED | JHINDMAN |
| ABOVE CEILING | 03/27/2017 | APPROVED | JHINDMAN |
| ELECTRIC 2ND ROUGH | 03/09/2017 | APPROVED - AS NOTED | RMARTIN |
| Note: WALLS ONLY | |||
| HVAC ROUGH | 03/08/2017 | APPROVED | JHINDMAN |
| Note: PER CONTRACTOR | |||
| ELECTRIC 2ND ROUGH | 03/08/2017 | Disapproved -FEE REQUIRED | RMARTIN |
| Note: NEED TO PHASE CONDUCTORS IN SWITCH BOXES THAT ARE HOT NEC 310.110, NEED TO MAKE JOINTS UP IN BOXES | |||
| FRAMING | 03/08/2017 | APPROVED | JHINDMAN |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 03/29/2017 | 03/29/2017 |
| MECH | COMPLETE | 01/19/2017 | 01/19/2017 |
| MECH | HOLD | 01/04/2017 | 01/13/2017 |
| Note: Clarify the outdoor or fresh air requirement as plan shows existing 6" duct thru roof, existing fresh air roof cap, existing 8" fresh air and new 6" fresh air duct between suite 302 ans 303 per FBC 5th ed. 107.2.1. F.Reodica - 386-986-4734. | |||
| BLD | COMPLETE | 12/16/2016 | 12/21/2016 |
| ELEC | COMPLETE | 12/16/2016 | 12/21/2016 |
| FI1 | COMPLETE | 12/16/2016 | 12/21/2016 |
| MECH | HOLD | 12/16/2016 | 12/21/2016 |
| Note: 1. Provide the capacity of existing hvac units to determine that it match with the distributed supply air shown on hvac plan per FBC 5th ed. 107.2.1. | |||
| PLUM | COMPLETE | 12/16/2016 | 12/21/2016 |
| UD1 | COMPLETE | 12/16/2016 | 12/19/2016 |
| ZON | COMPLETE | 12/16/2016 | 12/20/2016 |
| SW1 | COMPLETE | 12/16/2016 | 12/21/2016 |
| Note: Review not required. MEP only |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REVISION | ¤40.00 | 03/29/2017 |
| REINSPECTION FEE | ¤40.00 | 03/28/2017 |
| SITE PLAN 20 | ¤20.00 | 01/23/2017 |
| SURCHARGE FS 533.721 | ¤5.26 | 01/23/2017 |
| SURCHARGE - FS 468.631 | ¤5.26 | 01/23/2017 |
| ADMIN COMMERCIAL | ¤60.00 | 01/23/2017 |
| INSPECTION - COMMERCIAL ADD | ¤294.00 | 01/23/2017 |
| ELECTRIC FEE | ¤85.20 | 01/23/2017 |
| MECHANICAL FEE | ¤85.20 | 01/23/2017 |
| PLAN CHECK FEE | ¤100.00 | 01/23/2017 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤734.92 |