I want to search for...

Permit #2016120762

Permit Details

Status: COED

Parcel Id: 06-12-31-5825-00010-0302
Block: 00010
Subdivision: 2111 - TOWN CENTER PHASE II
Job Phone: (386)677-8736
Location Address: 145 CITY PL BLDG 1
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 01/13/2017
NOC: RECORDED
Applicant name: LEONARD MARINACCO
Owner: CITY CENTRE OF PALM COAST INC

Address

STE 301

PALM COAST, FL 32164

Address

145 CITY PL

PALM COAST, FL 32164

Lot: 0302
Contracted Stated Job Value: ¤45,000.00
Job Description: SUITE 302- INTERIOR BUILDOUT
Type: CN

Contractor

BOMAR CONSTRUCTION INC
Status Location Address State License Number Phone Fax
INACTIVE

27 S ORCHARD STREET

ORMOND BEACH, FL 32174

CGC015648 (Exp: 08/31/2022) (386)677-8736 (386)677-7726

Sub Contractors

STEVEN DUANE DENSLOW
Status Location Address State License Number Phone Fax
ACTIVE

317 RIO PINR DR

Ormond Beach, FL 32174

EC0001678 (Exp: 08/31/2026) 386-233-1553 386-673-5994
STEVEN KEITH JONES
Status Mailing Address State License Number Phone Fax
ACTIVE

345 MADISON AVE

DAYTONA BEACH, FL 32114

CMC057027 (Exp: 08/31/2026) (386)253-7774 (386)255-9431

Inspection History

Type Request Date Result Inspector
BUILDING FINAL 02/20/2017 APPROVED JHINDMAN
FIRE FINAL 02/20/2017 APPROVED JHINDMAN
U - UTILITY COMMERCIAL FINAL 02/20/2017 FINAL APPROVED DSPENCER
HVAC FINAL 02/16/2017 APPROVED CMINI
ELECTRIC FINAL 02/16/2017 APPROVED CMINI
ELECTRIC TEMP POLE 02/08/2017 APPROVED - AS NOTED RMARTIN
Note: SHOULD HAVE BEEN EARLY POWER INSPECTION, CALLED FPL SPOKE TO DELL RELEASED EARLY POWER 2:45
ELECTRIC - EARLY POWER 02/07/2017 Disapproved -FEE REQUIRED RMARTIN
Note: NEED ELECTRICIAN ON SITE FOR INSPECTION AND 8 FOOT LADDER TO CHECK CONDUIT RUN THROUGH CEILING, ALSO NEED TORQUE WRENCH ON SITE TO CHECK TORQUE SPECS NEC 110.14
ABOVE CEILING 02/03/2017 APPROVED CMINI
HVAC ROUGH 01/30/2017 APPROVED CMINI
Note: PER CONTRACTOR
FRAMING 01/17/2017 APPROVED DROCKWELL
ELECTRIC 2ND ROUGH 01/17/2017 APPROVED - AS NOTED RMARTIN
Note: NEED REVISION ON ELECTRIC ADDED, MARKED ON PLAN, BY FINAL

Review History

Department Status Date In Date Out
ELEC COMPLETE 02/15/2017 02/15/2017
PLUM COMPLETE 01/04/2017 01/12/2017
Note: No plumbing work - deleted sink at lobby.
MECH COMPLETE 01/04/2017 01/12/2017
MECH HOLD 12/21/2016 12/21/2016
Note: 1. Provide the capacity of existing hvac units to determine that it match with the distributed supply air shown on hvac plan per FBC 5th ed. 107.2.1. 2. Provide outdoor air calculation and outdoor air duct layout per FBCM 5th ed. 403.2. F.Reodica - 386-986 4734.
PLUM HOLD 12/16/2016 12/21/2016
Note: Provide plumbing plan suitable for review, construction and inspection per FBC 5th ed. 107.3.5. F.Reodica-386-986-4734.
UD1 COMPLETE 12/16/2016 12/16/2016
ZON COMPLETE 12/16/2016 12/20/2016
Note: Expanding existing Law Office
SW1 COMPLETE 12/16/2016 12/19/2016
BLD COMPLETE 12/16/2016 12/21/2016
ELEC COMPLETE 12/16/2016 12/21/2016
FI1 COMPLETE 12/16/2016 12/21/2016

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 02/20/2017
REVISION ¤40.00 02/20/2017
SITE PLAN 20 ¤20.00 01/13/2017
SURCHARGE FS 533.721 ¤5.31 01/13/2017
SURCHARGE - FS 468.631 ¤5.31 01/13/2017
ADMIN COMMERCIAL ¤60.00 01/13/2017
INSPECTION - COMMERCIAL ADD ¤315.00 01/13/2017
ELECTRIC FEE ¤87.00 01/13/2017
MECHANICAL FEE ¤87.00 01/13/2017
PLAN CHECK FEE ¤100.00 01/13/2017
Fees Total Due: ¤0.00 Total Paid: ¤759.62