I want to search for...
Permit #2017020105
Permit Details
Status: COED
| Parcel Id: 07-11-31-1230-00000-0C30 |
| Block: 00000 |
| Subdivision: 2206 - CYPRESS POINT PROFESSIONAL PARK CONDOMINIUM |
| Job Phone: (386) 446-5850 |
| Location Address: 50 CYPRESS POINT PKWY BLDG-C |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 02/24/2017 |
| NOC: RECORDED |
| Applicant name: CHARLES DALLAS RINEK |
| Owner: EVANS, JEFFREY & CINDY KIEL |
|
Address SUITE C-3 & 4 PALM COAST, FL 32164 |
|
Address 50 CYPRESS POINT PKWY PALM COAST, FL 32164 |
| Lot: 0C30 |
| Contracted Stated Job Value: ¤35,000.00 |
| Job Description: SUITE C3 & C4- "STATE FARM INSURANCE" |
| Type: CN |
Contractor
CHARLES RINEK CONSTRUCTION, INC.
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
P. O. Box 352502 Palm Coast, FL 32137 |
CGC046080 (Exp: 08/31/2026) | (386) 446-5850 | (386)445-9992 |
Sub Contractors
JONATHAN M PEARSON
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
209 N FORSYTH ST BUNNELL, FL 32110 |
CFC1425941 (Exp: 08/31/2026) | 386-597-0944 | 386-437-4996 |
CRAIG CHAPMAN
| Status | Location Address | State License Number | Phone |
| INACTIVE |
413 OAK PLACE PORT ORANGE, FL 32123 |
EC13007356 (Exp: 08/31/2024) | 386-316-5190 |
KEVIN HENRY BEHRENS
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
1200 SOUTH NOVA ROAD DAYTONA BEACH, FL 32114 |
CAC054733 (Exp: 08/31/2026) | (386)761-7751 | (386) 258-0058 |
Inspection History
| Type | Request Date | Result | Inspector |
| PLUMBING FINAL | 05/10/2017 | APPROVED | JGIBSON |
| ELECTRIC FINAL | 05/10/2017 | APPROVED | RMARTIN |
| HVAC FINAL | 05/10/2017 | APPROVED | JHINDMAN |
| BUILDING FINAL | 05/10/2017 | FINAL APPROVED | JHINDMAN |
| FIRE FINAL | 05/10/2017 | APPROVED | JHINDMAN |
| U - UTILITY COMMERCIAL FINAL | 05/10/2017 | FINAL APPROVED | JNICHOLS |
| PLUMBING 2ND ROUGH | 03/28/2017 | APPROVED - AS NOTED | JGIBSON |
| Note: PLANS CALL FOR TIE IN TO EXISTING VENT, BUT NO VENT IN ATTIC, NEED REVISION TO USE AUTO VENT | |||
| MONOLITHIC SLAB | 03/17/2017 | APPROVED | JHINDMAN |
| FRAMING | 03/17/2017 | APPROVED | JHINDMAN |
| ABOVE CEILING | 03/17/2017 | APPROVED | JHINDMAN |
| HVAC ROUGH | 03/13/2017 | APPROVED | CMINI |
| ELECTRIC 2ND ROUGH | 03/13/2017 | APPROVED - AS NOTED | RMARTIN |
| Note: ELECTRIC REVISION ON ADDED OUTLETS/SWITCHES NEEDS TO BE ON SITE BY ELECTRIC FINAL, MARKED ON PLAN | |||
| PLUMBING 1ST ROUGH | 03/10/2017 | APPROVED | CMINI |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 05/01/2017 | 05/02/2017 |
| PLUM | COMPLETE | 02/22/2017 | 02/23/2017 |
| ELEC | COMPLETE | 02/15/2017 | 02/15/2017 |
| MECH | COMPLETE | 02/15/2017 | 02/17/2017 |
| PLUM | HOLD | 02/15/2017 | 02/17/2017 |
| Note: Repeat comment: 1. Provide service sink per FBCP 5th ed. 403. Note: Business occupancy with occupant load over 15 people requires service sink per FBCP 5th ed. Table 403.1 Note g. This service sink shall be added to sanitary riser diagram. | |||
| BLD | COMPLETE | 02/03/2017 | 02/07/2017 |
| ELEC | HOLD | 02/03/2017 | 02/07/2017 |
| Note: 1. Provide electrical load calculations with panel schedule 2011 NEC art. 220 J. Hindman 986-3784. | |||
| FI1 | COMPLETE | 02/03/2017 | 02/07/2017 |
| MECH | HOLD | 02/03/2017 | 02/07/2017 |
| Note: Provide hvac plan either prepared by design professional or hvac contractor with signature and license number per FBC 5th ed. 105.3.1.2. Freodica - 386-986-4734 | |||
| PLUM | HOLD | 02/03/2017 | 02/07/2017 |
| Note: 1. Provide service sink per FBCP 5th ed. 403. 2. Provide sanitary riser diagram per FBC 5th ed. 107.3.5. | |||
| UD1 | COMPLETE | 02/03/2017 | 02/03/2017 |
| ZON | COMPLETE | 02/03/2017 | 02/03/2017 |
| SW1 | COMPLETE | 02/03/2017 | 02/06/2017 |
| MECH | HOLD | 02/07/2017 | |
| Note: 1. Provide hvac plan either prepared by design professional or hvac contractor with signature and license number per FBC 5th ed. 105.3.1.2. 2. Provide Florida licensed hvac contractor per FS 489. F.Reodica - 386-986-4734 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REVISION | ¤40.00 | 05/09/2017 |
| SITE PLAN 20 | ¤20.00 | 02/24/2017 |
| SURCHARGE FS 533.721 | ¤6.35 | 02/24/2017 |
| SURCHARGE - FS 468.631 | ¤6.35 | 02/24/2017 |
| ADMIN COMMERCIAL | ¤60.00 | 02/24/2017 |
| INSPECTION - COMMERCIAL ADD | ¤245.00 | 02/24/2017 |
| ELECTRIC FEE | ¤81.00 | 02/24/2017 |
| MECHANICAL FEE | ¤81.00 | 02/24/2017 |
| PLAN CHECK FEE | ¤100.00 | 02/24/2017 |
| PLUMBING FEE | ¤81.00 | 02/24/2017 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤720.70 |