Permit #2017041144

Permit Details

Status: COED

Parcel Id: 07-11-31-7057-00570-0100
CONDITIONED SPACE: 1360 sqft
CONDITIONED SPACE: 1360 sqft
OPENED PORCH (WITH ROOF) : 48 sqft
OPENED PORCH (WITH ROOF) : 48 sqft
GARAGE: 469 sqft
GARAGE: 469 sqft
OPENED PORCH (WITH ROOF) : 131 sqft
OPENED PORCH (WITH ROOF) : 131 sqft
Total Square Footage: 4016 sqft
Block: 00570
Subdivision: 2123 - SECTION 57-ULYSSES TREES
Job Phone: 386-931-2568
Location Address: 5 UNION RUN CT
Type: DU - DUPLEX
Issue Date: 06/09/2017
NOC: RECORDED
Applicant name: PETER JOSEPH LYDEN
Owner: MONKEVITCH, EUGENE & OLGA

Address

46 NORTH PARK CIRCLE

PALM COAST, FL 32137

Lot: 0100
Contracted Stated Job Value: ¤100,000.00
Job Description: DUPLEX
Type: CN

Contractor

DEL CONSTRUCTION INC.
Status Location Address State License Number Phone
INACTIVE

PO BOX 1009

BUNNELL, FL 32110

CBC1253392 (Exp: 08/31/2024) 386-931-2568

Sub Contractors

PETER JOSEPH LYDEN
Status Location Address State License Number Phone
CANCEL

17 UNIMAY CT

BUNNELL, FL 32110

EC0002436 (Exp: 08/31/2022) 386-931-2568
RUSSELL J CARTER
Status Location Address State License Number Phone Fax
ACTIVE

PO BOX 302

DELAND, FL 32721

CFC1425938 (Exp: 08/31/2026) 386-736-4220 386-736-4219
JOHN ROBERT BLEVINS JR
Status Location Address State License Number Phone Fax
ACTIVE

17 PORWYN LANE

PALM COAST, FL 32164

CAC1816125 (Exp: 08/31/2026) 386-585-8283 386-263-2096
PETER JOSEPH LYDEN
Status Location Address State License Number Phone
INACTIVE

PO BOX 1009

BUNNELL, FL 32110

CBC1253392 (Exp: 08/31/2024) 386-931-2568

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 09/18/2018 FINAL APPROVED DROCKWELL
BLD - BUILDING FINAL 09/14/2018 Disapproved - NO FEE DROCKWELL
Note: Receptical left side sink and under bar top not working
U -UTILITY RESIDENTIAL FINAL 08/28/2018 FINAL APPROVED MBACON
ROW - FINAL APRON (AFTER POUR) 08/17/2018 APPROVED CTROHA
Note: THIS IS A REINSPECTION MEETS THE MINIMUM REQUIREMENTS AT TIME OF THE INSPECTION
ROW - FINAL INSPECTION 08/17/2018 FINAL APPROVED CTROHA
Note: MEETS THE MINIMUM REQUIREMENTS AT TIME OF THE INSPECTION
FINAL SURVEY (OFFICE USE ONLY) 08/16/2018 APPROVED DREWIS
ROW - FINAL APRON (AFTER POUR) 08/09/2018 Disapproved - NO FEE CTROHA
Note: SEE PREVIOUS NOTES FOR THIS INSPECTION
ROW - FINAL APRON (AFTER POUR) 08/01/2018 Disapproved -FEE REQUIRED CTROHA
Note: APPROVED FINAL SURVEY IS REQUIRED TO BE ON SITE FOR THIS INSPECTION
ELECTRIC - EARLY POWER 07/13/2018 APPROVED - AS NOTED RMARTIN
Note: SPOKE TO SUSAN FPL RELEASED EARLY POWER 3:20
ELECTRIC - EARLY POWER 07/12/2018 Disapproved -FEE REQUIRED RMARTIN
Note: ALL DOORS LOCKED, NEED ACCESS FOR INSPECTION
U - SEWER TIE IN 06/22/2018 APPROVED MBACON
ROW - FINAL APRON (AFTER POUR) 03/29/2018 Disapproved -FEE REQUIRED KHOWELL
Note: ASPHALT PATCH HAS TO BE DONE, CLEAN THE CONCRETE OUT OF THE CULVERT PIPES AND REMOVE EXCESS OVER POUR FROM ALL OF THE MITERED END SECTIONS
ROW- PRE-APRON (PRE-POUR) 03/15/2018 APPROVED - AS NOTED KHOWELL
Note: READY TO POUR It is the BUILDER'S RESPONSIBILITY: to recheck elevations and pipe size, to insure that an obstruction does not exist upstream and or downstream, that the culvert pipe is set to and or follows the swale plan, form the driveway to the approved site plan and follow the approved driveway detail sheet provided by the City of Palm Coast. PRIOR to placement of concrete. COMPACT PRIOR TO POURING AND VERIFY THE DOWN STREAM PIPE IS NOT SET HIGHER THAN UP STREAM PIPE PRIOR TO POURING CONCRETE
LATH/BRICK/ WATER BARRIER 02/23/2018 APPROVED DROCKWELL
Note: THIS IS A REINSPECTION
LATH/BRICK/ WATER BARRIER 02/05/2018 Disapproved -FEE REQUIRED DROCKWELL
Note: Not ready for inspection
ELECTRIC TEMP POLE 01/23/2018 APPROVED - AS NOTED RMARTIN
Note: SPOKE TO SUSAN FPL RELEASED TEMP POLE 3:40
FIREWALL 01/12/2018 APPROVED DROCKWELL
Note: THIS IS A REINSPECTION
FIREWALL 01/10/2018 Disapproved - NO FEE DROCKWELL
Note: THIS IS A REINSPECTION/ See results last inspection. Drywall and compound must extend all the way to sub-facia
INSULATION 01/10/2018 APPROVED DROCKWELL
FIREWALL 01/08/2018 Disapproved -FEE REQUIRED DROCKWELL
Note: Firewall must extend all the way to sub-facia front and back.
ALL ROUGH 12/14/2017 APPROVED DROCKWELL
Note: THIS IS A REINSPECTION
ALL ROUGH 12/08/2017 Disapproved - NO FEE DROCKWELL
Note: No pressure on supply side/No test on sanitary limes.Right side
ROOF VALLEY & METAL 12/01/2017 APPROVED DROCKWELL
ROOF SHEATHING / BRACES/TIES/DOWN CELL 11/09/2017 APPROVED DROCKWELL
TIE BEAM / LINTEL 10/06/2017 APPROVED DROCKWELL
FOUND SURVEY APPROVED (OFFICE) 10/05/2017 APPROVED DREWIS
MONOLITHIC SLAB 08/01/2017 APPROVED DROCKWELL
GRAVITY SEWER TEST 07/25/2017 APPROVED JGIBSON
PLUMBING 1ST ROUGH UNDERGROUND 07/21/2017 APPROVED - AS NOTED JGIBSON
Note: FIRST ROUGH AND GRAVITY SEWER INSPECTED AND APPROVED

Review History

Department Status Date In Date Out
SW1 COMPLETE 08/15/2018 08/16/2018
Note: Released By: DREWIS final s
SW1 COMPLETE 10/04/2017 10/05/2017
Note: Released By: DREWIS Released By: DREWIS foundation s
BLD COMPLETE 06/06/2017 06/07/2017
PLUM COMPLETE 05/16/2017 05/23/2017
BLD HOLD 05/16/2017 05/23/2017
Note: 1. Sheet 5: Provide legible plan with sufficient clarity. FBC 5th ed. 107.2.1. 2nd request J. Hindman 986-3784.
ELEC COMPLETE 05/16/2017 05/23/2017
BLD HOLD 04/28/2017 05/02/2017
Note: 1. Sheet 5: Provide ligible plan with sufficient clarity. FBC 5th ed. 107.2.1. 2. Sheet 4: Foudation detail designations do not match with those shown on foundation plan. Coordinate per FBC 5th ed. 107.2.1. F.Reodica -386-986-4734.
ELEC HOLD 04/28/2017 05/02/2017
Note: 1. The electric plan must be signed and sealed or signed by the electrical contractor with their license number on it. J. Hindman 986-3784.
ENGIN1 COMPLETE 04/28/2017 05/02/2017
MECH COMPLETE 04/28/2017 05/02/2017
PLUM HOLD 04/28/2017 05/02/2017
Note: Sanitray riser diagram does not match with floor plan. Coordinate for clarity per FBC 5th ed. 107.2.1. F.Reodica - 386-986-4734.
SW1 COMPLETE 04/28/2017 05/02/2017
UD1 COMPLETE 04/28/2017 05/02/2017
ZON COMPLETE 04/28/2017 04/28/2017

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 09/26/2018
REINSPECTION FEE ¤40.00 09/26/2018
REINSPECTION FEE ¤40.00 09/26/2018
REINSPECTION FEE ¤40.00 09/26/2018
REINSPECTION FEE ¤40.00 01/09/2018
NEW RESIDENTIAL INSPECTIONS ¤710.00 06/09/2017
SITE PLAN 20 ¤20.00 06/09/2017
SURCHARGE FS 533.721 ¤25.67 06/09/2017
SURCHARGE - FS 468.631 ¤25.67 06/09/2017
STORM WATER PERMIT FEES ¤80.00 06/09/2017
3% TRANS IMPACT FEE CREDIT (¤187.48) 06/09/2017
3% TRANS IMPACT FEE CREDIT (¤187.48) 06/09/2017
ADMIN FEE ¤20.00 06/09/2017
ELECTRIC FEE ¤273.00 06/09/2017
3% FIRE IMPACT FEE CREDIT (¤12.86) 06/09/2017
3% FIRE IMPACT FEE CREDIT (¤12.86) 06/09/2017
IMPACT FEE FIRE NONRESIDENTIAL ¤428.58 06/09/2017
IMPACT FEE PARKS ¤1,698.48 06/09/2017
IMPACT FEE SCHOOL ¤7,200.00 06/09/2017
IMPACT FEE TRANSPORTATION ¤6,249.34 06/09/2017
MECHANICAL FEE ¤273.00 06/09/2017
3% PARKS IMPACT FEE CREDIT (¤50.95) 06/09/2017
3% PARKS IMPACT FEE CREDIT (¤50.95) 06/09/2017
PLAN CHECK FEE ¤142.00 06/09/2017
PLUMBING FEE ¤273.00 06/09/2017
Fees Total Due: ¤0.00 Total Paid: ¤17,116.16