I want to search for...
Permit #2017080319
Permit Details
Status: STATE
| Parcel Id: 07-11-31-7007-00150-0070 |
| Block: 00150 |
| Subdivision: 2185 - SECTION 7-FLORIDA PARK |
| Job Phone: 321-332-0001 |
| Location Address: 56 FORT CAROLINE LN |
| Type: ME - MECHANICAL |
| Issue Date: 08/22/2017 |
| NOC: RECORDED |
| Applicant name: CAREY L ZARM |
| Owner: GAINES BRENDA L |
|
Address 56 FORT CAROLINE LANE PALM COAST, FL 32137 |
| Lot: 0070 |
| Contracted Stated Job Value: ¤19,353.00 |
| Job Description: HVAC CHANGEOUT- 4 ton/ 17 Seer/ HP |
| Type: CN |
Contractor
SERVICE EXPERTS HEATING & AIR CONDITIONING
| Status | Location Address | Mailing Address | State License Number | Phone | Fax |
| CANCEL |
1725 S. NOVA ROAD DAYTONA BEACH, FL 32119 |
UNIT D-5 DAYTONA BEACH, FL 32119 |
CAC1817129 (Exp: 08/31/2020) | 321-332-0001 | 321-281-4733 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 08/31/2017 | Disapproved -FEE REQUIRED | CMINI |
| Note: trusses have been cut for this installation.R502.1.10.3 [IRC 502.11.3] Alterations to trusses.Truss members and components shall not be cut,notched, spliced or otherwise altered in any way without the approval of a registered design professional. Alterations resulting in the addition of load (e.g.,HVAC equipment, water heater, etc.), that exceed the design load for the truss, shall not be permitted without verification that the truss is capable of supporting the additional loading. Need engineered drawings for repair and corrections. mocp rating on condensor is 45, 50 amp installed. also notice to homeowner shall be affixed to electric panel.R403.2.4 Air-handling units. | |||
| HVAC FINAL | |||
| Note: THIS IS A REINSPECTION |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 08/08/2017 | 08/09/2017 |
| Note: Released By: JHINDMAN |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADMIN FEE | ¤20.00 | 08/22/2017 |
| INSPECTION 40 | ¤40.00 | 08/22/2017 |
| SURCHARGE FS 533.721 | ¤2.00 | 08/22/2017 |
| SURCHARGE - FS 468.631 | ¤2.00 | 08/22/2017 |
| REINSPECTION FEE | ¤40.00 | |
| Fees | Total Due: ¤40.00 | Total Paid: ¤64.00 |