I want to search for...
Permit #2017081127
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7004-00040-0280 |
| Block: 00040 |
| Subdivision: 2203 - SECTION 4-COUNTRY CLUB COVE |
| Job Phone: 386-860-2050 |
| Location Address: 2 CLARENDON CT N |
| Type: GEN - GENERATOR |
| Issue Date: 09/14/2017 |
| NOC: RECORDED |
| Applicant name: HENRY E TOOKE |
| Owner: EJ MCCALLUM INC |
|
Address 10 N CLAYMONT CT PALM COAST, FL 32137 |
| Lot: 0280 |
| Contracted Stated Job Value: ¤9,889.00 |
| Job Description: 22 KW GENERATOR W/200 AMP TRANSFER SWITCH |
| Type: CN |
Contractor
DBK,INC
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
398 S SHELL ROAD DEBARY, FL 32713 |
EC13006201 (Exp: 08/31/2020) | 386-860-2050 | 321-414-0201 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 12/19/2017 | FINAL APPROVED | RMARTIN |
| ELECTRIC FINAL | 12/15/2017 | Disapproved -FEE REQUIRED | RMARTIN |
| Note: NEED GROUND FROM 1ST MEANS TO HOUSE PANEL, AND SEPERATE GROUNDS AND NEUTRALS IN HOUSE PANEL NEC 250.32 B1 |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 08/30/2017 | 09/07/2017 |
| Note: Released By: JHINDMAN | |||
| ZON | COMPLETE | 08/30/2017 | 08/31/2017 |
| Note: Released By: TAWILLIAMS |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 12/18/2017 |
| SITE PLAN 20 | ¤20.00 | 09/14/2017 |
| SURCHARGE FS 533.721 | ¤2.00 | 09/14/2017 |
| SURCHARGE - FS 468.631 | ¤2.00 | 09/14/2017 |
| ADMIN FEE | ¤20.00 | 09/14/2017 |
| ELECTRIC FEE | ¤66.00 | 09/14/2017 |
| PLAN REVIEW 25 | ¤25.00 | 09/14/2017 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤175.00 |