Permit #2018031095
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7034-01380-0150 |
| Block: 01380 |
| Subdivision: 2165 - SECTION 34-EASTHAMPTON |
| Job Phone: 407-322-5854 |
| Location Address: 106 EDWARD DR |
| Type: GA - GAS |
| Issue Date: 05/01/2018 |
| NOC: Unknown |
| Applicant name: CLYDE H ROBERTSON JR |
| Owner: IMMEL KIRK & SHERRI H&W LIFE ESTATE |
|
Address 106 EDWARD DRIVE PALM COAST, FL 32164 |
| Lot: 0150 |
| Contracted Stated Job Value: ¤2,495.00 |
| Job Description: Install a 250 UG tank with approx.60' of 1/2" polypipe to a 350,000 BTU Generator |
| Type: CN |
Contractor
THERMOTANE PROPANE LLC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
PO BOX 635 SANFORD, FL 32771 |
00805 (Exp: 07/25/2027) | 407-322-5854 |
Inspection History
| Type | Request Date | Result | Inspector |
| GAS FINAL | 06/05/2018 | FINAL APPROVED | JGIBSON |
| GAS ROUGH | 05/25/2018 | APPROVED | DROCKWELL |
| GAS ROUGH | 05/24/2018 | Disapproved -FEE REQUIRED | JGIBSON |
| Note: STILL MISSING REQUIRED PAPER WORK MENTIONED ON LAST INSPECTION | |||
| GAS ROUGH | 05/17/2018 | Disapproved -FEE REQUIRED | JGIBSON |
| Note: G- 2417.4.1 TEST PRESSURE , NEED APPROVED SITE PLAN SHOWING LOCATION OF BURIED TANK, AND GENERATOR LOCATION AND APPROVED GAS RISER FROM CITY |
Review History
| Department | Status | Date In | Date Out |
| PLUM | COMPLETE | 04/27/2018 | 04/27/2018 |
| Note: Released By: FREODICA | |||
| ZON | COMPLETE | 04/09/2018 | 04/09/2018 |
| Note: Released By: AMOBLEY | |||
| PLUM | HOLD | 04/09/2018 | 04/11/2018 |
| Note: Held By: FREODICA Repeat comment: The gas pipe size of 1/2 " polypipe with delivery pressure of 12 inch w.c. and serving generator with 320,000 btu/hr fuel consumtion of approx. 60 ft from the gas tank does not comply with FBCFG 6th ed. Table 402. 4(35). F.Reodica -386-986-4734. Note: Provide also signature and license number of gas contractor on gas riser diagram per FBC 6th ed. 107.1. | |||
| PLUM | HOLD | 03/23/2018 | 03/27/2018 |
| Note: Held By: FREODICA The gas pipe size of 1/2 " polypipe with delivery pressure of 12 inch w.c. and serving generator with 320,000 btu/hr fuel consumtion of approx. 60 ft from the gas tank does not comply with FBCFG 6th ed. Table 402. 4(35). F.Reodica -386-986-4734. | |||
| ZON | HOLD | 03/23/2018 | 03/23/2018 |
| Note: Held By: AMOBLEY Please provide the actual survey showing the tank location with setbacks |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 05/24/2018 |
| REINSPECTION FEE | ¤40.00 | 05/24/2018 |
| SITE PLAN 20 | ¤20.00 | 05/01/2018 |
| SURCHARGE FS 533.721 | ¤2.00 | 05/01/2018 |
| SURCHARGE - FS 468.631 | ¤2.00 | 05/01/2018 |
| ADMIN FEE | ¤20.00 | 05/01/2018 |
| PLAN REVIEW 25 | ¤25.00 | 05/01/2018 |
| PLUMBING FEE | ¤61.50 | 05/01/2018 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤210.50 |