I want to search for...
Permit #2018051367
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7027-00600-0050 |
| Block: 00600 |
| Subdivision: 2128 - SECTION 27-WYNNFIELD |
| Job Phone: (386)774-8244 |
| Location Address: 2 WOODSTONE LN |
| Type: GEN - GENERATOR |
| Issue Date: 07/12/2018 |
| NOC: RECORDED |
| Applicant name: VINCENT PASQUALE POLIZZI |
| Owner: MORALES LUCAS & ESTHER MORALES H&W |
|
Address 2 WOODSTONE LANE PALM COAST, FL 32164 |
| Lot: 0050 |
| Contracted Stated Job Value: ¤7,500.00 |
| Job Description: GENERATOR & TWO 120 ABOVE GROUND LP TANKS |
| Type: CN |
Contractor
GAS PLUMBING SERVICES INC.
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
219 W OHIO AVENUE LAKE HELEN, FL 32734 |
CFC057948 (Exp: 08/31/2026) | (386)774-8244 | (386)775-1749 |
Sub Contractors
GERALD MARTIN DITARANTO
| Status | Location Address | State License Number | Phone |
| INACTIVE |
2560 W TULSA DRIVE DELAND, FL 32720 |
EC13005753 (Exp: 08/31/2026) | 386-532-5013 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 08/23/2018 | FINAL APPROVED | RMARTIN |
| GAS ROUGH | 08/23/2018 | APPROVED | JGIBSON |
| GAS FINAL | 08/23/2018 | APPROVED | JGIBSON |
| ELECTRIC FINAL | 08/22/2018 | Disapproved -FEE REQUIRED | RMARTIN |
| Note: NEED TO HAVE CONTRACTOR ON SITE FOR INSPECTION TO OPEN HOT PANELS AND TRANSFERSWITCH, ALSO NEED TO HAVE APPROVED ELECTRIC RISER ON SITE | |||
| GAS FINAL | 08/22/2018 | Disapproved - NO FEE | JGIBSON |
| Note: GAS ROUGH FINAL CAN NOT BE APPROVED UNTIL GAS ROUGH APPROVED, BOTH CAN BE SCHEDULED AT SAME TIME PROVIDED MANUFACTURES SPEC ALLOWS REGULATOR TO BE AT ITS CURRENT LOCATION | |||
| GAS FINAL | 08/06/2018 | Disapproved - NO FEE | JGIBSON |
| Note: GAS ROUGH MUST BE APPROVED BEFORE GAS FINAL | |||
| GAS ROUGH | 08/06/2018 | Disapproved -FEE REQUIRED | JGIBSON |
| Note: NO GUAGE ON GAS LINE, TANKS NOT SITTING 30' AWAY FROM GENERATOR, REGULATOR NOT AT EQUIPMENT IT SERVES |
Review History
| Department | Status | Date In | Date Out |
| PLUM | COMPLETE | 08/07/2018 | 08/10/2018 |
| Note: Released By: FREODICA Revised gas riser diagram. | |||
| ELEC | COMPLETE | 07/06/2018 | 07/10/2018 |
| Note: Released By: DREWIS | |||
| PLUM | COMPLETE | 07/06/2018 | 07/11/2018 |
| Note: Released By: JHINDMAN | |||
| ELEC | HOLD | 06/20/2018 | 06/22/2018 |
| Note: Held By: DREWIS Provide and electrical contractor as a subcontractor or have the electrical contractor apply for a seperate generator permit. Daniel Rewis 986-4736 | |||
| ZON | COMPLETE | 06/15/2018 | 06/15/2018 |
| Note: Released By: TDOAK | |||
| PLUM | HOLD | 06/15/2018 | 06/20/2018 |
| Note: Held By: FREODICA Repeat comment: Provide electrical contractor for generator installation per FS 489. Gas riser diagram is okay. F.Reodica -386-986-4734.. | |||
| PLUM | HOLD | 05/31/2018 | 06/05/2018 |
| Note: Held By: FREODICA Provide electrical contractor for generator installation per FS 489. Gas riser diagram is okay. F.Reodica -386-986-4734.. | |||
| ZON | HOLD | 05/31/2018 | 05/31/2018 |
| Note: Held By: AMOBLEY Please show tank location and generator location and provide setbacks to property line |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 08/22/2018 |
| REVISION | ¤40.00 | 08/10/2018 |
| REINSPECTION FEE | ¤40.00 | 08/07/2018 |
| SITE PLAN 20 | ¤20.00 | 07/12/2018 |
| SURCHARGE FS 533.721 | ¤2.00 | 07/12/2018 |
| SURCHARGE - FS 468.631 | ¤2.91 | 07/12/2018 |
| ADMIN FEE | ¤20.00 | 07/12/2018 |
| CONTRACTOR CHANGE | ¤40.00 | 07/12/2018 |
| ELECTRIC FEE | ¤64.50 | 07/12/2018 |
| PLAN REVIEW 25 | ¤25.00 | 07/12/2018 |
| PLUMBING FEE | ¤64.50 | 07/12/2018 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤358.91 |