I want to search for...

Permit #2018061323

Permit Details

Status: FINAL

Parcel Id: 48-11-31-1710-00000-0460
Block: 00000
Subdivision: 2087 - ESTATES AT GRAND HAVEN PHASE II
Job Phone: 386-679-6908
Location Address: 32 SCARLET OAK CIR
Type: GEN - GENERATOR
Issue Date: 08/02/2018
NOC: Unknown
Applicant name: GREGORY ALLEN HENRY
Owner: SPUDIS STEPHEN D & JACQUELINE H&W LIFE ESTATE

Address

32 SCARLET OAK CIR

PALM COAST, FL 32137

Lot: 0460
Contracted Stated Job Value: ¤1,000.00
Job Description: Adding 22kw generator with 200 amp ATS
Type: CN

Contractor

G HENRY ELECTRIC LLC
Status Location Address State License Number Phone
CANCEL

1332 SUNSET BLVD

DAYTONA BEACH, FL 32117

ER13015005 (Exp: 08/31/2020) 386-679-6908

Inspection History

Type Request Date Result Inspector
ELECTRIC FINAL 09/05/2018 FINAL APPROVED RMARTIN
ELECTRIC FINAL 09/04/2018 CANCELLED BY APPLICANT WEB
ELECTRIC FINAL 08/14/2018 Disapproved -FEE REQUIRED RMARTIN
Note: NEED PERMIT/PAPERWORK ON SITE FOR INSPECTION, NEED TO SEPERATE GRDS AND NEUTRALS, NEED TO REWIRE METER BACK TO UL LISTED AND CORRECTLY
ELECTRIC FINAL 08/08/2018 CANCELLED BY APPLICANT RMARTIN
Note: CANCELLED BY CONTRACTOR
ELEV CERT-FOUNDATION APPROVAL 08/07/2018 APPROVED JMYERS

Review History

Department Status Date In Date Out
PLFM COMPLETE 08/01/2018 08/01/2018
Note: Released By: JMYERS The elevation certificate submitted has been deemed acceptable.
PLFM HOLD 07/11/2018 07/11/2018
Note: Held By: JMYERS Previous comments not addressed. According to City of Palm Coast mapping resources, the subject property is located within an AE zone which is a Special Flood Hazard Area (SFHA). An Elevation Certificate needs to be provided for the generator to show that it has been placed 1-foot above base flood elevation pursuant to LDC 10.02.06. Only a Final Survey was submitted which did not show the proposed location of the generator. It also referenced the old FEMA FIRM, new maps took effect on 6/6/18.
ELEC COMPLETE 07/11/2018 07/13/2018
Note: Released By: DREWIS
PLUM COMPLETE 07/11/2018 07/13/2018
Note: Released By: JHINDMAN
ELEC HOLD 06/29/2018 07/05/2018
Note: Held By: DREWIS Provide a gas sub contractor or have a gas contractor apply for a permit. Daniel Rewis 986-4736
PLUM HOLD 06/29/2018 07/06/2018
Note: Held By: JHINDMAN 1. Provide a gas contractor and gas riser. 6th ed. FBC 107.1. 107.3.5. J. Hindman 986-3784.
ZON COMPLETE 06/29/2018 06/29/2018
Note: Released By: AMOBLEY
PLFM HOLD 06/29/2018 07/02/2018
Note: Held By: JMYERS According to City of Palm Coast mapping resources, the subject property is located within an AE zone which is a Special Flood Hazard Area (SFHA). An Elevation Certificate needs to be provided for the generator to show that it has been placed 1-foot above base flood elevation pursuant to LDC 10.02.06.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 08/31/2018
SITE PLAN 20 ¤20.00 08/02/2018
SURCHARGE FS 533.721 ¤2.00 08/02/2018
SURCHARGE - FS 468.631 ¤2.00 08/02/2018
ADMIN FEE ¤20.00 08/02/2018
ELECTRIC FEE ¤60.60 08/02/2018
PLAN REVIEW 25 ¤25.00 08/02/2018
Fees Total Due: ¤0.00 Total Paid: ¤169.60