I want to search for...
Permit #2018061323
Permit Details
Status: FINAL
| Parcel Id: 48-11-31-1710-00000-0460 |
| Block: 00000 |
| Subdivision: 2087 - ESTATES AT GRAND HAVEN PHASE II |
| Job Phone: 386-679-6908 |
| Location Address: 32 SCARLET OAK CIR |
| Type: GEN - GENERATOR |
| Issue Date: 08/02/2018 |
| NOC: Unknown |
| Applicant name: GREGORY ALLEN HENRY |
| Owner: SPUDIS STEPHEN D & JACQUELINE H&W LIFE ESTATE |
|
Address 32 SCARLET OAK CIR PALM COAST, FL 32137 |
| Lot: 0460 |
| Contracted Stated Job Value: ¤1,000.00 |
| Job Description: Adding 22kw generator with 200 amp ATS |
| Type: CN |
Contractor
G HENRY ELECTRIC LLC
| Status | Location Address | State License Number | Phone |
| CANCEL |
1332 SUNSET BLVD DAYTONA BEACH, FL 32117 |
ER13015005 (Exp: 08/31/2020) | 386-679-6908 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 09/05/2018 | FINAL APPROVED | RMARTIN |
| ELECTRIC FINAL | 09/04/2018 | CANCELLED BY APPLICANT | WEB |
| ELECTRIC FINAL | 08/14/2018 | Disapproved -FEE REQUIRED | RMARTIN |
| Note: NEED PERMIT/PAPERWORK ON SITE FOR INSPECTION, NEED TO SEPERATE GRDS AND NEUTRALS, NEED TO REWIRE METER BACK TO UL LISTED AND CORRECTLY | |||
| ELECTRIC FINAL | 08/08/2018 | CANCELLED BY APPLICANT | RMARTIN |
| Note: CANCELLED BY CONTRACTOR | |||
| ELEV CERT-FOUNDATION APPROVAL | 08/07/2018 | APPROVED | JMYERS |
Review History
| Department | Status | Date In | Date Out |
| PLFM | COMPLETE | 08/01/2018 | 08/01/2018 |
| Note: Released By: JMYERS The elevation certificate submitted has been deemed acceptable. | |||
| PLFM | HOLD | 07/11/2018 | 07/11/2018 |
| Note: Held By: JMYERS Previous comments not addressed. According to City of Palm Coast mapping resources, the subject property is located within an AE zone which is a Special Flood Hazard Area (SFHA). An Elevation Certificate needs to be provided for the generator to show that it has been placed 1-foot above base flood elevation pursuant to LDC 10.02.06. Only a Final Survey was submitted which did not show the proposed location of the generator. It also referenced the old FEMA FIRM, new maps took effect on 6/6/18. | |||
| ELEC | COMPLETE | 07/11/2018 | 07/13/2018 |
| Note: Released By: DREWIS | |||
| PLUM | COMPLETE | 07/11/2018 | 07/13/2018 |
| Note: Released By: JHINDMAN | |||
| ELEC | HOLD | 06/29/2018 | 07/05/2018 |
| Note: Held By: DREWIS Provide a gas sub contractor or have a gas contractor apply for a permit. Daniel Rewis 986-4736 | |||
| PLUM | HOLD | 06/29/2018 | 07/06/2018 |
| Note: Held By: JHINDMAN 1. Provide a gas contractor and gas riser. 6th ed. FBC 107.1. 107.3.5. J. Hindman 986-3784. | |||
| ZON | COMPLETE | 06/29/2018 | 06/29/2018 |
| Note: Released By: AMOBLEY | |||
| PLFM | HOLD | 06/29/2018 | 07/02/2018 |
| Note: Held By: JMYERS According to City of Palm Coast mapping resources, the subject property is located within an AE zone which is a Special Flood Hazard Area (SFHA). An Elevation Certificate needs to be provided for the generator to show that it has been placed 1-foot above base flood elevation pursuant to LDC 10.02.06. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 08/31/2018 |
| SITE PLAN 20 | ¤20.00 | 08/02/2018 |
| SURCHARGE FS 533.721 | ¤2.00 | 08/02/2018 |
| SURCHARGE - FS 468.631 | ¤2.00 | 08/02/2018 |
| ADMIN FEE | ¤20.00 | 08/02/2018 |
| ELECTRIC FEE | ¤60.60 | 08/02/2018 |
| PLAN REVIEW 25 | ¤25.00 | 08/02/2018 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤169.60 |