Permit #2018081235
Permit Details
Status: FINAL
| Parcel Id: 22-11-30-5545-00000-0020 |
| Block: 00000 |
| Subdivision: - |
| Job Phone: 386-274-3120 |
| Location Address: 4490 US HWY 1 N |
| Type: FU - FIRE UNDERGROUND |
| Issue Date: 09/17/2018 |
| NOC: Unknown |
| Applicant name: RICKY JOE ABERCROMBIE |
| Owner: TEAROC OF FLORIDA |
|
Address 4490 N US 1 STE 111 BUNNELL, FL 32110 |
| Lot: 0020 |
| Contracted Stated Job Value: ¤15,000.00 |
| Job Description: ALAMO STORAGE PHASE 2 - FIRE UNDERGROUND |
| Type: CN |
Contractor
TOMOKA CONSTRUCTION SERVICES, INC
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
810 FENTRESS CT DAYTONA BEACH, FL 32117 |
CUC1224170 (Exp: 08/31/2022) | 386-274-3120 | 386-274-3170 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE FINAL | 04/14/2020 | FINAL APPROVED | WMILLER |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION 1. need Contractor’s Material and Test Certificate for Underground Piping 2. NFPA 24 7.3.3 The center of a hose outlet shall be not less than 18 in. (minimum height requirement not met) 4/13/2020 from the list above the following remains deficient. NFPA 24 7.3.3 The center of a hose outlet shall be not less than 18 in. (minimum height requirement not met) | |||
| FIRE FINAL | 04/13/2020 | Disapproved -FEE REQUIRED | WMILLER |
| Note: THIS IS A REINSPECTION 1. need Contractor’s Material and Test Certificate for Underground Piping 2. NFPA 24 7.3.3 The center of a hose outlet shall be not less than 18 in. (minimum height requirement not met) 4/13/2020 from the list above the following remains deficient. NFPA 24 7.3.3 The center of a hose outlet shall be not less than 18 in. (minimum height requirement not met) | |||
| FIRE SYSTEM FLUSH | 04/07/2020 | APPROVED | WMILLER |
| HYDRANT FLOW TEST | 04/07/2020 | APPROVED | WMILLER |
| FIRE FINAL | 04/07/2020 | Disapproved - NO FEE | WMILLER |
| Note: 1. need Contractor’s Material and Test Certificate for Underground Piping 2. NFPA 24 7.3.3 The center of a hose outlet shall be not less than 18 in. (minimum height requirement not met) | |||
| FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR | 11/08/2018 | APPROVED | DREWIS |
| Note: 1st 0930 @ 210psi 2nd 1134 @ 210psi | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 11/07/2018 | APPROVED | DREWIS |
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 10/17/2018 | Disapproved - NO FEE | DREWIS |
| Note: Not ready. | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 10/01/2018 | APPROVED | DREWIS |
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 09/19/2018 | Disapproved -FEE REQUIRED | WMILLER |
| Note: uncover work for inspection and have approve documents on site at time of inspection.... 1. PLACEMENT OF PERMIT, 105.7 SHALL BE KEPT ON SITE DOCUMENTS MUST BE APPROVED AND KEPT ON SITE 107.3,1. AND SHALL BE OPEN TO INSPECTION BY THE BUILDING OFFICIAL 2. PROVIDE ACCESS FOR INSPECTION, FBC 6th edition 110.1 |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 08/31/2018 | 09/04/2018 |
| Note: Released By: JHINDMAN |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 04/13/2020 |
| REINSPECTION FEE | ¤40.00 | 09/26/2018 |
| CONTRACTOR CHANGE | ¤40.00 | 09/26/2018 |
| FIRE PLANS REVIEW | ¤40.00 | 09/17/2018 |
| ADMIN COMMERCIAL | ¤60.00 | 09/17/2018 |
| SURCHARGE FS 533.721 | ¤2.00 | 09/17/2018 |
| SURCHARGE - FS 468.631 | ¤2.00 | 09/17/2018 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤224.00 |