I want to search for...
Permit #2018090738
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7008-00010-0270 |
| Block: 00010 |
| Subdivision: 2204 - SECTION 8-COUNTRY CLUB COVE |
| Job Phone: 904-661-0000 |
| Location Address: 5 COLE CT |
| Type: ME - MECHANICAL |
| Issue Date: 09/24/2018 |
| NOC: Unknown |
| Applicant name: MARK VEILLEUX |
| Owner: VILJOEN DAVID P & MICHELLE H&W |
|
Address 104 CLUBHOUSE DRIVE #105 PALM COAST, FL 32137 |
| Lot: 0270 |
| Contracted Stated Job Value: ¤4,400.00 |
| Job Description: 2.5 TON / 15.50 SEER |
| Type: CN |
Contractor
ELITE HVAC GROUP LLC DBA SOLAR BEAR SERVICES
| Status | Location Address | Mailing Address | State License Number | Phone |
| CANCEL |
5771 MINING TERRACE JACKSONVILLE, FL 32257 |
# 102 JACKSONVILLE, FL 32257 |
CAC1817134 (Exp: 08/31/2020) | 904-661-0000 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 03/25/2019 | FINAL APPROVED | WMILLER |
| HVAC FINAL | 03/07/2019 | Disapproved -FEE REQUIRED | WMILLER |
| Note: 1. MOCP RATING NOT MATCHING BREAKERS MFBC 1303 (AHU CALLS FOR A MAX OF 45...... 50 IS INSTALLED) A/C CALLS FOR A MAX OF 30 AND A MIN OF 25..... 40 IS INSTALLED) 2. ANCHORING OF CONDENSING UNIT. PER FBC… R, M. 1307.2 APPLIANCES NEED TO BE FASTENED AT 4- POINTS, IN AN APPROVED MANNER FOR WIND RESISTENCE. | |||
| HVAC FINAL | 02/05/2019 | Disapproved -FEE REQUIRED | WMILLER |
| Note: THIS IS A REINSPECTION Per Owner 1. MOCP RATING NOT MATCHING BREAKERS MFBC 1303 2. CONDENSER NEEDS TO BE 3 inches ABOVE THE GROUND FBC, R, M1305.1.4.1 AND MISSING ANCHOR FASTENERS 3. PLACEMENT OF PERMIT, 105.7 SHALL BE KEPT ON SITE 4. DOCUMENTS MUST BE APPROVED AND KEPT ON SITE 107.3,1. AND SHALL BE OPEN TO INSPECTION BY THE BUILDING OFFICIAL (need the APPROVED paperwork on site at time of final) (PAPERWORK WAS NOT THE APPROVED PAPERWORK) | |||
| HVAC FINAL | 11/26/2018 | Disapproved -FEE REQUIRED | WMILLER |
| Note: KNOCKED AND RANG DOORBELL (NO ANSWER), ACCESS NEEDED FOR INSPECTION. (GREEN JEEP WRANGLER IN DRIVEWAY) |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 09/21/2018 | 09/21/2018 |
| Note: Released By: JHINDMAN |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 03/20/2019 |
| REINSPECTION FEE | ¤40.00 | 03/04/2019 |
| SURCHARGE FS 533.721 | ¤2.00 | 09/24/2018 |
| SURCHARGE - FS 468.631 | ¤2.00 | 09/24/2018 |
| ADMIN FEE | ¤20.00 | 09/24/2018 |
| INSPECTION 40 | ¤40.00 | 09/24/2018 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤144.00 |