Permit Details

Status: COED

Parcel Id: 06-12-31-5815-00000-0010
Block: 00000
Subdivision: 2118 - TOWN CENTER PHASE I
Job Phone: 386-238-1570
Location Address: 800 BELLE TERRE PKWY
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 12/21/2018
NOC: RECORDED
Applicant name: GARY LYNN ROBERTS
Owner: REAL SUB LLC

Address

PO BOX 32018

LAKELAND, FL 33802

Lot: 0010
Contracted Stated Job Value: ¤79,810.00
Job Description: UNIT 110- "SOUTHERN WIND ANIMAL HOSPITAL"
Type: CN

Contractor

COMMERCIAL CONSTRUCTION INC.
Status Location Address State License Number Phone Fax
ACTIVE

7 SUNSHINE BLVD

ORMOND BEACH, FL 32174

CGC059441 (Exp: 08/31/2026) 386-238-1570 386-238-1571

Sub Contractors

MIKE F WHALEY
Status Location Address State License Number Phone Fax
ACTIVE

804 Root Street

Daytona Beach, FL 32114

EC0001334 (Exp: 08/31/2026) (386) 252-2287 (386)257-1920
GARY S WELBORN
Status Location Address State License Number Phone Fax
ACTIVE

1709 North Nova Road

Holly Hill, 32117

CFC1426839 (Exp: 08/31/2026) (386) 257-1172 386-252-5979
STEVEN KEITH JONES
Status Mailing Address State License Number Phone Fax
ACTIVE

345 MADISON AVE

DAYTONA BEACH, FL 32114

CMC057027 (Exp: 08/31/2026) (386)253-7774 (386)255-9431

Inspection History

Type Request Date Result Inspector
ELECTRIC FINAL 04/17/2019 APPROVED RMARTIN
Note: THIS IS A REINSPECTION
U - UTILITY COMMERCIAL FINAL 04/17/2019 FINAL APPROVED JNICHOLS
PLUMBING FINAL 04/02/2019 CANCELLED BY APPLICANT WEB
PLUMBING FINAL 04/01/2019 APPROVED JGIBSON
ELECTRIC FINAL 04/01/2019 Disapproved -FEE REQUIRED RMARTIN
Note: NEED APPROVED REVISION SHOWING CHANGE ON X-RAY BREAKER SIZE/CONDUCTOR SIZE, AND 1PHASE TO 3PHASE
BUILDING FINAL 04/01/2019 FINAL APPROVED WMILLER
Note: pending electric final approval
FIRE FINAL 04/01/2019 APPROVED WMILLER
ABOVE CEILING 03/05/2019 APPROVED JHINDMAN
ELECTRIC FINAL 03/05/2019 CANCELLED BY APPLICANT WEB
HVAC FINAL 02/25/2019 APPROVED JHINDMAN
TUB SET 02/21/2019 APPROVED - AS NOTED JGIBSON
Note: THIS WAS A TEST FOR SHOWER PAN
TUB SET 02/20/2019 Disapproved -FEE REQUIRED JGIBSON
Note: DOOR LOCKED NO ACCESS RESCHEDUAL WHEN ABLE TO GAIN ENTRY
HVAC ROUGH 02/05/2019 APPROVED JHINDMAN
FRAMING 01/30/2019 APPROVED DROCKWELL
PLUMBING 2ND ROUGH 01/29/2019 APPROVED JGIBSON
ELECTRIC 2ND ROUGH 01/25/2019 APPROVED - AS NOTED RMARTIN
Note: NEED REVISION BY ELECTRIC FINAL ON ADDED ELECTRIC
PLUMBING 2ND ROUGH 01/25/2019 PARTIALLY APPROVED JGIBSON
Note: NEED NAIL PLATES IN MULTIPLE AREAS AND NEED TO SEE SHOWER VALVE INSTALLED ALONG WITH TEST ON SHOWER PAN, TWO STACKS NOT HOLDING AIR, 3'' AT W/M AND AT 2'' WHERE PRESSIRE GUAGE IS
PLUMBING 1ST ROUGH 01/07/2019 APPROVED - AS NOTED JGIBSON
Note: NEED REVISION TO SHOW OMITTING OF TWO DRAINS PER OWNER
MONOLITHIC SLAB 01/07/2019 APPROVED DROCKWELL

Review History

Department Status Date In Date Out
ELEC COMPLETE 04/02/2019 04/16/2019
Note: Released By: JHINDMAN
ELEC COMPLETE 02/19/2019 03/04/2019
Note: Released By: JHINDMAN
MECH CANCEL 02/19/2019 03/04/2019
PLUM COMPLETE 02/19/2019 03/04/2019
Note: Released By: RLEE
MECH COMPLETE 01/16/2019 01/31/2019
Note: Released By: RLEE
PLUM COMPLETE 01/16/2019 01/31/2019
Note: Released By: RLEE
BLD COMPLETE 01/16/2019 01/30/2019
Note: Released By: JHINDMAN
FI1 COMPLETE 12/18/2018 12/18/2018
Note: Released By: DREWIS Ref 2018120438 for sprinkler permit.
ZON COMPLETE 11/27/2018 11/28/2018
Note: Released By: JGONZALEZ
FI1 HOLD 11/27/2018 12/03/2018
Note: Held By: DREWIS Seperate sprinkler permit from Sprinkler Contractor needed: Sprinkler heads must be moved/added in different areas for coverage purposes, NFPA 13 8.6.2.2.1. This is also stated within the sprinkler legend on sheet A2. Daniel Rewis 986-4736
BLD COMPLETE 11/27/2018 12/11/2018
Note: Released By: JHINDMAN
ZON HOLD 11/02/2018 11/05/2018
Note: Held By: JGONZALEZ Revise plans calculation provide for totals do not add up.
FI1 HOLD 11/02/2018 11/13/2018
Note: Held By: DREWIS Update Florida Fire Prevention Code to the 6th Edition. Please depict the extiguishers. FFPC 9.9 Middle door must swing with egress, FFPC 101 7.2.1.4.2 Depict the existing sprinklers or if non existing, a seperate permit is needed. Daniel Rewis 986-4736
BLD HOLD 11/02/2018 11/15/2018
Note: Held By: RLEE 1. Provide ADA hardware specifications for the barn doors. 6th ed. FBC A404. 2. Door #4 does not comply with Florida Accessibility COde 2017 6th addotion. Cannot swing over clear floor space of fistures.
MECH COMPLETE 11/02/2018 11/15/2018
Note: Released By: RLEE
PLUM COMPLETE 11/02/2018 11/15/2018
Note: Released By: RLEE
BLD HOLD 10/10/2018 10/22/2018
Note: Held By: JHINDMAN 1. Provide ADA hardware specifications for the barn doors. 6th ed. FBC A404. J. Hindman 986-3784.
ELEC COMPLETE 10/10/2018 10/15/2018
Note: Released By: DREWIS
FI1 HOLD 10/10/2018 10/15/2018
Note: Held By: DREWIS Update Florida Fire Prevention Code to the 6th Edition. Please depict the extiguishers. FFPC 9.9 Depict the existing sprinklers or if non existing, a seperate permit is needed. Daniel Rewis 986-4736
MECH HOLD 10/10/2018 10/24/2018
Note: Held By: RLEE Provide seal and signature of engineer.
PLUM HOLD 10/10/2018 10/24/2018
Note: Held By: RLEE Provide seal and signature of engineer.
UD1 COMPLETE 10/10/2018 10/10/2018
Note: Released By: CJOHNSON
ZON HOLD 10/10/2018 10/11/2018
Note: Held By: JGONZALEZ Held By: JGONZALEZ 1. Will you be offering boarding and kenneling services? What are the planned terms for this service? Will there be overnights stays independent of surgery ?, What types of surgical procedures will be performed in the office? Will the boarding be exclusive to animals having surgical procedures? 2. Provide information in floor plan regarding the percentage of the quite room area are cages; percentage of treatment area is being used to kennel animals; and number of cages per area and sizes. 3. Show on a site plan the purposed area for pet walking in relation to the clinic area. 4. Provide information of disposal of fecal waste and medical waste produced.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 04/05/2019
REINSPECTION FEE ¤40.00 02/20/2019
CONTRACTOR CHANGE ¤40.00 01/03/2019
CONTRACTOR CHANGE ¤40.00 12/21/2018
ELECTRIC FEE ¤108.00 12/21/2018
ELECTRIC FEE (¤108.00) 12/21/2018
ELECTRIC FEE ¤108.00 12/21/2018
MECHANICAL FEE (¤108.00) 12/21/2018
MECHANICAL FEE ¤108.00 12/21/2018
MECHANICAL FEE ¤108.00 12/21/2018
PLAN CHECK FEE ¤100.00 12/21/2018
PLAN CHECK FEE (¤100.00) 12/21/2018
PLAN CHECK FEE ¤100.00 12/21/2018
PLUMBING FEE (¤108.00) 12/21/2018
PLUMBING FEE ¤108.00 12/21/2018
PLUMBING FEE ¤108.00 12/21/2018
SITE PLAN 20 ¤20.00 12/21/2018
SITE PLAN 20 (¤20.00) 12/21/2018
SITE PLAN 20 ¤20.00 12/21/2018
SURCHARGE FS 533.721 (¤5.04) 12/21/2018
SURCHARGE FS 533.721 ¤5.04 12/21/2018
SURCHARGE FS 533.721 ¤5.04 12/21/2018
SURCHARGE - FS 468.631 ¤7.56 12/21/2018
SURCHARGE - FS 468.631 (¤7.56) 12/21/2018
SURCHARGE - FS 468.631 ¤7.56 12/21/2018
ADMIN COMMERCIAL (¤60.00) 12/21/2018
ADMIN COMMERCIAL ¤60.00 12/21/2018
ADMIN COMMERCIAL ¤60.00 12/21/2018
INSPECTION - COMMERCIAL ADD ¤560.00 12/21/2018
INSPECTION - COMMERCIAL ADD (¤560.00) 12/21/2018
INSPECTION - COMMERCIAL ADD ¤560.00 12/21/2018
CONTRACTOR CHANGE (¤40.00) 12/21/2018
Fees Total Due: ¤0.00 Total Paid: ¤1,196.60