I want to search for...
Permit #2019050201
Permit Details
Status: FINAL
| Parcel Id: 22-11-30-5545-00000-0010 |
| Total Square Footage: 3600 sqft |
| Block: 00000 |
| Subdivision: - |
| Location Address: 4500 US HWY 1 BLDG 400 |
| Type: BC - BUILDING COMMERCIAL |
| Issue Date: 06/06/2019 |
| NOC: RECORDED |
| Applicant name: LUIS JORGE MEDEIROS |
| Owner: TEAROC OF FLORIDA INC |
|
Address 4490 N US 1 STE 111 BUNNELL, FL 32110 |
| Lot: 0010 |
| Contracted Stated Job Value: ¤100,000.00 |
| Job Description: BLDG 400 - 90 X 40 STORAGE BUILDING (REF # 2018090500 FOR FOUNDATION) |
| Type: CN |
Contractor
SUN STATE CUSTOM BUILDERS, LLC
| Status | Location Address | State License Number |
| CANCEL |
946 SHADICH DRIVE ORANGE CITY, FL |
CGC1519145 (Exp: 08/31/2022) |
Sub Contractors
RICHARD R EDWARDS
| Status | Location Address | State License Number | Phone |
| CANCEL |
P. O. Box 1637 Bunnell, FL 32110 |
ER0011603 (Exp: 08/31/2022) | (386) 437-1537 |
Inspection History
| Type | Request Date | Result | Inspector |
| BUILDING FINAL | 06/05/2020 | FINAL APPROVED | JCOLASANTI |
| U - UTILITY COMMERCIAL FINAL | 06/04/2020 | FINAL APPROVED | LFITZGERALD |
| FIRE FINAL | 06/02/2020 | APPROVED | WMILLER |
| Note: THIS IS A REINSPECTION 1. Missing Address... address identification FFPC 5th edition 10.12.1.5 minimum 6 inches in height 2. Fire extinguisher certification tags are out of date NFPA 10. 2. 3. Installation 13.6.3 Readily available… Conspicuously located along normal travel paths and exits and not obstructed from view and mounted 4. Travel distance for fire extinguishers exceeded... FFPC 1, 13.6.3.2.1.2.2 cannot exceed 75 ft. | |||
| FIRE FINAL | 05/27/2020 | Disapproved - NO FEE | WMILLER |
| Note: 1. Missing Address... address identification FFPC 5th edition 10.12.1.5 minimum 6 inches in height 2. Fire extinguisher certification tags are out of date NFPA 10. 2. 3. Installation 13.6.3 Readily available… Conspicuously located along normal travel paths and exits and not obstructed from view and mounted 4. Travel distance for fire extinguishers exceeded... FFPC 1, 13.6.3.2.1.2.2 cannot exceed 75 ft. | |||
| ELECTRIC FINAL | 05/11/2020 | APPROVED | RMARTIN |
| ELECTRIC 2ND ROUGH | 05/08/2020 | APPROVED | RMARTIN |
| ELECTRIC 1ST ROUGH | 05/07/2020 | APPROVED - AS NOTED | RMARTIN |
| Note: SITE STICKS ON SITE, UNDERGROUND IS GOOD | |||
| ROOF SHEATHING / BRACE / TIE DOWN | 12/04/2019 | APPROVED | FWILLIS |
| INSULATION | 11/12/2019 | APPROVED | JCOLASANTI |
| FRAMING | 10/31/2019 | APPROVED | JCOLASANTI |
Review History
| Department | Status | Date In | Date Out |
| PLFM | COMPLETE | 07/28/2020 | 07/28/2020 |
| Note: Released By: JMYERS The Final elevation certificate has been approved. | |||
| PLFM | COMPLETE | 11/13/2019 | 11/13/2019 |
| Note: Released By: JMYERS Please provide Final elevation certificate prior to receiving CO | |||
| MECH | COMPLETE | 05/21/2019 | 05/23/2019 |
| Note: Released By: RLEE | |||
| ELEC | COMPLETE | 05/21/2019 | 06/05/2019 |
| Note: Released By: RLEE | |||
| ARCHR | COMPLETE | 05/06/2019 | 05/09/2019 |
| Note: Released By: BDAWSON | |||
| BLD | COMPLETE | 05/06/2019 | 05/14/2019 |
| Note: Released By: JHINDMAN | |||
| DSD | COMPLETE | 05/06/2019 | 05/09/2019 |
| Note: Released By: DRAMIREZ | |||
| ELEC | HOLD | 05/06/2019 | 05/14/2019 |
| Note: Held By: JHINDMAN 1. Provide electrical load calculations per 2014 nec art.220 | |||
| FI1 | COMPLETE | 05/06/2019 | 05/14/2019 |
| Note: Released By: JHINDMAN | |||
| MECH | HOLD | 05/06/2019 | 05/14/2019 |
| Note: Held By: RLEE Provide mechanical layout and Energy Calculations with contractors signature and license. Identify location of unit in building and mounting. | |||
| PLUM | COMPLETE | 05/06/2019 | 05/14/2019 |
| Note: Released By: RLEE | |||
| UD1 | COMPLETE | 05/06/2019 | 05/07/2019 |
| Note: Released By: CJOHNSON |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| IMPACT FEE FIRE | ¤1,585.92 | 07/08/2020 |
| IMPACT FEE TRANSPORTATION | ¤2,402.40 | 07/08/2020 |
| MECHANICAL FEE | ¤120.00 | 06/06/2019 |
| PERMIT FEE | ¤550.00 | 06/06/2019 |
| PLAN CHECK FEE | ¤115.00 | 06/06/2019 |
| PLUMBING FEE | ¤120.00 | 06/06/2019 |
| SITE PLAN 20 | ¤20.00 | 06/06/2019 |
| SURCHARGE FS 533.721 | ¤11.05 | 06/06/2019 |
| SURCHARGE - FS 468.631 | ¤16.58 | 06/06/2019 |
| ADMIN COMMERCIAL | ¤60.00 | 06/06/2019 |
| ELECTRIC FEE | ¤120.00 | 06/06/2019 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤5,120.95 |