I want to search for...

Permit #2019050201

Permit Details

Status: FINAL

Parcel Id: 22-11-30-5545-00000-0010
Total Square Footage: 3600 sqft
Block: 00000
Subdivision: -
Location Address: 4500 US HWY 1 BLDG 400
Type: BC - BUILDING COMMERCIAL
Issue Date: 06/06/2019
NOC: RECORDED
Applicant name: LUIS JORGE MEDEIROS
Owner: TEAROC OF FLORIDA INC

Address

4490 N US 1 STE 111

BUNNELL, FL 32110

Lot: 0010
Contracted Stated Job Value: ¤100,000.00
Job Description: BLDG 400 - 90 X 40 STORAGE BUILDING (REF # 2018090500 FOR FOUNDATION)
Type: CN

Contractor

SUN STATE CUSTOM BUILDERS, LLC
Status Location Address State License Number
CANCEL

946 SHADICH DRIVE

ORANGE CITY, FL

CGC1519145 (Exp: 08/31/2022)

Sub Contractors

RICHARD R EDWARDS
Status Location Address State License Number Phone
CANCEL

P. O. Box 1637

Bunnell, FL 32110

ER0011603 (Exp: 08/31/2022) (386) 437-1537

Inspection History

Type Request Date Result Inspector
BUILDING FINAL 06/05/2020 FINAL APPROVED JCOLASANTI
U - UTILITY COMMERCIAL FINAL 06/04/2020 FINAL APPROVED LFITZGERALD
FIRE FINAL 06/02/2020 APPROVED WMILLER
Note: THIS IS A REINSPECTION 1. Missing Address... address identification FFPC 5th edition 10.12.1.5 minimum 6 inches in height 2. Fire extinguisher certification tags are out of date NFPA 10. 2. 3. Installation 13.6.3 Readily available… Conspicuously located along normal travel paths and exits and not obstructed from view and mounted 4. Travel distance for fire extinguishers exceeded... FFPC 1, 13.6.3.2.1.2.2 cannot exceed 75 ft.
FIRE FINAL 05/27/2020 Disapproved - NO FEE WMILLER
Note: 1. Missing Address... address identification FFPC 5th edition 10.12.1.5 minimum 6 inches in height 2. Fire extinguisher certification tags are out of date NFPA 10. 2. 3. Installation 13.6.3 Readily available… Conspicuously located along normal travel paths and exits and not obstructed from view and mounted 4. Travel distance for fire extinguishers exceeded... FFPC 1, 13.6.3.2.1.2.2 cannot exceed 75 ft.
ELECTRIC FINAL 05/11/2020 APPROVED RMARTIN
ELECTRIC 2ND ROUGH 05/08/2020 APPROVED RMARTIN
ELECTRIC 1ST ROUGH 05/07/2020 APPROVED - AS NOTED RMARTIN
Note: SITE STICKS ON SITE, UNDERGROUND IS GOOD
ROOF SHEATHING / BRACE / TIE DOWN 12/04/2019 APPROVED FWILLIS
INSULATION 11/12/2019 APPROVED JCOLASANTI
FRAMING 10/31/2019 APPROVED JCOLASANTI

Review History

Department Status Date In Date Out
PLFM COMPLETE 07/28/2020 07/28/2020
Note: Released By: JMYERS The Final elevation certificate has been approved.
PLFM COMPLETE 11/13/2019 11/13/2019
Note: Released By: JMYERS Please provide Final elevation certificate prior to receiving CO
MECH COMPLETE 05/21/2019 05/23/2019
Note: Released By: RLEE
ELEC COMPLETE 05/21/2019 06/05/2019
Note: Released By: RLEE
ARCHR COMPLETE 05/06/2019 05/09/2019
Note: Released By: BDAWSON
BLD COMPLETE 05/06/2019 05/14/2019
Note: Released By: JHINDMAN
DSD COMPLETE 05/06/2019 05/09/2019
Note: Released By: DRAMIREZ
ELEC HOLD 05/06/2019 05/14/2019
Note: Held By: JHINDMAN 1. Provide electrical load calculations per 2014 nec art.220
FI1 COMPLETE 05/06/2019 05/14/2019
Note: Released By: JHINDMAN
MECH HOLD 05/06/2019 05/14/2019
Note: Held By: RLEE Provide mechanical layout and Energy Calculations with contractors signature and license. Identify location of unit in building and mounting.
PLUM COMPLETE 05/06/2019 05/14/2019
Note: Released By: RLEE
UD1 COMPLETE 05/06/2019 05/07/2019
Note: Released By: CJOHNSON

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
IMPACT FEE FIRE ¤1,585.92 07/08/2020
IMPACT FEE TRANSPORTATION ¤2,402.40 07/08/2020
MECHANICAL FEE ¤120.00 06/06/2019
PERMIT FEE ¤550.00 06/06/2019
PLAN CHECK FEE ¤115.00 06/06/2019
PLUMBING FEE ¤120.00 06/06/2019
SITE PLAN 20 ¤20.00 06/06/2019
SURCHARGE FS 533.721 ¤11.05 06/06/2019
SURCHARGE - FS 468.631 ¤16.58 06/06/2019
ADMIN COMMERCIAL ¤60.00 06/06/2019
ELECTRIC FEE ¤120.00 06/06/2019
Fees Total Due: ¤0.00 Total Paid: ¤5,120.95