I want to search for...
Permit #2019060108
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7037-01030-0050 |
| Block: 01030 |
| Subdivision: 2176 - SECTION 37-LAKEVIEW |
| Job Phone: 386-597-3280 |
| Location Address: 9 LOUVET LN |
| Type: ME - MECHANICAL |
| Issue Date: 06/07/2019 |
| NOC: Unknown |
| Applicant name: GARY LLOYD SHEFFIELD |
| Owner: CREWS CHARLES & JOANIE H&W |
|
Address 9 LOUVET LANE PALM COAST, FL 32137 |
| Lot: 0050 |
| Contracted Stated Job Value: ¤4,400.00 |
| Job Description: 3.5 Ton 15 SEER |
| Type: CN |
Contractor
ADVANCED ENERGY SYSTEMS, PLLC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
48 EAGLE LAKES DRIVE FLAGLER BEACH, FL 32136 |
CAC048127 (Exp: 08/31/2026) | 386-597-3280 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 07/17/2019 | FINAL APPROVED | CPISCITELLI |
| Note: THIS IS A REINSPECTION | |||
| HVAC FINAL | 07/02/2019 | Disapproved -FEE REQUIRED | CPISCITELLI |
| Note: 1. MOCP RATING NOT MATCHING BREAKERS MFBC 1303. AHU Breaker calling for 45 Amp Breaker at 240V. Panel has a 40 AMP 2.DISCONNECT WITHIN SIGHT OF AIR CONDITIONING UNIT, AND READILY ACCESSIBLE..NEC 440.14. Disconnect in Closet is not Accessible. Can not open the door. It hits the AHU. |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 06/04/2019 | 06/04/2019 |
| Note: Released By: JHINDMAN |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 07/16/2019 |
| SURCHARGE FS 533.721 | ¤2.00 | 06/07/2019 |
| SURCHARGE - FS 468.631 | ¤2.00 | 06/07/2019 |
| ADMIN FEE | ¤20.00 | 06/07/2019 |
| INSPECTION 40 | ¤40.00 | 06/07/2019 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤104.00 |