Permit #2019080088

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7025-000A0-0011
Block: 000A0
Subdivision: 2189 - SECTION 25-PINE GROVE
Job Phone: 386-274-3120
Location Address: 1298 PALM COAST PKWY SW
Type: FU - FIRE UNDERGROUND
Issue Date: 09/06/2019
NOC: RECORDED
Applicant name: RICKY JOE ABERCROMBIE
Owner: PALM COAST/FUNDING ASSOC L.P. UNITED CORNERS

Address

525 PHARR RD NE

ATLANTA, GA 30305

Lot: 0011
Contracted Stated Job Value: ¤28,628.00
Job Description: Install 6" DIP U/G Fire Line. Install of 1 EA Fire Hydrant
Type: CN

Contractor

TOMOKA CONSTRUCTION SERVICES, INC
Status Location Address State License Number Phone Fax
INACTIVE

810 FENTRESS CT

DAYTONA BEACH, FL 32117

CUC1224170 (Exp: 08/31/2022) 386-274-3120 386-274-3170

Inspection History

Type Request Date Result Inspector
FIRE FINAL 10/31/2019 FINAL APPROVED WMILLER
FIRE SYSTEM FLUSH 09/26/2019 APPROVED MGARRETT
Note: Witnessed full bore flushing of underground fire line to building riser.
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 09/24/2019 APPROVED WMILLER
Note: THIS IS A REINSPECTION
FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR 09/23/2019 APPROVED WMILLER
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 09/23/2019 PARTIALLY APPROVED WMILLER
Note: THIS IS A REINSPECTION Partial approval for fire underground and tracer only marked on plans Still need to see warning tape when place prior to covering tape
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 09/20/2019 PARTIALLY APPROVED WMILLER
Note: THIS IS A REINSPECTION Partial approval for fire underground and tracer only marked on plans Still need to see warnoing tape when placed
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 09/19/2019 Disapproved - NO FEE WMILLER
Note: 1. Connection to Zurn Wilkins Riser is not correct per manufacturer Installation Instructions. 2. Coatings on underside bolts are not coated

Review History

Department Status Date In Date Out
FI1 HOLD 09/05/2019 09/05/2019
Note: Held By: WMILLER Please move Hydrant to new location with FDC as discussed.
FI1 COMPLETE 09/05/2019 09/06/2019
Note: Released By: WMILLER Approved with Red Lined Drawings Marked REVISION Will require as built and in field adjustments of FDC direction prior to final
FI1 HOLD 08/19/2019 09/05/2019
Note: Held By: WMILLER Please relocate the Hydrant and FDC as discussed with on site supervisor David Hester
FI1 HOLD 08/02/2019 08/12/2019
Note: Held By: WMILLER Relocate FDC away from building within 100 ft of hydrant... (FDC can not be located on building per AHJ)

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADMIN COMMERCIAL ¤60.00 09/06/2019
FIRE PLANS REVIEW ¤40.00 09/06/2019
SURCHARGE FS 533.721 ¤2.00 09/06/2019
SURCHARGE - FS 468.631 ¤2.00 09/06/2019
Fees Total Due: ¤0.00 Total Paid: ¤104.00