Permit #2019080247

Permit Details

Status: FINAL

Parcel Id: 25-10-30-4626-00000-00A0
Block: 00000
Subdivision: 2251 - NOTTINGHAM PHASE I-II (INFORMAL PLAT)
Job Phone: 386-274-3120
Location Address: 3895 OLD KINGS RD N
Type: FU - FIRE UNDERGROUND
Issue Date: 02/11/2020
NOC: Unknown
Applicant name: KYLE ROBERT HALL
Owner: 3895 OLD KINGS SP LLC C/O THE WILLIAM WARREN GROUP

Address

201 WILSHIRE BLVD, STE 102

SANTA MONICA, CA 90401

Lot: 00A0
Contracted Stated Job Value: ¤73,440.00
Job Description: FIRE MAIN
Type: CN

Contractor

TOMOKA CONSTRUCTION SERVICES, INC.
Status Location Address State License Number Phone Fax
ACTIVE

40 HOLLY STREET

HOLLY HILL, FL 32110

CUC1225507 (Exp: 08/31/2026) 386-274-3120 386-274-3170

Inspection History

Type Request Date Result Inspector
FIRE FINAL 06/24/2020 FINAL APPROVED WMILLER
Note: THIS IS A REINSPECTION Missing Contractor’s Material and Test Certificate for Underground Piping 6-24-2020.... MAterial and Test certificate received
FIRE FINAL 06/23/2020 Disapproved - NO FEE WMILLER
Note: Missing Contractor’s Material and Test Certificate for Underground Piping
HYDRANT FLOW TEST 06/12/2020 APPROVED WMILLER
HYDRANT FLOW TEST 06/04/2020 CANCELLED BY APPLICANT WEB
FIRE SYSTEM FLUSH 03/17/2020 APPROVED WMILLER
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 03/16/2020 APPROVED WMILLER
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION Fire mains depth and location only Still need to see warning tape and need approved plans and spec sheets, on site for future inspections (plans on site were not approved) (FDC's still need checked) Per notes above Looked at Warning Tape on Mains only
FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR 03/16/2020 APPROVED WMILLER
Note: THIS IS A REINSPECTION Fire mains only
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 03/09/2020 PARTIALLY APPROVED WMILLER
Note: THIS IS A REINSPECTION Fire mains depth and location only Still need to see warning tape and need approved plans and spec sheets, on site for future inspections (plans on site were not approved) (FDC's still need checked) Per notes above Looked at Warning Tape on Mains only
FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR 03/06/2020 PARTIALLY APPROVED WMILLER
Note: Fire mains only
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 03/06/2020 PARTIALLY APPROVED WMILLER
Note: Fire mains depth and location only Still need to see warning tape and need approved plans and spec sheets, on site for future inspections (plans on site were not approved) (FDC's still need checked)

Review History

Department Status Date In Date Out
FI1 COMPLETE 02/10/2020 02/11/2020
Note: Released By: WMILLER
FI1 HOLD 01/30/2020 02/10/2020
Note: Held By: WMILLER Notes for FDC on sheet 12 indicate Knox Locking caps, Locking caps are not permitted per AHJ and NFPA 13 6.8 Need to show check valves in accordance with NFPA 13 8.17.2.5.1 All FDC's must have a listed check valve
FI1 HOLD 01/16/2020 01/30/2020
Note: Held By: WMILLER Plans submitted cannot be uploaded as one file. Each sheet must be a separate pages and names according to the document requirements on the permit portal page. http://docs.palmcoastgov.com/departments/building/online/document-requirements.pdf
FI1 HOLD 08/07/2019 08/21/2019
Note: Held By: WMILLER Need digitally signed and sealed plans for review

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADMIN COMMERCIAL ¤60.00 02/11/2020
FIRE PLANS REVIEW ¤40.00 02/11/2020
SURCHARGE FS 533.721 ¤2.00 02/11/2020
SURCHARGE - FS 468.631 ¤2.00 02/11/2020
Fees Total Due: ¤0.00 Total Paid: ¤104.00