Permit #2019080247
Permit Details
Status: FINAL
| Parcel Id: 25-10-30-4626-00000-00A0 |
| Block: 00000 |
| Subdivision: 2251 - NOTTINGHAM PHASE I-II (INFORMAL PLAT) |
| Job Phone: 386-274-3120 |
| Location Address: 3895 OLD KINGS RD N |
| Type: FU - FIRE UNDERGROUND |
| Issue Date: 02/11/2020 |
| NOC: Unknown |
| Applicant name: KYLE ROBERT HALL |
| Owner: 3895 OLD KINGS SP LLC C/O THE WILLIAM WARREN GROUP |
|
Address 201 WILSHIRE BLVD, STE 102 SANTA MONICA, CA 90401 |
| Lot: 00A0 |
| Contracted Stated Job Value: ¤73,440.00 |
| Job Description: FIRE MAIN |
| Type: CN |
Contractor
TOMOKA CONSTRUCTION SERVICES, INC.
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
40 HOLLY STREET HOLLY HILL, FL 32110 |
CUC1225507 (Exp: 08/31/2026) | 386-274-3120 | 386-274-3170 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE FINAL | 06/24/2020 | FINAL APPROVED | WMILLER |
| Note: THIS IS A REINSPECTION Missing Contractor’s Material and Test Certificate for Underground Piping 6-24-2020.... MAterial and Test certificate received | |||
| FIRE FINAL | 06/23/2020 | Disapproved - NO FEE | WMILLER |
| Note: Missing Contractor’s Material and Test Certificate for Underground Piping | |||
| HYDRANT FLOW TEST | 06/12/2020 | APPROVED | WMILLER |
| HYDRANT FLOW TEST | 06/04/2020 | CANCELLED BY APPLICANT | WEB |
| FIRE SYSTEM FLUSH | 03/17/2020 | APPROVED | WMILLER |
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 03/16/2020 | APPROVED | WMILLER |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION Fire mains depth and location only Still need to see warning tape and need approved plans and spec sheets, on site for future inspections (plans on site were not approved) (FDC's still need checked) Per notes above Looked at Warning Tape on Mains only | |||
| FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR | 03/16/2020 | APPROVED | WMILLER |
| Note: THIS IS A REINSPECTION Fire mains only | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 03/09/2020 | PARTIALLY APPROVED | WMILLER |
| Note: THIS IS A REINSPECTION Fire mains depth and location only Still need to see warning tape and need approved plans and spec sheets, on site for future inspections (plans on site were not approved) (FDC's still need checked) Per notes above Looked at Warning Tape on Mains only | |||
| FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR | 03/06/2020 | PARTIALLY APPROVED | WMILLER |
| Note: Fire mains only | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 03/06/2020 | PARTIALLY APPROVED | WMILLER |
| Note: Fire mains depth and location only Still need to see warning tape and need approved plans and spec sheets, on site for future inspections (plans on site were not approved) (FDC's still need checked) |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 02/10/2020 | 02/11/2020 |
| Note: Released By: WMILLER | |||
| FI1 | HOLD | 01/30/2020 | 02/10/2020 |
| Note: Held By: WMILLER Notes for FDC on sheet 12 indicate Knox Locking caps, Locking caps are not permitted per AHJ and NFPA 13 6.8 Need to show check valves in accordance with NFPA 13 8.17.2.5.1 All FDC's must have a listed check valve | |||
| FI1 | HOLD | 01/16/2020 | 01/30/2020 |
| Note: Held By: WMILLER Plans submitted cannot be uploaded as one file. Each sheet must be a separate pages and names according to the document requirements on the permit portal page. http://docs.palmcoastgov.com/departments/building/online/document-requirements.pdf | |||
| FI1 | HOLD | 08/07/2019 | 08/21/2019 |
| Note: Held By: WMILLER Need digitally signed and sealed plans for review |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADMIN COMMERCIAL | ¤60.00 | 02/11/2020 |
| FIRE PLANS REVIEW | ¤40.00 | 02/11/2020 |
| SURCHARGE FS 533.721 | ¤2.00 | 02/11/2020 |
| SURCHARGE - FS 468.631 | ¤2.00 | 02/11/2020 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤104.00 |