I want to search for...

Permit #2019080937

Permit Details

Status: FINAL

Parcel Id: 06-12-31-5825-00000-0220
Block: 00000
Subdivision: 2111 - TOWN CENTER PHASE II
Job Phone: 386-437-1257
Location Address: 10000 COASTAL TRACE BLDG 8
Type: FU - FIRE UNDERGROUND
Issue Date: 11/05/2019
NOC: Unknown
Applicant name: CHELSEA MARIE BARNEY
Owner: CENTRAL LANDINGS PARTNERS LTD & CENTRAL LANDINGS 8

Address

335 N KNOWLES AVE STE 101

WINTER PARK, FL 32789

Lot: 0220
Contracted Stated Job Value: ¤18,478.00
Job Description: BLDG. 8- UNDERGROUND FIRE LINE WITH FDC, DCDA AND IN BUILDING RISER.
Type: CN

Contractor

4C'S TRUCKING & EXCAVATION INC
Status Location Address State License Number Phone Fax
ACTIVE

PO BOX 2682

BUNNELL, FL 32110

FPC15-000050 (Exp: 06/30/2026) 386-437-1257 386-437-4468

Inspection History

Type Request Date Result Inspector
FIRE FINAL 03/30/2020 FINAL APPROVED WMILLER
FIRE SYSTEM FLUSH 12/03/2019 APPROVED WMILLER
Note: added at the request of Mike on site
FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR 12/03/2019 APPROVED WMILLER
Note: Added at the request of Contractor
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 11/22/2019 APPROVED WMILLER
Note: THIS IS A REINSPECTION
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 11/06/2019 PARTIALLY APPROVED WMILLER
Note: Looked at riser, riser thrust, and riser to plastic pipe restraint only.

Review History

Department Status Date In Date Out
FI1 COMPLETE 10/28/2019 11/04/2019
Note: Released By: WMILLER
FI1 HOLD 10/22/2019 10/28/2019
Note: Held By: WMILLER Please upload the correct file for review (only an image of the adobe acrobat reader was uploaded)
FI1 HOLD 10/08/2019 10/16/2019
Note: Held By: WMILLER Hold per conversation with Designer/architect
FI1 HOLD 10/07/2019 10/08/2019
Note: Held By: WMILLER Please upload the drawings for review (only a picture of the Adobe reader was uploaded)
FI1 HOLD 09/11/2019 09/25/2019
Note: Held By: WMILLER I spoke with Teresa Benton (with the Engineers of Record, Gulf Stream Design) Who approached me onsight and asked if I knew what the status of this Review was. I explained the FDC is now shown located with parking in front or it. I explained I wanted to make sure if they had to Hash out the Parking space it wasnt going to cause Problems on the Building Approvals. She stated she had an easy solution and is going to move the Fdc to a location that will not have parking space in front of it. Please upload revision as soon as possible.
FI1 HOLD 09/06/2019 09/11/2019
Note: Held By: WMILLER Revision needed to relocate FDC within 100 feet of supply
FI1 HOLD 08/23/2019 09/05/2019
Note: Held By: WMILLER Please show distance between Supply and FDC... Fire Department Connection within 100' of the hydrant (NFPA 14 6.4.5.4.0

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADMIN COMMERCIAL ¤60.00 11/05/2019
FIRE PLANS REVIEW ¤40.00 11/05/2019
SURCHARGE FS 533.721 ¤2.00 11/05/2019
SURCHARGE - FS 468.631 ¤2.00 11/05/2019
Fees Total Due: ¤0.00 Total Paid: ¤104.00