I want to search for...
Permit #2019080946
Permit Details
Status: FINAL
| Parcel Id: 06-12-31-5825-00000-0220 |
| Block: 00000 |
| Subdivision: 2111 - TOWN CENTER PHASE II |
| Job Phone: 386-437-1257 |
| Location Address: 5000 SUNSET BLVD BLDG 6 |
| Type: FU - FIRE UNDERGROUND |
| Issue Date: 09/16/2019 |
| NOC: Unknown |
| Applicant name: CHELSEA MARIE BARNEY |
| Owner: CENTRAL LANDINGS PARTNERS LTD & CENTRAL LANDINGS 8 |
|
Address 335 N KNOWLES AVE STE 101 WINTER PARK, FL 32789 |
| Lot: 0220 |
| Contracted Stated Job Value: ¤18,478.00 |
| Job Description: BLDG. 6- UNDERGROUND FIRE LINE WITH FDC, DCDA AND IN BUILDING RISER. |
| Type: CN |
Contractor
4C'S TRUCKING & EXCAVATION INC
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
PO BOX 2682 BUNNELL, FL 32110 |
FPC15-000050 (Exp: 06/30/2026) | 386-437-1257 | 386-437-4468 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE FINAL | 05/13/2020 | FINAL APPROVED | WMILLER |
| FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR | 12/04/2019 | APPROVED | WMILLER |
| Note: THIS IS A REINSPECTION | |||
| FIRE SYSTEM FLUSH | 12/04/2019 | APPROVED | WMILLER |
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 12/04/2019 | APPROVED | WMILLER |
| Note: THIS IS A REINSPECTION Was witnessed prior | |||
| FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR | 11/21/2019 | CANCELLED BY APPLICANT | WMILLER |
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 10/30/2019 | Disapproved - NO FEE | WMILLER |
| Note: THIS IS A REINSPECTION Lines have been covered up and need to be exposed for inspection of thrust blocks, Warning tape will also need to be Inspected when placed | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 10/29/2019 | PARTIALLY APPROVED | WMILLER |
| Note: Placement, Tracing wire, and hardware coatings only. Still need to see thrust blocks in place and warning tape! Circled on Plans |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 09/06/2019 | 09/11/2019 |
| Note: Released By: WMILLER Redline distance ok for submittal, contractor will need to verify distance from FDC to Supply does not exceed 100 feet as built. | |||
| FI1 | HOLD | 08/23/2019 | 09/05/2019 |
| Note: Held By: WMILLER Please show distance between Supply and FDC... Fire Department Connection within 100' of the hydrant (NFPA 14 6.4.5.4.0 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADMIN COMMERCIAL | ¤60.00 | 09/16/2019 |
| FIRE PLANS REVIEW | ¤40.00 | 09/16/2019 |
| SURCHARGE FS 533.721 | ¤2.00 | 09/16/2019 |
| SURCHARGE - FS 468.631 | ¤2.00 | 09/16/2019 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤104.00 |