Permit #2019100375
Permit Details
Status: COED
| Parcel Id: 07-11-31-7001-0RPAB-0011 |
| Total Square Footage: 7471 sqft |
| Block: 0RPAB |
| Subdivision: 2143 - SECTION 1-FLORIDA PARK |
| Job Phone: (904)241-4477 |
| Location Address: 10 PALM HARBOR VILLAGE WAY |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 11/22/2019 |
| NOC: RECORDED |
| Applicant name: DARRELL GLEN SMITH |
| Owner: ALKHOURY PROPERTY MANAGEMENT INC |
|
Address PO BOX 3406 ST AUGUSTINE, FL 32085 |
| Lot: 0011 |
| Contracted Stated Job Value: ¤150,000.00 |
| Job Description: INTERIOR BUILDOUT- "CANTINA LOUIE" RESTAURANT |
| Type: CN |
Contractor
STYLES CONSTRUCTION INC.
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
PO BOX 50067 JACKSONVILLE BEACH, FL 32250 |
CBC1250669 (Exp: 08/31/2022) | (904)241-4477 | (904)241-0817 |
Sub Contractors
STYLES WAYNE SMITH
| Status | Location Address | State License Number | Phone |
| CANCEL |
PO BOX 330130 JACKSONVILLE, FL 32250 |
CFC1428682 (Exp: 10/31/2020) | 904-241-4131 |
BERNARD V ELLIOTT III
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
4533 SUNBEAM ROAD # 493 JACKSONVILLE, FL 32257 |
CAC057663 (Exp: 08/31/2024) | 904-662-2792 | 904-221-5560 |
ROBERT MCCLURE JR
| Status | Location Address | State License Number | Phone |
| CANCEL |
1521 INVERNESS ROAD FERNANDINA, FL 32034 |
ER0008818 (Exp: 08/31/2020) | 904-237-4701 |
DARRELL GLEN SMITH
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
PO BOX 50067 JACKSONVILLE BEACH, FL 32250 |
CBC1250669 (Exp: 08/31/2022) | (904)241-4477 | (904)241-0817 |
Inspection History
| Type | Request Date | Result | Inspector |
| BUILDING FINAL | 06/02/2020 | FINAL APPROVED | WMILLER |
| FIRE FINAL | 06/02/2020 | APPROVED | WMILLER |
| U - UTILITY COMMERCIAL FINAL | 06/02/2020 | FINAL APPROVED | LFITZGERALD |
| U-GREASE INTERCEPTOR FLOW/DYE TESTED | 06/01/2020 | APPROVED | LFITZGERALD |
| LDSC-PRE-PLANTING TREE QUALITY | 06/01/2020 | CANCELLED BY INSPECTOR | BDAWSON |
| Note: Landscape Bond Provided | |||
| LDSC-IRRIGATION FINAL | 06/01/2020 | CANCELLED BY INSPECTOR | BDAWSON |
| Note: Landscape Bond Provided | |||
| LDSC- SUBSTANTIAL COMPLETE (OFFICE USE) | 06/01/2020 | CANCELLED BY INSPECTOR | BDAWSON |
| Note: Landscape Bond Provided | |||
| LDSC- LANDSCAPE FINAL | 06/01/2020 | CANCELLED BY INSPECTOR | BDAWSON |
| Note: Landscape Bond Provided | |||
| PLUMBING FINAL | 06/01/2020 | APPROVED | JGIBSON |
| Note: THIS IS A REINSPECTION NEEDWALL PLATE COVERS, MISSING SHOCK ARRESTOR AT ICE MACHINE, WATER NOT HOT IN KIT. AREASINK AT WAITRESS AREA FLOOR SINK NOT DRAING MISSING ESCUSSION AT DISHWASHER | |||
| HVAC FINAL | 06/01/2020 | FINAL APPROVED | CPISCITELLI |
| Note: THIS IS A REINSPECTION | |||
| ELECTRIC FINAL | 06/01/2020 | APPROVED | RMARTIN |
| Note: THIS IS A REINSPECTION NEED DISCONNECT ON INSIDE OF ONE COOLER, NEED ARC SHEILDS ON A FEW OUTLETS CHECK ALL, NEED CORRECT BREAKER SIZES AND MARK RTU.....NEC 314.20, 440.14 6/1/20 corrected issues | |||
| GAS FINAL | 06/01/2020 | APPROVED | JGIBSON |
| Note: THIS IS A REINSPECTION NEED GAS LINE INCREASED TO 1/2'' AT WATER HEATER | |||
| ELECTRIC FINAL | 05/29/2020 | Disapproved - NO FEE | RMARTIN |
| Note: NEED DISCONNECT ON INSIDE OF ONE COOLER, NEED ARC SHEILDS ON A FEW OUTLETS CHECK ALL, NEED CORRECT BREAKER SIZES AND MARK RTU.....NEC 314.20, 440.14 | |||
| GAS FINAL | 05/29/2020 | PARTIALLY APPROVED | JGIBSON |
| Note: NEED GAS LINE INCREASED TO 1/2'' AT WATER HEATER | |||
| HOOD FINAL | 05/29/2020 | APPROVED | CPISCITELLI |
| Note: THIS IS A REINSPECTION ADDED ON 5/15/2020 11:02:30 AM THIS IS A REINSPECTION | |||
| HVAC FINAL | 05/29/2020 | Disapproved - NO FEE | CPISCITELLI |
| Note: not ready | |||
| PLUMBING FINAL | 05/29/2020 | PARTIALLY APPROVED | JGIBSON |
| Note: NEEDWALL PLATE COVERS, MISSING SHOCK ARRESTOR AT ICE MACHINE, WATER NOT HOT IN KIT. AREASINK AT WAITRESS AREA FLOOR SINK NOT DRAING MISSING ESCUSSION AT DISHWASHER | |||
| HVAC ROUGH | 05/28/2020 | APPROVED | CPISCITELLI |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION Inspected duct in back of kitchen | |||
| HOOD ROUGH | 05/15/2020 | APPROVED | CPISCITELLI |
| HOOD FINAL | 05/15/2020 | CANCELLED BY APPLICANT | CPISCITELLI |
| Note: THIS IS A REINSPECTION | |||
| ELECTRIC 2ND ROUGH | 05/07/2020 | APPROVED - AS NOTED | RMARTIN |
| Note: NEED TO LOOK AT COOLER CONNECTIONS ON FINAL | |||
| HOOD DUCT AND LIGHTING TEST | 05/07/2020 | APPROVED | CPISCITELLI |
| HOOD FINAL | 05/07/2020 | CANCELLED BY APPLICANT | CPISCITELLI |
| PLUMBING 2ND ROUGH | 05/07/2020 | APPROVED | JGIBSON |
| Note: THIS IS A REINSPECTION WRONG INSPECTION CALLED IN | |||
| EXTERIOR ARCHITECTURAL FEATURES | 05/07/2020 | APPROVED | MBACON |
| PLUMBING 2ND ROUGH | 03/19/2020 | Disapproved - NO FEE | JGIBSON |
| Note: WRONG INSPECTION CALLED IN | |||
| ELECTRIC 2ND ROUGH | 03/19/2020 | PARTIALLY APPROVED | RMARTIN |
| Note: KITCHEN AREA, LOOK AT COOLER CONNECTIONS AND ANSUL ON LATER INSPECTION | |||
| HVAC ROUGH | 03/19/2020 | PARTIALLY APPROVED | CPISCITELLI |
| Note: THIS IS A REINSPECTION Inspected duct in back of kitchen | |||
| GAS ROUGH | 03/19/2020 | APPROVED - AS NOTED | JGIBSON |
| Note: PER APPROVAL OF PLAN EXAMINER GAS RISER MATCHES, OK TO COVER CEILING WHERE GAS IS. NEED TO REMOVE ALL EXISTING OLD GAS LINES | |||
| FRAMING | 02/12/2020 | APPROVED | JDELBONIS |
| STOREFRONT | 02/12/2020 | APPROVED | JDELBONIS |
| INSULATION | 02/11/2020 | APPROVED | JDELBONIS |
| Note: THIS IS A REINSPECTION | |||
| PLUMBING 2ND ROUGH | 02/10/2020 | APPROVED - AS NOTED | JGIBSON |
| Note: THIS IS A REINSPECTION PER APPROVAL OF PLANS EXANINER '' MECHANICAL'' RELOCATION OF GAS WATER HEATER AND SIZE AND GAS RISER WASTE AND VENT TEST APPROVED WATER LINES ARE UNDER TEST AND APPROVED. CHECK PLANS FOR RECIRCULATION AND INSULATION | |||
| PLUMBING 2ND ROUGH | 02/10/2020 | APPROVED | JGIBSON |
| PLUMBING 2ND ROUGH | 02/07/2020 | PARTIALLY APPROVED | JGIBSON |
| Note: PROPERLY, VENTED, NO TEST ON WATER LINES,NOR ON WASTE AND VENT, ROOF DRAIN OVER COMERCIAL HOOD TO BE OFF SET AND TESTED, GAS NOT DONE, NEED REVISION ON RELOCATION OF TANKLESS WATER HEATERS, 3 TOTAL | |||
| HVAC ROUGH | 02/07/2020 | PARTIALLY APPROVED | CPISCITELLI |
| Note: Inspected main trunk lines over offices and front entry | |||
| ELECTRIC 1ST ROUGH | 02/07/2020 | APPROVED | RMARTIN |
| ELECTRIC 2ND ROUGH | 02/07/2020 | PARTIALLY APPROVED | RMARTIN |
| Note: MARKED ON PLAN, WALLS | |||
| INSULATION | 02/07/2020 | CANCELLED BY APPLICANT | WMILLER |
| FOOTER | 01/16/2020 | APPROVED | JDELBONIS |
| PLUMBING 1ST ROUGH | 01/16/2020 | APPROVED - AS NOTED | JGIBSON |
| Note: THIS IS A REINSPECTION THIS WAS PER RISER DIAGRAM NEEDS TO BE SIGNED AND SEALED | |||
| PLUMBING 1ST ROUGH | 01/10/2020 | PARTIALLY APPROVED | JGIBSON |
| Note: THIS APPROVAL IS BASED ''ONLY WHEN SIGHED AND SEALED PLUMBING RISER DIAGRAM HAS BEEN SUBMITTED AND APPROVED BY PLANS EXAMINER '' NO CONCRETE TO BE POURED UNTIL THIS STEP HAS BEEN DONE. | |||
| ABOVE CEILING | 01/10/2020 | APPROVED - AS NOTED | RMARTIN |
| Note: EMAILED FPL RELEASED POWER 11:30 | |||
| PLUMBING 1ST ROUGH | 12/23/2019 | Disapproved -FEE REQUIRED | JGIBSON |
| Note: THIS IS A REINSPECTION NOT READY, P-312. 3 ALL SANITARY AND GREASE LINES ARE TO BE TESTED IN SECTION OR IN IT`S INTIRIETY NOT READY | |||
| PLUMBING 1ST ROUGH | 12/20/2019 | CANCELLED BY APPLICANT | JGIBSON |
| FOOTER | 12/13/2019 | APPROVED | JDELBONIS |
Review History
| Department | Status | Date In | Date Out |
| ARCHR | CANCEL | 06/01/2020 | 06/01/2020 |
| Note: Landscape bond w/ plans provided | |||
| MECH | COMPLETE | 04/27/2020 | 04/29/2020 |
| Note: Released By: CPISCITELLI | |||
| BLD | COMPLETE | 04/13/2020 | 04/24/2020 |
| Note: Released By: FREODICA | |||
| MECH | HOLD | 04/13/2020 | 04/17/2020 |
| Note: Held By: CPISCITELLI 1. Upload a complete (emphasis on complete) copy of the ETL listing for the hood. 2. Revise and upload plan sheet M-5 to reflect the installation details used by the contractor. This so there is a record between design and installation and an agreement to the installation by the engineer of record (albeit after the fact). Be sure fastener types and cementitious wallboard type are described- Your description below did not include any information. 3. Please provide a digital signature on all mechanical plan sheets and engineering analysis that complies with Florida Administrative Code 61G15-23.004. | |||
| BLD | COMPLETE | 03/16/2020 | 03/16/2020 |
| Note: Released By: FREODICA not applicable | |||
| ARCHR | HOLD | 03/16/2020 | 03/30/2020 |
| Note: Held By: BDAWSON - Provide DBH and species of existing trees on site. - Provide mitigation calculations. - Provide tree density calculations. - Show, label and dimension landscape buffers on plans. 10' w. Buffer A North & West, 10' w. Buffer C on East and 25' w. Buffer G South. - Refer to LDC 11.03.05 for landscape buffer requirements. Call City Landscape Architect at 386-302-7057 if clarification is needed. - Provide medium screen shrub around dumpster. - Provide medium screen shrub around any other above ground utiliies/equipment. - If there are any parking lights on site show them on plan to ensure 15' separation between pole and any new shade trees on site. - Provide irrigation plans. Indicate water source for irrigation on plans. Please note that 50% of new landscape must be drought tolerant or native if re-use is not the source. - Show sight triangles on plan. Pull back any proposed landscape buffer plantings as needed to not create sight visibility issues. - Provide an 8' average minimum foundation planting bed along South side of building walkway w/ 2 layers of plantings and 1 understory tree per 50 lf of building. - Provide (3) sabal palms in each VUA landscape island to replace lost credits of trees being removed from these areas. - Specify type of mulch being used. - Provide tree and palm planting/staking details. | |||
| PLUM | COMPLETE | 03/16/2020 | 03/16/2020 |
| Note: Released By: FREODICA | |||
| BLD | COMPLETE | 03/11/2020 | 03/12/2020 |
| Note: Released By: FREODICA Not applicable | |||
| PLUM | HOLD | 03/09/2020 | 03/10/2020 |
| Note: Held By: FREODICA Repeat comment: Revision: changed plumbing riser diagram (sanitary and grease lines) 1. Sanitary and grease layouts do not match with riser diagram. Coordinate the piping layout, pipe sizes, and identify the fixtures and specify if they are new or existing for clarity per FBC 6th ed. 107.2.1. FReodica-386-986-4734 | |||
| PLFM | CANCEL | 03/09/2020 | 03/09/2020 |
| Note: Floodplain review not required, structure is not in a flood zone. | |||
| ZON | CANCEL | 03/09/2020 | 03/09/2020 |
| ARCHR | COMPLETE | 03/09/2020 | 03/11/2020 |
| Note: Released By: BDAWSON | |||
| ELEC | COMPLETE | 02/28/2020 | 03/05/2020 |
| Note: Released By: JMUNSON | |||
| PLUM | HOLD | 02/28/2020 | 03/02/2020 |
| Note: Held By: FREODICA Revision: Gas riser and domastic water diagrams. Gas riser diagram does not include the (3) gas heaters at patio. Coordinate with gas layout for clarity per FBC 6th ed. sec. 107.2.1. FReodica - 386-986-4734. | |||
| PLUM | HOLD | 02/07/2020 | 03/02/2020 |
| Note: Held By: FREODICA Revision: changed plumbing riser diagram (sanitary and grease lines) 1. Sanitary and grease layouts do not match with riser diagram. Coordinate the piping layout, pipe sizes, and identify the fixtures and specify if they are new or existing for clarity per FBC 6th ed. 107.2.1. FReodica-386-986-4734 | |||
| BLD | COMPLETE | 01/22/2020 | 02/07/2020 |
| Note: Released By: FREODICA Revision : Sheet A3.2 - changed parapet from slope to vertical | |||
| UD1 | COMPLETE | 11/19/2019 | 11/19/2019 |
| Note: Released By: CJOHNSON | |||
| MECH | COMPLETE | 11/06/2019 | 11/13/2019 |
| Note: Released By: CPISCITELLI | |||
| UD1 | HOLD | 11/06/2019 | 11/07/2019 |
| Note: Held By: CJOHNSON Add note on P-1 and P-3 "Pump out and clean existing grease interceptors. Verify with Utility inspector that the grease interceptors are in good condition and plumbed properly." | |||
| BLD | COMPLETE | 10/09/2019 | 10/22/2019 |
| Note: Released By: MGARRETT | |||
| ELEC | COMPLETE | 10/09/2019 | 10/21/2019 |
| Note: Released By: JMUNSON | |||
| FI1 | COMPLETE | 10/09/2019 | 10/22/2019 |
| Note: Released By: WMILLER | |||
| MECH | HOLD | 10/09/2019 | 10/17/2019 |
| Note: Held By: CPISCITELLI Provide rooftop plan showing penetration details. Need hood duct detail through building including clearance from commbustibles. Could not find hinged detail on fan. Provide more detailed duct drawing showing all units with freshair ducts penetrations. Please describe method of access to roof top units | |||
| PLUM | COMPLETE | 10/09/2019 | 10/22/2019 |
| Note: Released By: MGARRETT | |||
| UD1 | HOLD | 10/09/2019 | 10/14/2019 |
| Note: Held By: CJOHNSON Add note on P-1 and P-3 Pump out and clean existing grease interceptors. Verify with Utility inspector that the grease interceptors are in good condition and plumbed properly. | |||
| ZON | COMPLETE | 10/09/2019 | 10/10/2019 |
| Note: Released By: JGONZALEZ |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REVISION | ¤40.00 | 06/01/2020 |
| REINSPECTION FEE | ¤40.00 | 03/16/2020 |
| REVISION | ¤40.00 | 03/16/2020 |
| SITE PLAN 20 | ¤20.00 | 11/22/2019 |
| SURCHARGE FS 533.721 | ¤5.30 | 11/22/2019 |
| SURCHARGE - FS 468.631 | ¤7.95 | 11/22/2019 |
| ADMIN COMMERCIAL | ¤60.00 | 11/22/2019 |
| INSPECTION - COMMERCIAL ADD | ¤1,050.00 | 11/22/2019 |
| ELECTRIC FEE | ¤150.00 | 11/22/2019 |
| MECHANICAL FEE | ¤150.00 | 11/22/2019 |
| PLAN CHECK FEE | ¤172.50 | 11/22/2019 |
| PLUMBING FEE | ¤150.00 | 11/22/2019 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤1,885.75 |