Permit #2019100375

Permit Details

Status: COED

Parcel Id: 07-11-31-7001-0RPAB-0011
Total Square Footage: 7471 sqft
Block: 0RPAB
Subdivision: 2143 - SECTION 1-FLORIDA PARK
Job Phone: (904)241-4477
Location Address: 10 PALM HARBOR VILLAGE WAY
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 11/22/2019
NOC: RECORDED
Applicant name: DARRELL GLEN SMITH
Owner: ALKHOURY PROPERTY MANAGEMENT INC

Address

PO BOX 3406

ST AUGUSTINE, FL 32085

Lot: 0011
Contracted Stated Job Value: ¤150,000.00
Job Description: INTERIOR BUILDOUT- "CANTINA LOUIE" RESTAURANT
Type: CN

Contractor

STYLES CONSTRUCTION INC.
Status Location Address State License Number Phone Fax
CANCEL

PO BOX 50067

JACKSONVILLE BEACH, FL 32250

CBC1250669 (Exp: 08/31/2022) (904)241-4477 (904)241-0817

Sub Contractors

STYLES WAYNE SMITH
Status Location Address State License Number Phone
CANCEL

PO BOX 330130

JACKSONVILLE, FL 32250

CFC1428682 (Exp: 10/31/2020) 904-241-4131
BERNARD V ELLIOTT III
Status Location Address State License Number Phone Fax
INACTIVE

4533 SUNBEAM ROAD # 493

JACKSONVILLE, FL 32257

CAC057663 (Exp: 08/31/2024) 904-662-2792 904-221-5560
ROBERT MCCLURE JR
Status Location Address State License Number Phone
CANCEL

1521 INVERNESS ROAD

FERNANDINA, FL 32034

ER0008818 (Exp: 08/31/2020) 904-237-4701
DARRELL GLEN SMITH
Status Location Address State License Number Phone Fax
CANCEL

PO BOX 50067

JACKSONVILLE BEACH, FL 32250

CBC1250669 (Exp: 08/31/2022) (904)241-4477 (904)241-0817

Inspection History

Type Request Date Result Inspector
BUILDING FINAL 06/02/2020 FINAL APPROVED WMILLER
FIRE FINAL 06/02/2020 APPROVED WMILLER
U - UTILITY COMMERCIAL FINAL 06/02/2020 FINAL APPROVED LFITZGERALD
U-GREASE INTERCEPTOR FLOW/DYE TESTED 06/01/2020 APPROVED LFITZGERALD
LDSC-PRE-PLANTING TREE QUALITY 06/01/2020 CANCELLED BY INSPECTOR BDAWSON
Note: Landscape Bond Provided
LDSC-IRRIGATION FINAL 06/01/2020 CANCELLED BY INSPECTOR BDAWSON
Note: Landscape Bond Provided
LDSC- SUBSTANTIAL COMPLETE (OFFICE USE) 06/01/2020 CANCELLED BY INSPECTOR BDAWSON
Note: Landscape Bond Provided
LDSC- LANDSCAPE FINAL 06/01/2020 CANCELLED BY INSPECTOR BDAWSON
Note: Landscape Bond Provided
PLUMBING FINAL 06/01/2020 APPROVED JGIBSON
Note: THIS IS A REINSPECTION NEEDWALL PLATE COVERS, MISSING SHOCK ARRESTOR AT ICE MACHINE, WATER NOT HOT IN KIT. AREASINK AT WAITRESS AREA FLOOR SINK NOT DRAING MISSING ESCUSSION AT DISHWASHER
HVAC FINAL 06/01/2020 FINAL APPROVED CPISCITELLI
Note: THIS IS A REINSPECTION
ELECTRIC FINAL 06/01/2020 APPROVED RMARTIN
Note: THIS IS A REINSPECTION NEED DISCONNECT ON INSIDE OF ONE COOLER, NEED ARC SHEILDS ON A FEW OUTLETS CHECK ALL, NEED CORRECT BREAKER SIZES AND MARK RTU.....NEC 314.20, 440.14 6/1/20 corrected issues
GAS FINAL 06/01/2020 APPROVED JGIBSON
Note: THIS IS A REINSPECTION NEED GAS LINE INCREASED TO 1/2'' AT WATER HEATER
ELECTRIC FINAL 05/29/2020 Disapproved - NO FEE RMARTIN
Note: NEED DISCONNECT ON INSIDE OF ONE COOLER, NEED ARC SHEILDS ON A FEW OUTLETS CHECK ALL, NEED CORRECT BREAKER SIZES AND MARK RTU.....NEC 314.20, 440.14
GAS FINAL 05/29/2020 PARTIALLY APPROVED JGIBSON
Note: NEED GAS LINE INCREASED TO 1/2'' AT WATER HEATER
HOOD FINAL 05/29/2020 APPROVED CPISCITELLI
Note: THIS IS A REINSPECTION ADDED ON 5/15/2020 11:02:30 AM THIS IS A REINSPECTION
HVAC FINAL 05/29/2020 Disapproved - NO FEE CPISCITELLI
Note: not ready
PLUMBING FINAL 05/29/2020 PARTIALLY APPROVED JGIBSON
Note: NEEDWALL PLATE COVERS, MISSING SHOCK ARRESTOR AT ICE MACHINE, WATER NOT HOT IN KIT. AREASINK AT WAITRESS AREA FLOOR SINK NOT DRAING MISSING ESCUSSION AT DISHWASHER
HVAC ROUGH 05/28/2020 APPROVED CPISCITELLI
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION Inspected duct in back of kitchen
HOOD ROUGH 05/15/2020 APPROVED CPISCITELLI
HOOD FINAL 05/15/2020 CANCELLED BY APPLICANT CPISCITELLI
Note: THIS IS A REINSPECTION
ELECTRIC 2ND ROUGH 05/07/2020 APPROVED - AS NOTED RMARTIN
Note: NEED TO LOOK AT COOLER CONNECTIONS ON FINAL
HOOD DUCT AND LIGHTING TEST 05/07/2020 APPROVED CPISCITELLI
HOOD FINAL 05/07/2020 CANCELLED BY APPLICANT CPISCITELLI
PLUMBING 2ND ROUGH 05/07/2020 APPROVED JGIBSON
Note: THIS IS A REINSPECTION WRONG INSPECTION CALLED IN
EXTERIOR ARCHITECTURAL FEATURES 05/07/2020 APPROVED MBACON
PLUMBING 2ND ROUGH 03/19/2020 Disapproved - NO FEE JGIBSON
Note: WRONG INSPECTION CALLED IN
ELECTRIC 2ND ROUGH 03/19/2020 PARTIALLY APPROVED RMARTIN
Note: KITCHEN AREA, LOOK AT COOLER CONNECTIONS AND ANSUL ON LATER INSPECTION
HVAC ROUGH 03/19/2020 PARTIALLY APPROVED CPISCITELLI
Note: THIS IS A REINSPECTION Inspected duct in back of kitchen
GAS ROUGH 03/19/2020 APPROVED - AS NOTED JGIBSON
Note: PER APPROVAL OF PLAN EXAMINER GAS RISER MATCHES, OK TO COVER CEILING WHERE GAS IS. NEED TO REMOVE ALL EXISTING OLD GAS LINES
FRAMING 02/12/2020 APPROVED JDELBONIS
STOREFRONT 02/12/2020 APPROVED JDELBONIS
INSULATION 02/11/2020 APPROVED JDELBONIS
Note: THIS IS A REINSPECTION
PLUMBING 2ND ROUGH 02/10/2020 APPROVED - AS NOTED JGIBSON
Note: THIS IS A REINSPECTION PER APPROVAL OF PLANS EXANINER '' MECHANICAL'' RELOCATION OF GAS WATER HEATER AND SIZE AND GAS RISER WASTE AND VENT TEST APPROVED WATER LINES ARE UNDER TEST AND APPROVED. CHECK PLANS FOR RECIRCULATION AND INSULATION
PLUMBING 2ND ROUGH 02/10/2020 APPROVED JGIBSON
PLUMBING 2ND ROUGH 02/07/2020 PARTIALLY APPROVED JGIBSON
Note: PROPERLY, VENTED, NO TEST ON WATER LINES,NOR ON WASTE AND VENT, ROOF DRAIN OVER COMERCIAL HOOD TO BE OFF SET AND TESTED, GAS NOT DONE, NEED REVISION ON RELOCATION OF TANKLESS WATER HEATERS, 3 TOTAL
HVAC ROUGH 02/07/2020 PARTIALLY APPROVED CPISCITELLI
Note: Inspected main trunk lines over offices and front entry
ELECTRIC 1ST ROUGH 02/07/2020 APPROVED RMARTIN
ELECTRIC 2ND ROUGH 02/07/2020 PARTIALLY APPROVED RMARTIN
Note: MARKED ON PLAN, WALLS
INSULATION 02/07/2020 CANCELLED BY APPLICANT WMILLER
FOOTER 01/16/2020 APPROVED JDELBONIS
PLUMBING 1ST ROUGH 01/16/2020 APPROVED - AS NOTED JGIBSON
Note: THIS IS A REINSPECTION THIS WAS PER RISER DIAGRAM NEEDS TO BE SIGNED AND SEALED
PLUMBING 1ST ROUGH 01/10/2020 PARTIALLY APPROVED JGIBSON
Note: THIS APPROVAL IS BASED ''ONLY WHEN SIGHED AND SEALED PLUMBING RISER DIAGRAM HAS BEEN SUBMITTED AND APPROVED BY PLANS EXAMINER '' NO CONCRETE TO BE POURED UNTIL THIS STEP HAS BEEN DONE.
ABOVE CEILING 01/10/2020 APPROVED - AS NOTED RMARTIN
Note: EMAILED FPL RELEASED POWER 11:30
PLUMBING 1ST ROUGH 12/23/2019 Disapproved -FEE REQUIRED JGIBSON
Note: THIS IS A REINSPECTION NOT READY, P-312. 3 ALL SANITARY AND GREASE LINES ARE TO BE TESTED IN SECTION OR IN IT`S INTIRIETY NOT READY
PLUMBING 1ST ROUGH 12/20/2019 CANCELLED BY APPLICANT JGIBSON
FOOTER 12/13/2019 APPROVED JDELBONIS

Review History

Department Status Date In Date Out
ARCHR CANCEL 06/01/2020 06/01/2020
Note: Landscape bond w/ plans provided
MECH COMPLETE 04/27/2020 04/29/2020
Note: Released By: CPISCITELLI
BLD COMPLETE 04/13/2020 04/24/2020
Note: Released By: FREODICA
MECH HOLD 04/13/2020 04/17/2020
Note: Held By: CPISCITELLI 1. Upload a complete (emphasis on complete) copy of the ETL listing for the hood. 2. Revise and upload plan sheet M-5 to reflect the installation details used by the contractor. This so there is a record between design and installation and an agreement to the installation by the engineer of record (albeit after the fact). Be sure fastener types and cementitious wallboard type are described- Your description below did not include any information. 3. Please provide a digital signature on all mechanical plan sheets and engineering analysis that complies with Florida Administrative Code 61G15-23.004.
BLD COMPLETE 03/16/2020 03/16/2020
Note: Released By: FREODICA not applicable
ARCHR HOLD 03/16/2020 03/30/2020
Note: Held By: BDAWSON - Provide DBH and species of existing trees on site. - Provide mitigation calculations. - Provide tree density calculations. - Show, label and dimension landscape buffers on plans. 10' w. Buffer A North & West, 10' w. Buffer C on East and 25' w. Buffer G South. - Refer to LDC 11.03.05 for landscape buffer requirements. Call City Landscape Architect at 386-302-7057 if clarification is needed. - Provide medium screen shrub around dumpster. - Provide medium screen shrub around any other above ground utiliies/equipment. - If there are any parking lights on site show them on plan to ensure 15' separation between pole and any new shade trees on site. - Provide irrigation plans. Indicate water source for irrigation on plans. Please note that 50% of new landscape must be drought tolerant or native if re-use is not the source. - Show sight triangles on plan. Pull back any proposed landscape buffer plantings as needed to not create sight visibility issues. - Provide an 8' average minimum foundation planting bed along South side of building walkway w/ 2 layers of plantings and 1 understory tree per 50 lf of building. - Provide (3) sabal palms in each VUA landscape island to replace lost credits of trees being removed from these areas. - Specify type of mulch being used. - Provide tree and palm planting/staking details.
PLUM COMPLETE 03/16/2020 03/16/2020
Note: Released By: FREODICA
BLD COMPLETE 03/11/2020 03/12/2020
Note: Released By: FREODICA Not applicable
PLUM HOLD 03/09/2020 03/10/2020
Note: Held By: FREODICA Repeat comment: Revision: changed plumbing riser diagram (sanitary and grease lines) 1. Sanitary and grease layouts do not match with riser diagram. Coordinate the piping layout, pipe sizes, and identify the fixtures and specify if they are new or existing for clarity per FBC 6th ed. 107.2.1. FReodica-386-986-4734
PLFM CANCEL 03/09/2020 03/09/2020
Note: Floodplain review not required, structure is not in a flood zone.
ZON CANCEL 03/09/2020 03/09/2020
ARCHR COMPLETE 03/09/2020 03/11/2020
Note: Released By: BDAWSON
ELEC COMPLETE 02/28/2020 03/05/2020
Note: Released By: JMUNSON
PLUM HOLD 02/28/2020 03/02/2020
Note: Held By: FREODICA Revision: Gas riser and domastic water diagrams. Gas riser diagram does not include the (3) gas heaters at patio. Coordinate with gas layout for clarity per FBC 6th ed. sec. 107.2.1. FReodica - 386-986-4734.
PLUM HOLD 02/07/2020 03/02/2020
Note: Held By: FREODICA Revision: changed plumbing riser diagram (sanitary and grease lines) 1. Sanitary and grease layouts do not match with riser diagram. Coordinate the piping layout, pipe sizes, and identify the fixtures and specify if they are new or existing for clarity per FBC 6th ed. 107.2.1. FReodica-386-986-4734
BLD COMPLETE 01/22/2020 02/07/2020
Note: Released By: FREODICA Revision : Sheet A3.2 - changed parapet from slope to vertical
UD1 COMPLETE 11/19/2019 11/19/2019
Note: Released By: CJOHNSON
MECH COMPLETE 11/06/2019 11/13/2019
Note: Released By: CPISCITELLI
UD1 HOLD 11/06/2019 11/07/2019
Note: Held By: CJOHNSON Add note on P-1 and P-3 "Pump out and clean existing grease interceptors. Verify with Utility inspector that the grease interceptors are in good condition and plumbed properly."
BLD COMPLETE 10/09/2019 10/22/2019
Note: Released By: MGARRETT
ELEC COMPLETE 10/09/2019 10/21/2019
Note: Released By: JMUNSON
FI1 COMPLETE 10/09/2019 10/22/2019
Note: Released By: WMILLER
MECH HOLD 10/09/2019 10/17/2019
Note: Held By: CPISCITELLI Provide rooftop plan showing penetration details. Need hood duct detail through building including clearance from commbustibles. Could not find hinged detail on fan. Provide more detailed duct drawing showing all units with freshair ducts penetrations. Please describe method of access to roof top units
PLUM COMPLETE 10/09/2019 10/22/2019
Note: Released By: MGARRETT
UD1 HOLD 10/09/2019 10/14/2019
Note: Held By: CJOHNSON Add note on P-1 and P-3 Pump out and clean existing grease interceptors. Verify with Utility inspector that the grease interceptors are in good condition and plumbed properly.
ZON COMPLETE 10/09/2019 10/10/2019
Note: Released By: JGONZALEZ

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REVISION ¤40.00 06/01/2020
REINSPECTION FEE ¤40.00 03/16/2020
REVISION ¤40.00 03/16/2020
SITE PLAN 20 ¤20.00 11/22/2019
SURCHARGE FS 533.721 ¤5.30 11/22/2019
SURCHARGE - FS 468.631 ¤7.95 11/22/2019
ADMIN COMMERCIAL ¤60.00 11/22/2019
INSPECTION - COMMERCIAL ADD ¤1,050.00 11/22/2019
ELECTRIC FEE ¤150.00 11/22/2019
MECHANICAL FEE ¤150.00 11/22/2019
PLAN CHECK FEE ¤172.50 11/22/2019
PLUMBING FEE ¤150.00 11/22/2019
Fees Total Due: ¤0.00 Total Paid: ¤1,885.75