I want to search for...
Permit #2019100988
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7028-00810-0220 |
| Total Square Footage: 2489 sqft |
| Block: 00810 |
| Subdivision: 2199 - SECTION 28-WYNNFIELD |
| Job Phone: 386-755-5944 |
| Location Address: 2 POINT PLEASANT DR |
| Type: GEN - GENERATOR |
| Issue Date: 11/04/2019 |
| NOC: RECORDED |
| Applicant name: DONALD RAY HOLLINGSWORTH |
| Owner: MCGRIFF EDWARD C & DEBORAH L H&W |
|
Address 2 POINT PLEASANT DR PALM COAST, FL 32164 |
| Lot: 0220 |
| Contracted Stated Job Value: ¤11,779.54 |
| Job Description: Installation Stand by Generator |
| Type: CN |
Contractor
HOLLY ELECTRIC INC
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
PO BOX 2266 LAKE CITY , FL 32025 |
EC13005429 (Exp: 08/31/2026) | 386-755-5944 | 386-755-5443 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 12/10/2019 | FINAL APPROVED | RMARTIN |
Review History
| Department | Status | Date In | Date Out |
| ZON | COMPLETE | 11/01/2019 | 11/04/2019 |
| Note: Released By: AMOBLEY | |||
| ELEC | COMPLETE | 11/01/2019 | 11/01/2019 |
| Note: Released By: JMUNSON | |||
| ZON | HOLD | 10/31/2019 | 11/01/2019 |
| Note: Held By: TDOAK Provide accurate setback from proposed generator to rear property line. There is only 29' from the rear of the home to the rear property line so the setback cannot be 42'. | |||
| ELEC | HOLD | 10/31/2019 | 11/01/2019 |
| Note: Held By: JMUNSON Need lockable disconnect. NEC 2014 art 445.18 | |||
| ELEC | HOLD | 10/24/2019 | 10/25/2019 |
| Note: Held By: JMUNSON Need a Riser Diagram. Need to show Transfer switch. Need to show Disconnect between the transfer switch and generator. NEC 2014 sec 445.18. Need to show what size generator is being installed. | |||
| PLUM | CANCEL | 10/24/2019 | 10/30/2019 |
| Note: Not Needed seperate permit for gas. | |||
| ZON | HOLD | 10/24/2019 | 10/25/2019 |
| Note: Held By: AMOBLEY Please provide a site plan/survey with setbacks from generator to property line |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADMIN FEE | ¤20.00 | 11/04/2019 |
| ELECTRIC FEE | ¤67.07 | 11/04/2019 |
| PLAN REVIEW 25 | ¤25.00 | 11/04/2019 |
| SITE PLAN 20 | ¤20.00 | 11/04/2019 |
| SURCHARGE FS 533.721 | ¤2.00 | 11/04/2019 |
| SURCHARGE - FS 468.631 | ¤2.00 | 11/04/2019 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤136.07 |