I want to search for...
Permit #2019120806
Permit Details
Status: FINAL
| Parcel Id: 39-12-31-3380-00000-0110 |
| Block: 00000 |
| Subdivision: 2141 - KINGS POINTE COMMERCIAL SUBDIVISION |
| Job Phone: 386-760-7660 |
| Location Address: 6130 STATE RD 100 |
| Type: FSS - FIRE SUPRESSION SYSTEM |
| Issue Date: 01/03/2020 |
| NOC: Unknown |
| Applicant name: GEORGE A BOULWARE JR |
| Owner: QSR ENTERPRISES LLC |
|
Address PO BOX 59924 DALLAS, TX 75229 |
| Lot: 0110 |
| Contracted Stated Job Value: ¤1,250.00 |
| Job Description: KITCHEN SUPPRESSION SYSTEM |
| Type: CN |
Contractor
PYE-BARKER FIRE & SAFETY, LLC
| Status | Location Address | State License Number | Phone |
| INACTIVE |
4189 DAIRY CT, STE F PORT ORANGE, FL 32127 |
FED17-000005 (Exp: 12/31/2025) | 386-760-7660 |
Inspection History
| Type | Request Date | Result | Inspector |
| FINAL HOOD & EXTINGUSHING SYSTEM FUNCTIONAL TEST | 01/06/2020 | FINAL APPROVED | WMILLER |
| Note: THIS IS A REINSPECTION | |||
| FINAL HOOD & EXTINGUSHING SYSTEM FUNCTIONAL TEST | 01/03/2020 | Disapproved - NO FEE | WMILLER |
| Note: Gas shutt-off switch did not work |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 12/30/2019 | 01/02/2020 |
| Note: Released By: WMILLER | |||
| FI1 | HOLD | 12/23/2019 | 12/30/2019 |
| Note: Held By: WMILLER Please submit riser diagram for suppression system (need to see System Control Automation, Agent tanks, Remote Manual Pull station, Detection line, Detectors, Duct Protection nozzle, Plenum Protection nozzle, each Appliance Protection nozzle, etc. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADMIN FEE | ¤200.00 | 01/03/2020 |
| ADMIN COMMERCIAL | ¤60.00 | 01/03/2020 |
| FIRE PLANS REVIEW | ¤40.00 | 01/03/2020 |
| SURCHARGE FS 533.721 | ¤2.00 | 01/03/2020 |
| SURCHARGE - FS 468.631 | ¤2.00 | 01/03/2020 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤304.00 |