Permit #2019120896
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7015-00020-0950 |
| Block: 00020 |
| Subdivision: 2194 - SECTION 15-COUNTRY CLUB COVE |
| Job Phone: 904-282-5050 |
| Location Address: 64 COCHISE CT |
| Type: ME - MECHANICAL |
| Issue Date: 12/30/2019 |
| NOC: Unknown |
| Applicant name: MICHAEL R NIQUETTE |
| Owner: BORNREADY HOLDINGS PTY LTD TRUSTEE |
|
Address OCEAN SHORES NSW 2483, 0 |
|
Address 15 MULI MULI AVE NSW 2483, 0 |
| Lot: 0950 |
| Contracted Stated Job Value: ¤1,500.00 |
| Job Description: 2 TON, 14 SEER HEATPUMP SPLIT EQUAL |
| Type: CN |
Contractor
TOTAL AIR CARE INC
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
PO BOX 2004 ORANGE PARK, FL 32065 |
CAC1815232 (Exp: 08/31/2022) | 904-282-5050 | 904-291-5956 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 03/26/2020 | FINAL APPROVED | CPISCITELLI |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION MOCP RATING NOT MATCHING BREAKERS MFBC 1303. (Breaker for AHU in panel was changed but the breaker in attic was not changed to a 45AMP. Need to change breaker in attic to 45 AMP) Above was corrected on this permit | |||
| HVAC FINAL | 03/11/2020 | Disapproved -FEE REQUIRED | CPISCITELLI |
| Note: THIS IS A REINSPECTION MOCP RATING NOT MATCHING BREAKERS MFBC 1303. (Breaker for AHU in panel was changed but the breaker in attic was not changed to a 45AMP. Need to change breaker in attic to 45 AMP) | |||
| HVAC FINAL | 03/04/2020 | Disapproved -FEE REQUIRED | CPISCITELLI |
| Note: THIS IS A REINSPECTION. Breaker for AHU is still incorrect. The Minimum circuit amps @240V is 44AMP. The Max fuse is 45AMP. There is a 40AMP in panel. The breaker needs to be a 45AMP | |||
| HVAC FINAL | 02/24/2020 | Disapproved -FEE REQUIRED | CPISCITELLI |
| Note: THIS IS A REINSPECTION. MOCP RATING NOT MATCHING BREAKERS MFBC 1303. ( Breakers are still incorrect. Changed the wrong breakers. changed the breakers for the main house unit not porch unit. Need 45 AMP for AHU and 25 AMP max for ODU) | |||
| HVAC FINAL | 01/10/2020 | Disapproved -FEE REQUIRED | CPISCITELLI |
| Note: 1. DOCUMENTS MUST BE APPROVED AND KEPT ON SITE 107.3,1. AND SHALL BE OPEN TO INSPECTION BY THE BUILDING OFFICIAL (need the APPROVED AHRI on site at time of final) 2. MOCP RATING NOT MATCHING BREAKERS MFBC 1303( ODU calls for Max of 25 AMP. AHU calls for 45AMP @220v. The breakers need to be changed) 3. 3 inches ABOVE THE GROUND FBC, R, M1305.1.4.1 3inches ABOVE THE ADJOINING GROUND. (ODU is level with grade. Need to install a hurricane pad under unit) 4. PAN SIZE M1411.3.1 (1) AUXILIARY AND SECONDARY DRAIN SYSTEMS MUST NOT BE LESS THAN 3” LONGER AND WIDER.( Drain pan in attic it too small and unit is not inside pan. Need to install larger drain pan and center AHU in pan.) |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 12/30/2019 | 12/30/2019 |
| Note: Released By: CPISCITELLI |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 03/11/2020 |
| REINSPECTION FEE | ¤40.00 | 03/04/2020 |
| REINSPECTION FEE | ¤40.00 | 02/24/2020 |
| REINSPECTION FEE | ¤40.00 | 02/20/2020 |
| ADMIN FEE | ¤20.00 | 12/30/2019 |
| INSPECTION 40 | ¤40.00 | 12/30/2019 |
| SURCHARGE FS 533.721 | ¤2.00 | 12/30/2019 |
| SURCHARGE - FS 468.631 | ¤2.00 | 12/30/2019 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤224.00 |