I want to search for...
Permit #2020010236
Permit Details
Status: FINAL
| Parcel Id: 09-12-31-2477-00000-0040 |
| Block: 00000 |
| Subdivision: 2247 - FLAGLER REGIONAL BUSINESS PARK |
| Job Phone: (386)672-8688 |
| Location Address: 250 OLD KINGS RD S |
| Type: CM - COMMERCIAL MECHANICAL |
| Issue Date: 01/09/2020 |
| NOC: Unknown |
| Applicant name: SHAWN MICHAEL HISS |
| Owner: SIZEMORE, DUANE S |
|
Address TRUSTEE BUNNELL, FL 32110 |
|
Address 920 GALLBERRY CT BUNNELL, FL 32110 |
| Lot: 0040 |
| Contracted Stated Job Value: ¤4,000.00 |
| Job Description: change out 3 ton 14 seer system |
| Type: CN |
Contractor
CLIMATE CONTROL HEATING & AIR CONDITIONING INC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
1315 LPGA BLVD HOLLY HILL, FL 32117 |
CAC1813585 (Exp: 08/31/2026) | (386)672-8688 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 02/04/2020 | FINAL APPROVED | CPISCITELLI |
| Note: THIS IS A REINSPECTION | |||
| LDSC- LANDSCAPE FINAL | 01/28/2020 | CANCELLED BY INSPECTOR | BDAWSON |
| Note: Landscape inspection not required per CDO and DCDO. | |||
| HVAC FINAL | 01/28/2020 | Disapproved -FEE REQUIRED | CPISCITELLI |
| Note: MOCP RATING NOT MATCHING BREAKERS MFBC 1303. (AHU calls for 50AMP @208V. There is a 60AMP in the panel) |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 01/09/2020 | 01/09/2020 |
| Note: Released By: CPISCITELLI | |||
| ZON | COMPLETE | 01/09/2020 | 01/09/2020 |
| Note: Released By: JGONZALEZ |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 01/29/2020 |
| SURCHARGE FS 533.721 | ¤2.00 | 01/09/2020 |
| SURCHARGE - FS 468.631 | ¤2.00 | 01/09/2020 |
| ADMIN COMMERCIAL | ¤60.00 | 01/09/2020 |
| MECHANICAL FEE | ¤62.40 | 01/09/2020 |
| PLAN CHECK FEE | ¤100.00 | 01/09/2020 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤266.40 |