I want to search for...
Permit #2020010344
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7003-00090-0190 |
| Block: 00090 |
| Subdivision: 2190 - SECTION 3-COUNTRY CLUB COVE |
| Job Phone: 321-332-0001 |
| Location Address: 19 CLARIDGE CT S |
| Type: ME - MECHANICAL |
| Issue Date: 01/14/2020 |
| NOC: RECORDED |
| Applicant name: CAREY L ZARM |
| Owner: FITZGERALD JOSEPHINE M LIFE ESTATE |
|
Address PO BOX 351231 PALM COAST, FL 32135 |
| Lot: 0190 |
| Contracted Stated Job Value: ¤11,500.00 |
| Job Description: HVAC Changeout- 3.5 ton/ 15 seer/ hp |
| Type: CN |
Contractor
SERVICE EXPERTS HEATING & AIR CONDITIONING
| Status | Location Address | Mailing Address | State License Number | Phone | Fax |
| CANCEL |
1725 S. NOVA ROAD DAYTONA BEACH, FL 32119 |
UNIT D-5 DAYTONA BEACH, FL 32119 |
CAC1817129 (Exp: 08/31/2020) | 321-332-0001 | 321-281-4733 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 02/27/2020 | FINAL APPROVED | CPISCITELLI |
| Note: THIS IS A REINSPECTION | |||
| HVAC FINAL | 01/23/2020 | Disapproved -FEE REQUIRED | CPISCITELLI |
| Note: 1. UNIT LABELING..FBC.R. M1303.1 MUST IDENTIFY MAXIMUM OVER CURRENT BREAKER SIZE ON AIR HANDLER UNIT WITH FACTORY APPLIED LABEL. (Heater not marked could not verify breaker size on AHU) 2. PROTECTION OF PIPING INSULATION FBC ENERGY CONSERVATION R403.4.1 (Armaflex missing on suction line in garage near unit) |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 01/13/2020 | 01/13/2020 |
| Note: Released By: CPISCITELLI |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 02/25/2020 |
| SURCHARGE FS 533.721 | ¤2.00 | 01/14/2020 |
| SURCHARGE - FS 468.631 | ¤2.00 | 01/14/2020 |
| ADMIN FEE | ¤20.00 | 01/14/2020 |
| INSPECTION 40 | ¤40.00 | 01/14/2020 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤104.00 |