Permit #2020040300
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7028-00270-0100 |
| Total Square Footage: 2209 sqft |
| Block: -7 |
| Subdivision: - |
| Job Phone: 386-574-2909 |
| Location Address: 33 POWDER HORN DR |
| Type: GEN - GENERATOR |
| Issue Date: 04/20/2020 |
| NOC: Unknown |
| Applicant name: BRIAN THOMAS HANEY |
| Owner: MULROY MARTIN J & |
|
Address 33 POWDER HORN DRIVE PALM COAST, FL 32164 |
| Lot: 02 |
| Contracted Stated Job Value: ¤2,000.00 |
| Job Description: GENERATOR |
| Type: CN |
Contractor
DELTRON ELECTRIC FL
| Status | Location Address | Mailing Address | State License Number | Phone |
| CANCEL |
1308 E NORMANDY BLVD DELTONA, FL 32725 |
STE E DELTONA, FL 32725 |
EC13009060 (Exp: 08/31/2022) | 386-574-2909 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 09/30/2020 | CANCELLED BY APPLICANT | WEB |
| ELECTRIC FINAL | 09/24/2020 | FINAL APPROVED | RMARTIN |
| ELECTRIC FINAL | 05/11/2020 | CANCELLED BY APPLICANT | WEB |
| Note: THIS IS A REINSPECTION GAS PERMIT NEEDS TO BE PULLED, NEW TANK INSTALLED, REGULATOR, GAS PIPING AND VENTING WERE DONE......ALSO ELECTRICIAN NEEDS TO MEET ON SITE TO OPEN UP LIVE PANELS AND TO DO START UP UNDER LOAD | |||
| ELECTRIC FINAL | 04/21/2020 | Disapproved - NO FEE | RMARTIN |
| Note: GAS PERMIT NEEDS TO BE PULLED, NEW TANK INSTALLED, REGULATOR, GAS PIPING AND VENTING WERE DONE......ALSO ELECTRICIAN NEEDS TO MEET ON SITE TO OPEN UP LIVE PANELS AND TO DO START UP UNDER LOAD |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 04/20/2020 | 04/20/2020 |
| Note: Released By: JMUNSON | |||
| ELEC | HOLD | 04/16/2020 | 04/16/2020 |
| Note: Held By: JMUNSON Button on the back of the generator is not lockable in the open position. NEC 2014 art 445.18 | |||
| ELEC | HOLD | 04/10/2020 | 04/14/2020 |
| Note: Held By: JMUNSON Need to show the disconnect between the ATS and the generator. NEC 2014 art 445.18 | |||
| ELEC | HOLD | 04/08/2020 | 04/09/2020 |
| Note: Held By: JMUNSON 1. Specify what size generator is being installed 2. Submit riser diagram showing wire size, transfer switch and disconnect between the transfer switch and the generator. | |||
| ZON | COMPLETE | 04/08/2020 | 04/09/2020 |
| Note: Released By: AMOBLEY |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADMIN FEE | ¤20.00 | 04/20/2020 |
| ELECTRIC FEE | ¤61.20 | 04/20/2020 |
| PLAN REVIEW 25 | ¤25.00 | 04/20/2020 |
| SITE PLAN 20 | ¤20.00 | 04/20/2020 |
| SURCHARGE FS 533.721 | ¤2.00 | 04/20/2020 |
| SURCHARGE - FS 468.631 | ¤2.00 | 04/20/2020 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤130.20 |