Permit #2020050202
Permit Details
Status: FINAL
| Parcel Id: 08-12-31-5830-00000-0000 |
| Block: 00000 |
| Subdivision: 2096 - TUSCAN RESERVE |
| Job Phone: (904)529-5257 |
| Location Address: 700 TUSCAN RESERVE DR |
| Type: FS - FIRE SPRINKLER WET COMMERCIAL |
| Issue Date: 06/16/2020 |
| NOC: RECORDED |
| Applicant name: JOHN P SWANSON |
| Owner: SW TUSCAN RESERVE, LP |
|
Address 360 CENTRAL AVE, SUITE 1130 SAINT PETERSBURG, FL 33701 |
| Lot: 0000 |
| Contracted Stated Job Value: ¤21,000.00 |
| Job Description: #700 - FIRE SPRINKLER |
| Type: CN |
Contractor
SWANSON FIRE PROTECTION LLC
| Status | Location Address | Mailing Address | State License Number | Phone | Fax |
| ACTIVE |
2220 COUNTY ROAD 210 W. JACKSONVILLE, FL 32259 |
SUITE 108-139 JACKSONVILLE, FL 32259 |
1944800012003 (Exp: 06/30/2026) | (904)529-5257 | (904)529-5258 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE FINAL | 11/10/2020 | FINAL APPROVED | JBODEN |
| FIRE SPRINKLER 1ST ROUGH | 07/22/2020 | APPROVED - AS NOTED | WMILLER |
| Note: THIS IS A REINSPECTION missing heads in great room areas on second and third floors per plans 07-22-2020.... Missing heads placed, approved | |||
| FIRE SPRINKLER 2ND RGH HYDROSTATIC PRESS TEST | 07/22/2020 | CANCELLED BY INSPECTOR | WMILLER |
| FIRE SPRINKLER HYDROSTATIC TEST | 07/22/2020 | APPROVED | WMILLER |
| Note: THIS IS A REINSPECTION will need to recall after missing heads are placed 07-22-2020.... approved | |||
| FIRE SPRINKLER 1ST ROUGH | 07/17/2020 | PARTIALLY APPROVED | WMILLER |
| Note: missing heads in great room areas on second and third floors per plans (each side of west stairs) missing fire blocking material at through penetrations | |||
| FIRE SPRINKLER HYDROSTATIC TEST | 07/17/2020 | Disapproved - NO FEE | WMILLER |
| Note: will need to recall after missing heads are placed |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 06/02/2020 | 06/15/2020 |
| Note: Released By: WMILLER | |||
| FI1 | HOLD | 05/05/2020 | 05/19/2020 |
| Note: Held By: WMILLER 1. Freeze Protection Required per NFPA 13R, section 6.2 (please show method of freeze protection for stairways) 2. Note on sheet FP-2 indicates no sprinklers on second floor stair (please show method of stairway protection for second floor) per FBC 2017 [F] 903.1.2.2 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADMIN COMMERCIAL | ¤60.00 | 06/16/2020 |
| FIRE PLANS REVIEW | ¤40.00 | 06/16/2020 |
| SURCHARGE FS 533.721 | ¤2.00 | 06/16/2020 |
| SURCHARGE - FS 468.631 | ¤2.00 | 06/16/2020 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤104.00 |