Permit #2020060367
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7004-00010-0020 |
| Total Square Footage: 2094 sqft |
| Block: 00010 |
| Subdivision: 2203 - SECTION 4-COUNTRY CLUB COVE |
| Job Phone: 386-574-2909 |
| Location Address: 4 CHERRY CT |
| Type: GEN - GENERATOR |
| Issue Date: 06/23/2020 |
| NOC: Unknown |
| Applicant name: BRIAN THOMAS HANEY |
| Owner: KAMBAR, ROBERT & MARY JEAN |
|
Address LIFE ESTATE PALM COAST, FL 32137 |
|
Address 4 CHERRY COURT PALM COAST, FL 32137 |
| Lot: 0020 |
| Contracted Stated Job Value: ¤2,400.00 |
| Job Description: GENERAC Generator Installation |
| Type: CN |
Contractor
DELTRON ELECTRIC FL
| Status | Location Address | Mailing Address | State License Number | Phone |
| CANCEL |
1308 E NORMANDY BLVD DELTONA, FL 32725 |
STE E DELTONA, FL 32725 |
EC13009060 (Exp: 08/31/2022) | 386-574-2909 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC UNDERGROUND | 08/04/2020 | CANCELLED BY APPLICANT | WEB |
| ELECTRIC FINAL | 08/04/2020 | FINAL APPROVED | RMARTIN |
| Note: THIS IS A REINSPECTION Contractor needs to meet on site to open up panels and do a start up on the generator. | |||
| ELECTRIC FINAL | 07/31/2020 | Disapproved - NO FEE | JMUNSON |
| Note: Contractor needs to meet on site to open up panels and do a start up on the generator. |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 06/23/2020 | 06/23/2020 |
| Note: Released By: JMUNSON | |||
| ELEC | HOLD | 06/19/2020 | 06/22/2020 |
| Note: Held By: JMUNSON Disconnect has to be able to be locked in the open position breaker inside the cover is not. NEC 2014 445.18 | |||
| ZON | COMPLETE | 06/19/2020 | 06/22/2020 |
| Note: Released By: ELENS | |||
| BADMIN | COMPLETE | 06/17/2020 | 06/19/2020 |
| Note: Released By: BBEMBRY YOUR ARE ONLY SUBMITTING THE ZONING HOLD YOU NEED TO SUBMIT THE ELECTRICAL HOLD ALSO | |||
| ELEC | HOLD | 06/17/2020 | 06/17/2020 |
| Note: Held By: JMUNSON Disconnect has to be able to be locked in the open position breaker inside the cover is not. NEC 2014 445.18 | |||
| ZON | HOLD | 06/17/2020 | 06/17/2020 |
| Note: Held By: ELENS Repeat comment: Revise site plan to show generator encroaching only 2ft into easement and applicant must complete a easement encroach ment form. Otherwise relocate generator to rear of property. The revised site plan still shows the generator within the 5 foot easement. It cannot be located in the easement. (Or, if approved, it may encroach two feet into the easement with an Encroachment Agreement.) | |||
| ZON | HOLD | 06/12/2020 | 06/12/2020 |
| Note: Held By: JGONZALEZ Revise site plan to show generator encroaching only 2ft into easement and applicant must complete a easement encroach ment form. Otherwise relocate generator to rear of property. | |||
| ELEC | HOLD | 06/12/2020 | 06/12/2020 |
| Note: Held By: JMUNSON Push button on the back of the generator is not lockable. NEC 2014 art 445.18 | |||
| BADMIN | COMPLETE | 06/10/2020 | 06/10/2020 |
| Note: Released By: JMONTARULI Need to answer all holds | |||
| ELEC | HOLD | 06/08/2020 | 06/09/2020 |
| Note: Held By: JMUNSON Submit riser diagram showing wire size and lockable disconnect. | |||
| ZON | HOLD | 06/08/2020 | 06/09/2020 |
| Note: Held By: ELENS Generator cannot be in the 5 foot easement. Please provide the setback from the property line to the generator. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADMIN FEE | ¤20.00 | 06/23/2020 |
| ELECTRIC FEE | ¤61.44 | 06/23/2020 |
| PLAN REVIEW 25 | ¤25.00 | 06/23/2020 |
| SITE PLAN 20 | ¤20.00 | 06/23/2020 |
| SURCHARGE FS 533.721 | ¤2.03 | 06/23/2020 |
| SURCHARGE - FS 468.631 | ¤3.04 | 06/23/2020 |
| WORK WITHOUT PERMIT | ¤101.44 | 06/23/2020 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤232.95 |