Permit #2020060367

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7004-00010-0020
Total Square Footage: 2094 sqft
Block: 00010
Subdivision: 2203 - SECTION 4-COUNTRY CLUB COVE
Job Phone: 386-574-2909
Location Address: 4 CHERRY CT
Type: GEN - GENERATOR
Issue Date: 06/23/2020
NOC: Unknown
Applicant name: BRIAN THOMAS HANEY
Owner: KAMBAR, ROBERT & MARY JEAN

Address

LIFE ESTATE

PALM COAST, FL 32137

Address

4 CHERRY COURT

PALM COAST, FL 32137

Lot: 0020
Contracted Stated Job Value: ¤2,400.00
Job Description: GENERAC Generator Installation
Type: CN

Contractor

DELTRON ELECTRIC FL
Status Location Address Mailing Address State License Number Phone
CANCEL

1308 E NORMANDY BLVD

DELTONA, FL 32725

STE E

DELTONA, FL 32725

EC13009060 (Exp: 08/31/2022) 386-574-2909

Inspection History

Type Request Date Result Inspector
ELECTRIC UNDERGROUND 08/04/2020 CANCELLED BY APPLICANT WEB
ELECTRIC FINAL 08/04/2020 FINAL APPROVED RMARTIN
Note: THIS IS A REINSPECTION Contractor needs to meet on site to open up panels and do a start up on the generator.
ELECTRIC FINAL 07/31/2020 Disapproved - NO FEE JMUNSON
Note: Contractor needs to meet on site to open up panels and do a start up on the generator.

Review History

Department Status Date In Date Out
ELEC COMPLETE 06/23/2020 06/23/2020
Note: Released By: JMUNSON
ELEC HOLD 06/19/2020 06/22/2020
Note: Held By: JMUNSON Disconnect has to be able to be locked in the open position breaker inside the cover is not. NEC 2014 445.18
ZON COMPLETE 06/19/2020 06/22/2020
Note: Released By: ELENS
BADMIN COMPLETE 06/17/2020 06/19/2020
Note: Released By: BBEMBRY YOUR ARE ONLY SUBMITTING THE ZONING HOLD YOU NEED TO SUBMIT THE ELECTRICAL HOLD ALSO
ELEC HOLD 06/17/2020 06/17/2020
Note: Held By: JMUNSON Disconnect has to be able to be locked in the open position breaker inside the cover is not. NEC 2014 445.18
ZON HOLD 06/17/2020 06/17/2020
Note: Held By: ELENS Repeat comment: Revise site plan to show generator encroaching only 2ft into easement and applicant must complete a easement encroach ment form. Otherwise relocate generator to rear of property. The revised site plan still shows the generator within the 5 foot easement. It cannot be located in the easement. (Or, if approved, it may encroach two feet into the easement with an Encroachment Agreement.)
ZON HOLD 06/12/2020 06/12/2020
Note: Held By: JGONZALEZ Revise site plan to show generator encroaching only 2ft into easement and applicant must complete a easement encroach ment form. Otherwise relocate generator to rear of property.
ELEC HOLD 06/12/2020 06/12/2020
Note: Held By: JMUNSON Push button on the back of the generator is not lockable. NEC 2014 art 445.18
BADMIN COMPLETE 06/10/2020 06/10/2020
Note: Released By: JMONTARULI Need to answer all holds
ELEC HOLD 06/08/2020 06/09/2020
Note: Held By: JMUNSON Submit riser diagram showing wire size and lockable disconnect.
ZON HOLD 06/08/2020 06/09/2020
Note: Held By: ELENS Generator cannot be in the 5 foot easement. Please provide the setback from the property line to the generator.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADMIN FEE ¤20.00 06/23/2020
ELECTRIC FEE ¤61.44 06/23/2020
PLAN REVIEW 25 ¤25.00 06/23/2020
SITE PLAN 20 ¤20.00 06/23/2020
SURCHARGE FS 533.721 ¤2.03 06/23/2020
SURCHARGE - FS 468.631 ¤3.04 06/23/2020
WORK WITHOUT PERMIT ¤101.44 06/23/2020
Fees Total Due: ¤0.00 Total Paid: ¤232.95