Permit #2020071420
Permit Details
Status: FINAL
| Parcel Id: 44-11-31-4985-00000-0150 |
| Total Square Footage: 4962 sqft |
| Block: 00000 |
| Subdivision: 1160 - OAKS NORTH SUBDIVISION |
| Job Phone: 386-574-2909 |
| Location Address: 9 SENTRY OAK PL |
| Type: GEN - GENERATOR |
| Issue Date: 08/07/2020 |
| NOC: Unknown |
| Applicant name: BRIAN THOMAS HANEY |
| Owner: VITALE LOUIS STEVEN JR & DEBRA DIANE H&W |
|
Address 9 SENTRY OAK PALM COAST, FL 32137 |
| Lot: 0150 |
| Contracted Stated Job Value: ¤2,250.00 |
| Job Description: Installation of 200 AMP ATS for Generac generator |
| Type: CN |
Contractor
DELTRON ELECTRIC FL
| Status | Location Address | Mailing Address | State License Number | Phone |
| CANCEL |
1308 E NORMANDY BLVD DELTONA, FL 32725 |
STE E DELTONA, FL 32725 |
EC13009060 (Exp: 08/31/2022) | 386-574-2909 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC UNDERGROUND | 09/24/2020 | CANCELLED BY APPLICANT | WEB |
| ELECTRIC UNDERGROUND | 09/24/2020 | APPROVED | JMUNSON |
| ELECTRIC FINAL | 09/24/2020 | FINAL APPROVED | JMUNSON |
| Note: THIS IS A REINSPECTION Homeowner has permit docs and will be on site for inspection. Thank you! 9/10/20 HOME OWNER TRIED TO START GENERATOR, WOULD NOT START, NEED TO HAVE CONTRACTOR ON SITE FOR INSPECTION | |||
| ELECTRIC FINAL | 09/10/2020 | CANCELLED BY APPLICANT | WEB |
| Note: Home owner, Donald Copeland, has permit job docs and will be on site. | |||
| ELECTRIC FINAL | 09/10/2020 | Disapproved - NO FEE | RMARTIN |
| Note: Homeowner has permit docs and will be on site for inspection. Thank you! 9/10/20 HOME OWNER TRIED TO START GENERATOR, WOULD NOT START, NEED TO HAVE CONTRACTOR ON SITE FOR INSPECTION |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 08/12/2020 | 08/12/2020 |
| Note: Released By: JMUNSON | |||
| ELEC | HOLD | 08/06/2020 | 08/06/2020 |
| Note: Held By: JMUNSON 1. The wire size for the generator is not rated for 200 amps. NEC 2014 art 310.15(B) (16) | |||
| ELEC | COMPLETE | 08/06/2020 | 08/06/2020 |
| Note: Released By: JMUNSON | |||
| ELEC | HOLD | 08/03/2020 | 08/05/2020 |
| Note: Held By: JMUNSON 1. On riser diagram it says 25 KW the specs that were uploaded were for 16-22 Kw. Need to upload specs for the 25 kw. 2. The wire size for the generator is not rated for 200 amps which is the size breaker in the 25 kw generator. wire needs to be rated for the breaker. NEC 2014 art 310.15 (B) (16) | |||
| ZON | COMPLETE | 08/03/2020 | 08/04/2020 |
| Note: Released By: AMOBLEY | |||
| ELEC | HOLD | 07/30/2020 | 07/30/2020 |
| Note: Held By: JMUNSON 1.#3 wire is not rated for the 200 amp breaker that is installed in the 25 KW generator. 2. Submit manufactured specs. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADMIN FEE | ¤20.00 | 08/07/2020 |
| BUILDING DISCOUNT 100% | (¤106.35) | 08/07/2020 |
| ELECTRIC FEE | ¤61.35 | 08/07/2020 |
| PLAN REVIEW 25 | ¤25.00 | 08/07/2020 |
| SITE PLAN 20 | ¤20.00 | 08/07/2020 |
| SURCHARGE FS 533.721 | ¤2.00 | 08/07/2020 |
| SURCHARGE - FS 468.631 | ¤2.00 | 08/07/2020 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤24.00 |