I want to search for...
Permit #2020080817
Permit Details
Status: CANCEL
| Parcel Id: 15-11-31-2830-00000-0690 |
| Block: 00000 |
| Subdivision: 1071 - FRONT STREET @ GRAND HAVEN PHASE 1 |
| Job Phone: (386) 437-8496 |
| Location Address: 49 LAGARE ST |
| Type: EL - ELECTRICAL |
| NOC: Unknown |
| Applicant name: MARK E SMITH |
| Owner: SEIDEL THOMAS E |
|
Address 49 LAGARE STREET PALM COAST, FL 32137 |
| Lot: 0690 |
| Contracted Stated Job Value: ¤680.00 |
| Job Description: 50 CIRCUIT FOR GENERATOR OUTLET & INTERLOCK KIT |
| Type: CN |
Contractor
ELECTRICAL WIRING SOLUTIONS INC.
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
P. O. Box 351482 PALM COAST, FL 32164 |
EC0002128 (Exp: 08/31/2026) | (386) 437-8496 | 386-586-3612 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL |
Review History
| Department | Status | Date In | Date Out |
| ELEC | HOLD | 08/18/2020 | 08/18/2020 |
| Note: Held By: JMUNSON 8/3 Romex is not rated for 50 amps. NEC 2014 art 310.15 (B) (16) & 334.80 | |||
| ELEC | CANCEL |