Permit #2020100088
Permit Details
Status: FINAL
| Parcel Id: 16-11-30-4939-00000-0030 |
| Block: 00000 |
| Subdivision: 2263 - PALM COAST INDUSTRIAL PARK PHASE III |
| Job Phone: 386-446-6426 |
| Location Address: 25 RAILSIDE WAY |
| Type: FU - FIRE UNDERGROUND |
| Issue Date: 10/15/2020 |
| NOC: RECORDED |
| Applicant name: SCOTT DALE SOWERS |
| Owner: V3 LLC |
|
Address 25 RAILSIDE WAY PALM COAST, FL 32137 |
| Lot: 0030 |
| Contracted Stated Job Value: ¤23,268.75 |
| Job Description: Underground Fire Line |
| Type: CN |
Contractor
S E CLINE CONSTRUCTION INC
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
PO BOX 354425 PALM COAST, FL 32137 |
FPC12-000038 (Exp: 06/30/2026) | 386-446-6426 | 386-446-6481 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE FINAL | 11/05/2021 | FINAL APPROVED | LMILLER |
| Note: THIS IS A REINSPECTION missing signage, no documents on site, hydrants need a minimum of 18 inches from center of caps to surrounding grade, OS&Y needs to to be chained and locked, other in progress inspections need to be approved prior to final 11-05-21... notes above resolved | |||
| FIRE SYSTEM FLUSH | 10/25/2021 | APPROVED | LMILLER |
| FIRE SYSTEM FLUSH | 10/14/2021 | Disapproved - NO FEE | LMILLER |
| Note: no one on site to flush system | |||
| HYDRANT FLOW TEST | 10/14/2021 | Disapproved - NO FEE | LMILLER |
| Note: no one on site to test hydrants | |||
| FIRE FINAL | 10/14/2021 | Disapproved -FEE REQUIRED | LMILLER |
| Note: missing signage, no documents on site, hydrants need a minimum of 18 inches from center of caps to surrounding grade, OS&Y needs to to be chained and locked, other in progress inspections need to be approved prior to final | |||
| FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR | 06/01/2021 | APPROVED | WMILLER |
| Note: THIS IS A REINSPECTION needs to be tested per NFPA 24,at 200 psi. for two hours (minimum pressure not met 06-01-21... notes above resolved | |||
| FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR | 05/27/2021 | Disapproved -FEE REQUIRED | WMILLER |
| Note: needs to be tested per NFPA 24,at 200 psi. for two hours (minimum pressure not met | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 05/25/2021 | APPROVED | JMUNSON |
| Note: THIS IS A REINSPECTION Marked on plan 5/25/21 Marked on plans. finished to the building and looked at line running north for future building stops at post. | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 04/29/2021 | PARTIALLY APPROVED | JMUNSON |
| Note: Marked on plan |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 10/09/2020 | 10/13/2020 |
| Note: Released By: WMILLER | |||
| FI1 | HOLD | 10/02/2020 | 10/07/2020 |
| Note: Held By: WMILLER Note on sheet C-7 states... 6" DDCV assembly with attached FDC (per city detail), City detail for FDC was not provided. Please provide City detail as indicated. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION - COMMERCIAL | ¤60.00 | 11/04/2021 |
| EXTENSION | ¤40.00 | 10/08/2021 |
| REINSPECTION FEE | ¤40.00 | 10/08/2021 |
| SURCHARGE FS 533.721 | ¤2.00 | 10/15/2020 |
| SURCHARGE - FS 468.631 | ¤2.00 | 10/15/2020 |
| ADMIN COMMERCIAL | ¤60.00 | 10/15/2020 |
| FIRE PLANS REVIEW | ¤40.00 | 10/15/2020 |
| BUILDING DISCOUNT 100% | (¤100.00) | 10/15/2020 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤144.00 |