I want to search for...

Permit #2020100088

Permit Details

Status: FINAL

Parcel Id: 16-11-30-4939-00000-0030
Block: 00000
Subdivision: 2263 - PALM COAST INDUSTRIAL PARK PHASE III
Job Phone: 386-446-6426
Location Address: 25 RAILSIDE WAY
Type: FU - FIRE UNDERGROUND
Issue Date: 10/15/2020
NOC: RECORDED
Applicant name: SCOTT DALE SOWERS
Owner: V3 LLC

Address

25 RAILSIDE WAY

PALM COAST, FL 32137

Lot: 0030
Contracted Stated Job Value: ¤23,268.75
Job Description: Underground Fire Line
Type: CN

Contractor

S E CLINE CONSTRUCTION INC
Status Location Address State License Number Phone Fax
ACTIVE

PO BOX 354425

PALM COAST, FL 32137

FPC12-000038 (Exp: 06/30/2026) 386-446-6426 386-446-6481

Inspection History

Type Request Date Result Inspector
FIRE FINAL 11/05/2021 FINAL APPROVED LMILLER
Note: THIS IS A REINSPECTION missing signage, no documents on site, hydrants need a minimum of 18 inches from center of caps to surrounding grade, OS&Y needs to to be chained and locked, other in progress inspections need to be approved prior to final 11-05-21... notes above resolved
FIRE SYSTEM FLUSH 10/25/2021 APPROVED LMILLER
FIRE SYSTEM FLUSH 10/14/2021 Disapproved - NO FEE LMILLER
Note: no one on site to flush system
HYDRANT FLOW TEST 10/14/2021 Disapproved - NO FEE LMILLER
Note: no one on site to test hydrants
FIRE FINAL 10/14/2021 Disapproved -FEE REQUIRED LMILLER
Note: missing signage, no documents on site, hydrants need a minimum of 18 inches from center of caps to surrounding grade, OS&Y needs to to be chained and locked, other in progress inspections need to be approved prior to final
FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR 06/01/2021 APPROVED WMILLER
Note: THIS IS A REINSPECTION needs to be tested per NFPA 24,at 200 psi. for two hours (minimum pressure not met 06-01-21... notes above resolved
FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR 05/27/2021 Disapproved -FEE REQUIRED WMILLER
Note: needs to be tested per NFPA 24,at 200 psi. for two hours (minimum pressure not met
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 05/25/2021 APPROVED JMUNSON
Note: THIS IS A REINSPECTION Marked on plan 5/25/21 Marked on plans. finished to the building and looked at line running north for future building stops at post.
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 04/29/2021 PARTIALLY APPROVED JMUNSON
Note: Marked on plan

Review History

Department Status Date In Date Out
FI1 COMPLETE 10/09/2020 10/13/2020
Note: Released By: WMILLER
FI1 HOLD 10/02/2020 10/07/2020
Note: Held By: WMILLER Note on sheet C-7 states... 6" DDCV assembly with attached FDC (per city detail), City detail for FDC was not provided. Please provide City detail as indicated.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION - COMMERCIAL ¤60.00 11/04/2021
EXTENSION ¤40.00 10/08/2021
REINSPECTION FEE ¤40.00 10/08/2021
SURCHARGE FS 533.721 ¤2.00 10/15/2020
SURCHARGE - FS 468.631 ¤2.00 10/15/2020
ADMIN COMMERCIAL ¤60.00 10/15/2020
FIRE PLANS REVIEW ¤40.00 10/15/2020
BUILDING DISCOUNT 100% (¤100.00) 10/15/2020
Fees Total Due: ¤0.00 Total Paid: ¤144.00