Permit #2020101345
Permit Details
Status: COED
| Parcel Id: 07-11-31-7034-00460-0020 |
| CONDITIONED SPACE: 2518 sqft |
| GARAGE: 730 sqft |
| OPENED PORCH (WITH ROOF) : 310 sqft |
| OPENED PORCH (WITH ROOF) : 57 sqft |
| Total Square Footage: 3615 sqft |
| Block: 00460 |
| Subdivision: 2165 - SECTION 34-EASTHAMPTON |
| Job Phone: 386-931-1725 |
| Location Address: 16 ESSEX LN |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 11/30/2020 |
| NOC: RECORDED |
| Applicant name: JOSEPH ALEIXO PORTAL |
| Owner: PORTAL FLEISBERTO A TRUSTEE |
|
Address 21 PRINCESS KIM LANE PALM COAST, FL 32164 |
| Lot: 0020 |
| Contracted Stated Job Value: ¤200,000.00 |
| Job Description: SINGLE FAMILY RESIDENCE |
| Type: CN |
Contractor
SWEETWATER CUSTOM HOMES INC.
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
1105 LAMBERT AVENUE FLAGLER BEACH, FL 32136 |
CBC1252965 (Exp: 08/31/2024) | 386-931-1725 | 386-439-4676 |
Sub Contractors
JONATHAN M PEARSON
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
209 N FORSYTH ST BUNNELL, FL 32110 |
CFC1425941 (Exp: 08/31/2026) | 386-597-0944 | 386-437-4996 |
JOHN ROBERT BLEVINS JR
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
17 PORWYN LANE PALM COAST, FL 32164 |
CAC1816125 (Exp: 08/31/2026) | 386-585-8283 | 386-263-2096 |
OLEG BELINSKIY
| Status | Location Address | State License Number | Phone |
| ACTIVE |
19 PINE CIRCLE DRIVE19 PALM COAST, FL 32167 |
CCC1325974 (Exp: 08/31/2026) | 386-263-7906 |
WILLIAM TODD SIKES
| Status | Location Address | State License Number | Phone |
| ACTIVE |
83 PORT ROYAL DR ST AUGUSTINE, FL 32084 |
EC0002726 (Exp: 08/31/2026) | 904-762-8762 |
Inspection History
| Type | Request Date | Result | Inspector |
| BLD - BUILDING FINAL | 04/05/2022 | FINAL APPROVED | RMARTIN |
| Note: THIS IS A REINSPECTION Missing termite certification. Energy calculations do not match AHU and A/C units installed. Please submit a revision to the building department for the installed units. Outlet next to 2nd window from the rear of the master bedroom has an open ground The smoke detector in the master bed needs 4" clearance from the soffit wall. The rear bathroom toilet does not have the required 15" minimum clearance from the vanity. | |||
| ROW - STORMWATER FINAL | 04/05/2022 | APPROVED - AS NOTED | PFLANAGAN |
| Note: 4/5/22 at time of inspection plants are gone out of 5 foot easement Can't have any PLANTS in the 5 foot easement around property line except fence | |||
| ROW- PROJECT STATUS | 04/04/2022 | APPROVED | GBERTOLA |
| Note: meeting with the builder | |||
| U-CROSS CONNECTION | 04/01/2022 | APPROVED - AS NOTED | JHARDING |
| Note: No cross connections. | |||
| BLD - BUILDING FINAL | 04/01/2022 | Disapproved - NO FEE | JWALKER |
| Note: Missing termite certification. Energy calculations do not match AHU and A/C units installed. Please submit a revision to the building department for the installed units. Outlet next to 2nd window from the rear of the master bedroom has an open ground The smoke detector in the master bed needs 4" clearance from the soffit wall. The rear bathroom toilet does not have the required 15" minimum clearance from the vanity. | |||
| U -UTILITY RESIDENTIAL FINAL | 04/01/2022 | FINAL APPROVED | JHARDING |
| ROW - FINAL APRON (AFTER POUR) | 04/01/2022 | APPROVED | PFLANAGAN |
| ROW - STORMWATER FINAL | 04/01/2022 | Disapproved -FEE REQUIRED | PFLANAGAN |
| Note: Can't have any PLANTS in the 5 foot easement around property line except fence | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 03/28/2022 | APPROVED | PFLANAGAN |
| FINAL SURVEY (OFFICE USE ONLY) | 03/28/2022 | APPROVED | PFLANAGAN |
| ELECTRIC - EARLY POWER | 03/04/2022 | APPROVED - AS NOTED | JMUNSON |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION 1. Called wrong inspection. Must set temp pole do not give temp power to over head services. 2. Riser to tall on service. NEC 2017 344.30 5/25/21 Called in wrong inspection 3/4/22 Emailed FPL at 8:23 am | |||
| ROW- PRE-APRON (PRE-POUR) | 02/11/2022 | APPROVED - AS NOTED | PFLANAGAN |
| Note: *There is a sidewalk going to garage but there is no sidewalk on site plan THE SIDEWALK NEEDS TO BE ON FINAL SURVEY TO PASS. *The sidewalk going to main entrence to home need to be revised do to it being formed to 4' *READY TO POUR at the time of Inspection. Note that heavy rain is in the forecast and builder should double check the elevations and that the pipe is level before pouring. If the pipe floats up at the band connection, it should be corrected before pouring. | |||
| MONOLITHIC SLAB | 12/16/2021 | APPROVED | JWALKER |
| GRAVITY SEWER TEST | 10/27/2021 | APPROVED - AS NOTED | MGIBSON |
| Note: THIS IS THE LAST TIME SCHEDUALING GRAVITY SEWER, BOTH GRAVITY SEWER ''AND'' U-SEWER BOTH NEED TO BE SCHEDULED BY CONTRACTOR!!!! | |||
| U - SEWER TIE IN | 10/27/2021 | APPROVED | MGIBSON |
| INSULATION | 09/14/2021 | APPROVED | TSTAUFFACHER |
| PEP TANK INSTALLATION REQUEST | 08/17/2021 | APPROVED | TCHURCHILL |
| INSULATION | 08/03/2021 | APPROVED | TSTAUFFACHER |
| LATH/BRICK/ WATER BARRIER | 07/20/2021 | APPROVED | TSTAUFFACHER |
| ALL ROUGH | 07/07/2021 | APPROVED | MMESSER |
| ROOF VALLEY & METAL | 06/15/2021 | APPROVED | MMESSER |
| Note: THIS IS A REINSPECTION Not Complete | |||
| ROOF VALLEY & METAL | 06/11/2021 | Disapproved -FEE REQUIRED | TSTAUFFACHER |
| Note: Not Complete | |||
| ELECTRIC TEMP POLE | 05/27/2021 | APPROVED - AS NOTED | RMARTIN |
| Note: THIS INSPECTION WAS DONE BY JOSH ON WRONG INSPECTION/ EMAILED FPL RELEASED POWER 9:00 | |||
| ELECTRIC - EARLY POWER | 05/25/2021 | Disapproved - NO FEE | JMUNSON |
| Note: THIS IS A REINSPECTION 1. Called wrong inspection. Must set temp pole do not give temp power to over head services. 2. Riser to tall on service. NEC 2017 344.30 5/25/21 Called in wrong inspection | |||
| ELECTRIC - EARLY POWER | 05/07/2021 | Disapproved - NO FEE | JMUNSON |
| Note: 1. Called wrong inspection. Must set temp pole do not give temp power to over head services. 2. Riser to tall on service. NEC 2017 344.30 | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 04/21/2021 | APPROVED | TSTAUFFACHER |
| TIE BEAM / LINTEL | 03/30/2021 | APPROVED | TSTAUFFACHER |
| Note: THIS IS A REINSPECTION Marked in green paint//multiple vertical bar do not meet coverage requirements R404.1.3.3.7.4Support and cover. Reinforcement shall be secured in the proper location in the forms with tie wire or other bar support system to prevent displacement during the concrete placement operation. Steel reinforcement in concrete cast against the earth shall have a minimum cover of 3 inches (75 mm). Minimum cover for reinforcement in concrete cast in removable forms that will be exposed to the earth or weather shall be 11/2 inches (38 mm) for No. 5 bars and smaller, and 2 inches (50 mm) for No. 6 bars and larger. For concrete cast in removable forms that will not be exposed to the earth or weather, and for concrete cast in stay-in-place forms, minimum cover shall be 3/4 inch (19 mm). The minus tolerance for cover shall not exceed the smaller of one-third the required cover or 3/8 inch (10 mm). | |||
| TIE BEAM / LINTEL | 03/29/2021 | Disapproved - NO FEE | TSTAUFFACHER |
| Note: Marked in green paint//multiple vertical bar do not meet coverage requirements R404.1.3.3.7.4Support and cover. Reinforcement shall be secured in the proper location in the forms with tie wire or other bar support system to prevent displacement during the concrete placement operation. Steel reinforcement in concrete cast against the earth shall have a minimum cover of 3 inches (75 mm). Minimum cover for reinforcement in concrete cast in removable forms that will be exposed to the earth or weather shall be 11/2 inches (38 mm) for No. 5 bars and smaller, and 2 inches (50 mm) for No. 6 bars and larger. For concrete cast in removable forms that will not be exposed to the earth or weather, and for concrete cast in stay-in-place forms, minimum cover shall be 3/4 inch (19 mm). The minus tolerance for cover shall not exceed the smaller of one-third the required cover or 3/8 inch (10 mm). | |||
| WATER METER INSTALLATION REQUEST | 03/26/2021 | APPROVED | CSTONE |
| FOUND SURVEY APPROVED (OFFICE) | 03/03/2021 | APPROVED | TDOAK |
| MONOLITHIC SLAB | 02/16/2021 | APPROVED | TSTAUFFACHER |
| PLUMBING 1ST ROUGH UNDERGROUND | 02/04/2021 | APPROVED | JGIBSON |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 04/04/2022 | 04/04/2022 |
| Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM | |||
| ENGIN1 | COMPLETE | 12/07/2021 | 12/08/2021 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| SW1 | COMPLETE | 12/07/2021 | 12/15/2021 |
| Note: Released By: CONRAD TROHA - (386)986-4767 - CTROHA@PALMCOASTGOV.COM revision for sidewalk | |||
| ZON | COMPLETE | 12/07/2021 | 12/07/2021 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 11/23/2021 | 11/24/2021 |
| Note: Released By: FRED REODICA - (386)986-4734 - FREODICA@PALMCOASTGOV.COM na | |||
| ELEC | COMPLETE | 11/23/2021 | 11/24/2021 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 09/07/2021 | 09/07/2021 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 08/27/2021 | 08/30/2021 |
| Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 08/27/2021 | 08/31/2021 |
| Note: Released By: HAROLD ALLEN - - HALLEN@PALMCOASTGOV.COM | |||
| ZON | HOLD | 08/27/2021 | 08/27/2021 |
| Note: Held By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM Please submit revised site plan to reflect the revised floor plan with the large concrete patio. | |||
| MECH | HOLD | 08/24/2021 | 08/24/2021 |
| Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM Energy Calcs say 12000 BTU minisplit. Plans say 18000 BTU. Revise to match or remove size from Floor Plan. (Second Request) | |||
| ELEC | COMPLETE | 08/24/2021 | 08/25/2021 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| MECH | HOLD | 08/23/2021 | 08/23/2021 |
| Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM Energy Calcs say 12000 BTU minisplit. Plans say 18000 BTU. Revise to match or remove size from plans | |||
| MECH | HOLD | 08/17/2021 | 08/17/2021 |
| Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM Provide energy calcs for garage minisplit. (Second Request) R503.2 FBC Energy Conservation 2020 7Th edition | |||
| BLD | COMPLETE | 08/17/2021 | 08/17/2021 |
| Note: Released By: FRED REODICA - (386)986-4734 - FREODICA@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 08/17/2021 | 08/17/2021 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| BLD | HOLD | 08/09/2021 | 08/10/2021 |
| Note: Held By: HAROLD ALLEN - - HALLEN@PALMCOASTGOV.COM REVIEW COMMENTS: Concrete slab is being installed. No detail provided for slab. Provide the strength of the concrete and will there be a footer? | |||
| ELEC | HOLD | 08/09/2021 | 08/10/2021 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM upload new electric plans | |||
| MECH | HOLD | 08/09/2021 | 08/10/2021 |
| Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM Provide energy calcs for garage minisplit. | |||
| BADMIN | HOLD | 08/03/2021 | 08/03/2021 |
| Note: Held By: SCOTT THOMAS - - STHOMAS@PALMCOASTGOV.COM PLANS ARE NOT FOR FBC 2017. PLEASE RESUBMIT | |||
| BADMIN | COMPLETE | 08/03/2021 | 08/03/2021 |
| Note: Released By: SCOTT THOMAS - - STHOMAS@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 03/03/2021 | 03/03/2021 |
| Note: Released By: TRACEY DOAK - (386)986-2473 - TDOAK@PALMCOASTGOV.COM | |||
| ENGIN1 | COMPLETE | 02/26/2021 | 03/01/2021 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@CI.PALM-COAST.FL.US | |||
| ZON | HOLD | 02/26/2021 | 02/26/2021 |
| Note: Held By: TRACEY DOAK - (386)986-2473 - TDOAK@PALMCOASTGOV.COM Please provide the front setback from the closest point (left side where lot is smaller). | |||
| ZON | COMPLETE | 11/17/2020 | 11/18/2020 |
| Note: Released By: ELENS | |||
| SW1 | COMPLETE | 11/17/2020 | 11/18/2020 |
| Note: Released By: CTROHA | |||
| ZON | HOLD | 11/09/2020 | 11/10/2020 |
| Note: Held By: ELENS I do not see a correction form, nor a revised landscape plan. Repeat comment: Four trees are required for this site. (Need one more.) Also, please clarify the left side setback on the site plan. It is covered. | |||
| MECH | COMPLETE | 11/09/2020 | 11/09/2020 |
| Note: Released By: CPISCITELLI | |||
| SW1 | HOLD | 11/09/2020 | 11/10/2020 |
| Note: Held By: KRUTH SITE PLAN HAS ELEVATIONS THAT ARE TO HIGH BASED ON CENTER OF THE ROAD ELEVATIONS | |||
| BLD | COMPLETE | 11/09/2020 | 11/16/2020 |
| Note: Released By: JPI | |||
| ENGIN1 | COMPLETE | 11/09/2020 | 11/10/2020 |
| Note: Released By: TBAKER | |||
| BLD | HOLD | 10/29/2020 | 11/04/2020 |
| Note: Held By: JPI 1. Roof underlayment – worksheet calls out synthetic, details call out 15# felt (unacceptable) , peel and stick and sheet 6/7 calls out 30# felt. Reconcile revise and cloud revisions 2. No lintels, soffit, or underlayment on product approval | |||
| CUSVC | COMPLETE | 10/29/2020 | 11/02/2020 |
| Note: Released By: HHAND | |||
| ELEC | COMPLETE | 10/29/2020 | 11/02/2020 |
| Note: Released By: JMUNSON | |||
| ENGIN1 | COMPLETE | 10/29/2020 | 10/29/2020 |
| Note: Released By: TBAKER | |||
| LOCATE | COMPLETE | 10/29/2020 | 11/02/2020 |
| Note: Released By: CSTONE | |||
| MECH | HOLD | 10/29/2020 | 11/02/2020 |
| Note: Held By: CPISCITELLI 1. Plans show R4.1 on walls. Energy Calcs say R5. Revise to match. 2. Energy Calcs and EPL card need to be signed by the builder | |||
| PLUM | COMPLETE | 10/29/2020 | 11/04/2020 |
| Note: Released By: JPI | |||
| SW1 | HOLD | 10/29/2020 | 11/02/2020 |
| Note: Held By: CTROHA See marked up site plan | |||
| ZON | HOLD | 10/29/2020 | 10/30/2020 |
| Note: Held By: ELENS Four trees are required for this site. (Need one more.) | |||
| SWALE | COMPLETE | 10/29/2020 | 01/25/2021 |
| Note: Released By: TBAKER |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| CONTRACTOR CHANGE | ¤40.00 | 04/04/2022 |
| CONTRACTOR CHANGE | ¤40.00 | 04/04/2022 |
| PLAN REVIEW - REVISION | ¤32.50 | 04/04/2022 |
| REINSPECTION FEE | ¤40.00 | 04/04/2022 |
| SW ENG REINSPECTION 20 | ¤20.00 | 04/04/2022 |
| STORM WATER PERMIT FEES | ¤80.00 | 11/30/2020 |
| 3% TRANS IMPACT FEE CREDIT | (¤50.22) | 11/30/2020 |
| SEWER CREDIT | (¤1,466.00) | 11/30/2020 |
| SEWER INSPECTION | ¤25.00 | 11/30/2020 |
| SEWER CAPITAL FACILITY | ¤4,596.07 | 11/30/2020 |
| WATER CAPITAL FACILITY FEE | ¤3,374.18 | 11/30/2020 |
| NEW RESIDENTIAL INSPECTIONS | ¤648.00 | 11/30/2020 |
| SITE PLAN 20 | ¤20.00 | 11/30/2020 |
| SURCHARGE FS 533.721 | ¤2.00 | 11/30/2020 |
| SURCHARGE - FS 468.631 | ¤2.00 | 11/30/2020 |
| CONNECTION FEES | ¤1,002.88 | 11/30/2020 |
| METER - DEPOSIT | ¤60.00 | 11/30/2020 |
| WATER- TURN ON | ¤25.00 | 11/30/2020 |
| ADMIN FEE | ¤20.00 | 11/30/2020 |
| BUILDING DISCOUNT 100% | (¤1,560.80) | 11/30/2020 |
| ELECTRIC FEE | ¤254.40 | 11/30/2020 |
| 3% FIRE IMPACT FEE CREDIT | (¤11.01) | 11/30/2020 |
| IMPACT FEE FIRE | ¤367.00 | 11/30/2020 |
| IMPACT FEE PARKS | ¤1,199.12 | 11/30/2020 |
| IMPACT FEE SCHOOL | ¤3,600.00 | 11/30/2020 |
| IMPACT FEE TRANSPORTATION | ¤1,674.00 | 11/30/2020 |
| MECHANICAL FEE | ¤254.40 | 11/30/2020 |
| WATER -IRRIGATION INSPECTION | ¤25.00 | 11/30/2020 |
| 3% PARKS IMPACT FEE CREDIT | (¤35.97) | 11/30/2020 |
| PLAN CHECK FEE | ¤129.60 | 11/30/2020 |
| PLUMBING FEE | ¤254.40 | 11/30/2020 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤14,661.55 |