I want to search for...
Permit #2021020525
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-5112-00000-0110 |
| Block: 00000 |
| Subdivision: 1164 - PINE LAKES INDUSTRIAL PARK |
| Job Phone: 386-274-3120 |
| Location Address: 4 COMMERCE BLVD |
| Type: FU - FIRE UNDERGROUND |
| Issue Date: 03/05/2021 |
| NOC: RECORDED |
| Applicant name: KYLE ROBERT HALL |
| Owner: GIOIA PROPERTIES LLC |
|
Address 10 COMMERCE BLVD PALM COAST, FL 32164 |
| Lot: 0110 |
| Contracted Stated Job Value: ¤40,000.00 |
| Job Description: Installation of 6" Fire Main, DDCVA w/ FDC & Fire Hydrants |
| Type: CN |
Contractor
TOMOKA CONSTRUCTION SERVICES, INC.
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
40 HOLLY STREET HOLLY HILL, FL 32110 |
CUC1225507 (Exp: 08/31/2026) | 386-274-3120 | 386-274-3170 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE FINAL | 09/10/2021 | FINAL APPROVED | JMUNSON |
| HYDRANT FLOW TEST | 08/27/2021 | APPROVED | JMUNSON |
| FIRE SYSTEM FLUSH | 08/27/2021 | CANCELLED BY INSPECTOR | JMUNSON |
| FIRE SYSTEM FLUSH | 05/04/2021 | APPROVED | JMUNSON |
| FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR | 05/03/2021 | APPROVED | JMUNSON |
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 04/23/2021 | APPROVED | JMUNSON |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION In Building Risers 4/20/21 Marked on plan 4/21/21 Marked on plan 4/22/21 Marked on plans from deflection to island | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 04/22/2021 | PARTIALLY APPROVED | JMUNSON |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION In Building Risers 4/20/21 Marked on plan 4/21/21 Marked on plan 4/22/21 Marked on plans from deflection to island | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 04/21/2021 | PARTIALLY APPROVED | JMUNSON |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION In Building Risers 4/20/21 Marked on plan 4/21/21 Marked on plan | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 04/20/2021 | PARTIALLY APPROVED | JMUNSON |
| Note: THIS IS A REINSPECTION In Building Risers 4/20/21 Marked on plan | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 03/10/2021 | PARTIALLY APPROVED | JBODEN |
| Note: In Building Risers |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 03/01/2021 | 03/05/2021 |
| Note: Released By: JOHN BODEN - (386)986-2624 - JBODEN@PALMCOASTGOV.COM | |||
| FI1 | HOLD | 02/09/2021 | 02/24/2021 |
| Note: Held By: WILLIAM MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please separate Fire Lines and Fire Department Connection per AHJ (FDC lines should not be connected to the fire lines and should enter the building separate from the supply line) JFYI... A note was placed on sheet 14 stating the height to the top of the FDC can not be higher than 36" per AHJ |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADMIN COMMERCIAL | ¤60.00 | 03/05/2021 |
| BUILDING DISCOUNT 100% | (¤100.00) | 03/05/2021 |
| FIRE PLANS REVIEW | ¤40.00 | 03/05/2021 |
| SURCHARGE FS 533.721 | ¤2.00 | 03/05/2021 |
| SURCHARGE - FS 468.631 | ¤2.00 | 03/05/2021 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤4.00 |