I want to search for...

Permit #2021020525

Permit Details

Status: FINAL

Parcel Id: 07-11-31-5112-00000-0110
Block: 00000
Subdivision: 1164 - PINE LAKES INDUSTRIAL PARK
Job Phone: 386-274-3120
Location Address: 4 COMMERCE BLVD
Type: FU - FIRE UNDERGROUND
Issue Date: 03/05/2021
NOC: RECORDED
Applicant name: KYLE ROBERT HALL
Owner: GIOIA PROPERTIES LLC

Address

10 COMMERCE BLVD

PALM COAST, FL 32164

Lot: 0110
Contracted Stated Job Value: ¤40,000.00
Job Description: Installation of 6" Fire Main, DDCVA w/ FDC & Fire Hydrants
Type: CN

Contractor

TOMOKA CONSTRUCTION SERVICES, INC.
Status Location Address State License Number Phone Fax
ACTIVE

40 HOLLY STREET

HOLLY HILL, FL 32110

CUC1225507 (Exp: 08/31/2026) 386-274-3120 386-274-3170

Inspection History

Type Request Date Result Inspector
FIRE FINAL 09/10/2021 FINAL APPROVED JMUNSON
HYDRANT FLOW TEST 08/27/2021 APPROVED JMUNSON
FIRE SYSTEM FLUSH 08/27/2021 CANCELLED BY INSPECTOR JMUNSON
FIRE SYSTEM FLUSH 05/04/2021 APPROVED JMUNSON
FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR 05/03/2021 APPROVED JMUNSON
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 04/23/2021 APPROVED JMUNSON
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION In Building Risers 4/20/21 Marked on plan 4/21/21 Marked on plan 4/22/21 Marked on plans from deflection to island
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 04/22/2021 PARTIALLY APPROVED JMUNSON
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION In Building Risers 4/20/21 Marked on plan 4/21/21 Marked on plan 4/22/21 Marked on plans from deflection to island
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 04/21/2021 PARTIALLY APPROVED JMUNSON
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION In Building Risers 4/20/21 Marked on plan 4/21/21 Marked on plan
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 04/20/2021 PARTIALLY APPROVED JMUNSON
Note: THIS IS A REINSPECTION In Building Risers 4/20/21 Marked on plan
FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING 03/10/2021 PARTIALLY APPROVED JBODEN
Note: In Building Risers

Review History

Department Status Date In Date Out
FI1 COMPLETE 03/01/2021 03/05/2021
Note: Released By: JOHN BODEN - (386)986-2624 - JBODEN@PALMCOASTGOV.COM
FI1 HOLD 02/09/2021 02/24/2021
Note: Held By: WILLIAM MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please separate Fire Lines and Fire Department Connection per AHJ (FDC lines should not be connected to the fire lines and should enter the building separate from the supply line) JFYI... A note was placed on sheet 14 stating the height to the top of the FDC can not be higher than 36" per AHJ

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADMIN COMMERCIAL ¤60.00 03/05/2021
BUILDING DISCOUNT 100% (¤100.00) 03/05/2021
FIRE PLANS REVIEW ¤40.00 03/05/2021
SURCHARGE FS 533.721 ¤2.00 03/05/2021
SURCHARGE - FS 468.631 ¤2.00 03/05/2021
Fees Total Due: ¤0.00 Total Paid: ¤4.00