I want to search for...

Permit #2021030720

Permit Details

Status: COED

Parcel Id: 07-11-31-7009-00420-0200
CONDITIONED SPACE: 2422 sqft
GARAGE: 428 sqft
OPENED PORCH (WITH ROOF) : 160 sqft
OPENED PORCH (WITH ROOF) : 33 sqft
Total Square Footage: 3043 sqft
Block: 00420
Subdivision: 2208 - SECTION 9-FLORIDA PARK
Job Phone: 321-610-3924
Location Address: 43 FENWOOD LN
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 03/24/2021
NOC: RECORDED
Applicant name: KENNETH WAYNE CAMBELL JR
Owner: TAGGART LAURA

Address

64 FRANCISCAN LANE

PALM COAST, FL 32136

Lot: 0200
Contracted Stated Job Value: ¤300,000.00
Job Description: SINGLE FAMILY RESIDENCE
Type: CN

Contractor

MERCEDES PREMIER HOMES LLC
Status Location Address Mailing Address State License Number Phone
CANCEL

4885 N WICKHAM RD

MELBOURNE, FL 32940

SUITE 101

MELBOURNE, FL 32940

CBC058803 (Exp: 08/31/2022) 321-610-3924

Sub Contractors

THOMAS A REGULA
Status Location Address State License Number Phone Fax
INACTIVE

11320 PHILLIPS PKWY DRIVE E

JACKSONVILLE, FL 32256

CMC1250075 (Exp: 08/31/2026) 904-278-0339 904-278-0366
SANTOS L HERNANDEZ
Status Location Address State License Number Phone Fax
ACTIVE

946 SHADDICK DRIVE

ORANGE CITY, FL 32763

CCC1328011 (Exp: 08/31/2026) 386-218-4942 386-218-4937
JEFFREY TROY SABAKA
Status Location Address State License Number Phone Fax
ACTIVE

2191 DEERWOOD ACRES DR

ST AUGUSTINE, FL 32084

CFC1427439 (Exp: 08/31/2026) 904-838-2218 904-819-0965
JOSEPH C WRIGHT
Status Location Address Mailing Address State License Number Phone Fax
ACTIVE

15 HARGROVE LANE

PALM COAST, FL 32137

UNIT 3 D

PALM COAST, FL 32137

EC13003278 (Exp: 08/31/2026) 386-447-9644 386-447-9633
ZACHARY PETER BOERA
Status Location Address State License Number Phone
CANCEL

7225 SANDSCOVE COURT, SUITE 1

WINTER PARK, FL 32792

CAC1817652 (Exp: 08/31/2022) 407-629-6920

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 11/18/2021 FINAL APPROVED DCUSHING
ROW - STORMWATER FINAL 11/15/2021 APPROVED - AS NOTED KRUTH
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION the swale is supposed to flow to the left and the right side is way lower than the left call for information 11/12/21 - As stated in the first failed inspection. Storm water is supposed to flow from right to left. Swale was graded to flow left to right. Fill needed from the left property line to about 1/2 way across the front of the house to allow water to flow in the right directions. corrections made
ROW - STORMWATER FINAL 11/12/2021 Disapproved -FEE REQUIRED RGROSS
Note: THIS IS A REINSPECTION the swale is supposed to flow to the left and the right side is way lower than the left call for information 11/12/21 - As stated in the first failed inspection. Storm water is supposed to flow from right to left. Swale was graded to flow left to right. Fill needed from the left property line to about 1/2 way across the front of the house to allow water to flow in the right directions.
ROW - STORMWATER FINAL 11/09/2021 Disapproved -FEE REQUIRED KRUTH
Note: the swale is supposed to flow to the left and the right side is way lower than the left call for information
U -UTILITY RESIDENTIAL FINAL 11/09/2021 FINAL APPROVED DHANEY
ROW - FINAL APRON (AFTER POUR) 11/09/2021 APPROVED KRUTH
ROW FIELD SURVEY /GRADING CERTIFICATION 11/08/2021 APPROVED KRUTH
FINAL SURVEY (OFFICE USE ONLY) 11/08/2021 APPROVED KRUTH
U-CROSS CONNECTION 08/27/2021 APPROVED - AS NOTED JHARDING
Note: No irrigation, no cross connections.
U - SEWER TIE IN 08/26/2021 APPROVED JGIBSON
ROW- PRE-APRON (PRE-POUR) 08/23/2021 APPROVED - AS NOTED KRUTH
Note: THIS IS A REINSPECTION pipe elevations are good but way to much water in the pipe and apron way to soft to pour corrections made pipe is good at the time of the inspection It is the BUILDER'S RESPONSIBILITY: to recheck elevations and pipe size, to insure that an obstruction does not exist upstream and or downstream, that the culvert pipe is set to and or follows the swale plan, form the driveway to the approved site plan and follow the approved driveway detail sheet provided by the City of Palm Coast. PRIOR to placement of concrete.
ROW- PRE-APRON (PRE-POUR) 08/20/2021 Disapproved -FEE REQUIRED KRUTH
Note: pipe elevations are good but way to much water in the pipe and apron way to soft to pour
ELECTRIC - EARLY POWER 08/20/2021 APPROVED - AS NOTED JMUNSON
Note: Emailed FPL at 10:48 am
LATH/BRICK/ WATER BARRIER 07/15/2021 APPROVED MMESSER
Note: THIS IS A REINSPECTION not ready, raw wood exposed at arches over windows
LATH/BRICK/ WATER BARRIER 07/13/2021 Disapproved -FEE REQUIRED WMILLER
Note: not ready, raw wood exposed at arches over windows
LATH/BRICK/ WATER BARRIER 07/06/2021 CANCELLED BY APPLICANT WEB
INSULATION 07/01/2021 APPROVED FWILLIS
ALL ROUGH 06/30/2021 CANCELLED BY APPLICANT WEB
Note: THIS IS A REINSPECTION missing front window and missing door in master bedroom. all windoes and doors need to be installed for all rough or openings need to be sealed off to keep water out missing firestop in two locations. red spray paint on floor indicates where firestiop is missing. this is an incomplete inspection
ALL ROUGH 06/30/2021 APPROVED WMILLER
Note: 6-30-21... prior notes resolved New inspection due to canceled inspection THIS IS A REINSPECTION missing front window and missing door in master bedroom. all windoes and doors need to be installed for all rough or openings need to be sealed off to keep water out missing firestop in two locations. red spray paint on floor indicates where firestiop is missing. this is an incomplete inspection
ALL ROUGH 06/25/2021 Disapproved - NO FEE BGREVE
Note: missing front window and missing door in master bedroom. all windoes and doors need to be installed for all rough or openings need to be sealed off to keep water out missing firestop in two locations. red spray paint on floor indicates where firestiop is missing. this is an incomplete inspection
ROOF SHEATHING / BRACES/TIES/DOWN CELL 06/16/2021 CANCELLED BY APPLICANT WEB
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION S101 Shows Anchor Bolts. If not required show detail. S201 HETA Straps not nailed, RIGHT REAR. S301 Header Detail at bearing wall door, shows 18" straps from header to stud. INSPECTION STOPPED. 6-9-21... notes above resolved... 1. GABLE ENDS NOT PER DETAIL 1201 2. CONTINUOUS LOAD PATH… R301,2.1 OVERFRAMING NOT TIED TO STRUCTURAL MEMBERS BENEATH 3. DETAILS 601 NOT COMPLETED PER DETAIL. (INSPECTION STOPPED)
ROOF SHEATHING / BRACES/TIES/DOWN CELL 06/16/2021 APPROVED BGREVE
Note: New inspection due to canceled inspection THIS IS A REINSPECTION THIS IS A REINSPECTION S101 Shows Anchor Bolts. If not required show detail. S201 HETA Straps not nailed, RIGHT REAR. S301 Header Detail at bearing wall door, shows 18" straps from header to stud. INSPECTION STOPPED. 6-9-21... notes above resolved... 1. GABLE ENDS NOT PER DETAIL 1201 2. CONTINUOUS LOAD PATH… R301,2.1 OVERFRAMING NOT TIED TO STRUCTURAL MEMBERS BENEATH 3. DETAILS 601 NOT COMPLETED PER DETAIL. (INSPECTION STOPPED)
ROOF SHEATHING / BRACES/TIES/DOWN CELL 06/09/2021 Disapproved - NO FEE WMILLER
Note: THIS IS A REINSPECTION S101 Shows Anchor Bolts. If not required show detail. S201 HETA Straps not nailed, RIGHT REAR. S301 Header Detail at bearing wall door, shows 18" straps from header to stud. INSPECTION STOPPED. 6-9-21... notes above resolved... 1. GABLE ENDS NOT PER DETAIL 1201 2. CONTINUOUS LOAD PATH… R301,2.1 OVERFRAMING NOT TIED TO STRUCTURAL MEMBERS BENEATH 3. DETAILS 601 NOT COMPLETED PER DETAIL. (INSPECTION STOPPED)
ROOF VALLEY & METAL 06/08/2021 APPROVED BGREVE
ROOF VALLEY & METAL 06/07/2021 CANCELLED BY APPLICANT WEB
ROOF SHEATHING / BRACES/TIES/DOWN CELL 06/07/2021 Disapproved -FEE REQUIRED FWILLIS
Note: S101 Shows Anchor Bolts. If not required show detail. S201 HETA Straps not nailed, RIGHT REAR. S301 Header Detail at bearing wall door, shows 18" straps from header to stud. INSPECTION STOPPED.
FOUND SURVEY APPROVED (OFFICE) 06/05/2021 APPROVED TBAKER
ELECTRIC TEMP POLE 05/14/2021 APPROVED - AS NOTED RMARTIN
Note: EMAILED FPL RELEASED POWER 10:50
TIE BEAM / LINTEL 05/11/2021 APPROVED BGREVE
MONOLITHIC SLAB 04/28/2021 APPROVED BGREVE
PLUMBING 1ST ROUGH UNDERGROUND 04/23/2021 APPROVED JGIBSON
GRAVITY SEWER TEST 04/23/2021 APPROVED JGIBSON
WATER METER INSTALLATION REQUEST 03/26/2021 APPROVED CSTONE

Review History

Department Status Date In Date Out
SW1 COMPLETE 11/17/2021 11/17/2021
Note: Released By: KALEN RUTH - (386)566-1273 - KRUTH@PALMCOASTGOV.COM
ZON COMPLETE 11/16/2021 11/16/2021
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
ENGIN1 COMPLETE 08/11/2021 08/11/2021
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
SW1 HOLD 08/11/2021 08/19/2021
Note: Held By: ROBERT GROSS - (386)986-4769 - RGROSS@PALMCOASTGOV.COM See Checklist of items required on the surevey. Note that the outside grade at the foundation must be a mimimum of 4 inches below the Finished Floor Elevation.
ZON HOLD 08/11/2021 08/11/2021
Note: Held By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM Revised site plan has been submitted. What has been revised?
CUSVC COMPLETE 06/21/2021 06/28/2021
Note: Released By: HALEIGH HAND - -
ENGIN1 COMPLETE 06/04/2021 06/05/2021
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON COMPLETE 06/04/2021 06/04/2021
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
MECH COMPLETE 04/13/2021 04/13/2021
Note: Released By: CHRIS PISCITELLI - - CPISCITELLI@PALMCOASTGOV.COM
ELEC COMPLETE 03/19/2021 03/19/2021
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
BLD COMPLETE 03/10/2021 03/13/2021
Note: Released By: JPI
CUSVC COMPLETE 03/10/2021 03/17/2021
Note: Released By: HALEIGH HAND - -
ELEC HOLD 03/10/2021 03/11/2021
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Electric load calcs do not match the square footage of the house. 2. Need to reference the 2017 NEC not the 2014 on electrical plan.
ENGIN1 COMPLETE 03/10/2021 03/10/2021
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@CI.PALM-COAST.FL.US
LOCATE COMPLETE 03/10/2021 03/11/2021
Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM
MECH COMPLETE 03/10/2021 03/11/2021
Note: Released By: CHRIS PISCITELLI - - CPISCITELLI@PALMCOASTGOV.COM
PLUM COMPLETE 03/10/2021 03/13/2021
Note: Released By: JPI
SW1 COMPLETE 03/10/2021 03/16/2021
Note: Released By: KALEN RUTH - (386)566-1273 - KKRUTH@PALMCOASTGOV.COM
ZON COMPLETE 03/10/2021 03/15/2021
Note: Released By: ALISHA MOBLEY - (386)986-4733 - AMOBLEY@PALMCOASTGOV.COM
SWALE COMPLETE 03/10/2021 06/09/2021
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
CONTRACTOR CHANGE ¤40.00 11/10/2021
REINSPECTION FEE ¤40.00 11/10/2021
REINSPECTION FEE ¤40.00 11/10/2021
SW ENG - FIELD SURVEY INSPECT ¤20.00 11/10/2021
SW ENG REINSPECTION 20 ¤20.00 11/10/2021
SW ENG REINSPECTION 30 ¤30.00 11/10/2021
STORM WATER PERMIT FEES ¤80.00 03/24/2021
3% TRANS IMPACT FEE CREDIT (¤51.54) 03/24/2021
SEWER INSPECTION ¤25.00 03/24/2021
SEWER CAPITAL FACILITY ¤4,664.55 03/24/2021
WATER CAPITAL FACILITY FEE ¤3,424.45 03/24/2021
NEW RESIDENTIAL INSPECTIONS ¤600.00 03/24/2021
SITE PLAN 20 ¤20.00 03/24/2021
SURCHARGE FS 533.721 ¤2.00 03/24/2021
SURCHARGE - FS 468.631 ¤2.00 03/24/2021
METER - DEPOSIT ¤60.00 03/24/2021
WATER- TURN ON ¤25.00 03/24/2021
ADMIN FEE ¤20.00 03/24/2021
CONNECTION FEES ¤1,017.83 03/24/2021
BUILDING DISCOUNT 100% (¤1,460.00) 03/24/2021
ELECTRIC FEE ¤240.00 03/24/2021
3% FIRE IMPACT FEE CREDIT (¤11.01) 03/24/2021
IMPACT FEE FIRE ¤367.00 03/24/2021
IMPACT FEE PARKS ¤1,199.12 03/24/2021
IMPACT FEE SCHOOL ¤3,600.00 03/24/2021
IMPACT FEE TRANSPORTATION ¤1,718.00 03/24/2021
MECHANICAL FEE ¤240.00 03/24/2021
WATER -IRRIGATION INSPECTION ¤25.00 03/24/2021
3% PARKS IMPACT FEE CREDIT (¤35.97) 03/24/2021
PLAN CHECK FEE ¤120.00 03/24/2021
PLUMBING FEE ¤240.00 03/24/2021
Fees Total Due: ¤0.00 Total Paid: ¤16,321.43