I want to search for...
Permit #2021040044
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7035-01550-0050 |
| Block: 01550 |
| Subdivision: 2172 - SECTION 35-BELLE TERRE |
| Job Phone: 386-327-6937 |
| Location Address: 31 BIRCHBARK LN |
| Type: SLRE - SOLAR ELECTRIC - PHOTOVOLTAIC |
| Issue Date: 04/07/2021 |
| NOC: RECORDED |
| Applicant name: ROBERT JAMES RIHERD |
| Owner: ALCORN TIMOTHY A & KATHLEEN D ALCORN H&W |
|
Address 31 BIRCHBARK LANE PALM COAST, FL 32137 |
| Lot: 0050 |
| Contracted Stated Job Value: ¤63,615.00 |
| Job Description: 6,560 Watt Rooftop Mounted Solar System |
| Type: CN |
Contractor
EMPOWER SOLAR SOLUTIONS
| Status | Location Address | State License Number | Phone |
| INACTIVE |
100 E GRANADA BLVD ORMOND BEACH, FL 32176 |
CVC57067 (Exp: 08/31/2024) | 386-327-6937 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 05/20/2021 | FINAL APPROVED | RMARTIN |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION CONDUCTOR SIZE IS NOT RATED FOR 80AMP FUSES, PLANS DO NOT MATCH WHAT IS INSTALLED 5/14/21 #6 wire is not rated for the 75 amp fuses that are installed. Plans call for 80 amp fuses and #4 wire. | |||
| ELECTRIC FINAL | 05/14/2021 | Disapproved -FEE REQUIRED | JMUNSON |
| Note: THIS IS A REINSPECTION CONDUCTOR SIZE IS NOT RATED FOR 80AMP FUSES, PLANS DO NOT MATCH WHAT IS INSTALLED 5/14/21 #6 wire is not rated for the 75 amp fuses that are installed. Plans call for 80 amp fuses and #4 wire. | |||
| ELECTRIC FINAL | 05/06/2021 | Disapproved -FEE REQUIRED | RMARTIN |
| Note: CONDUCTOR SIZE IS NOT RATED FOR 80AMP FUSES, PLANS DO NOT MATCH WHAT IS INSTALLED |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 04/05/2021 | 04/05/2021 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 04/05/2021 | 04/06/2021 |
| Note: Released By: FRED REODICA - (386)986-4734 - FReodica@ci.palm-coast.fl.us | |||
| BLD | COMPLETE | 04/01/2021 | 04/01/2021 |
| Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM | |||
| ELEC | HOLD | 04/01/2021 | 04/01/2021 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM #6 is not rated for 80 amps NEC 2017 310.15 (b) (16) |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 05/19/2021 |
| REINSPECTION FEE | ¤40.00 | 05/10/2021 |
| SURCHARGE FS 533.721 | ¤2.00 | 04/07/2021 |
| SURCHARGE - FS 468.631 | ¤2.00 | 04/07/2021 |
| ADMIN FEE | ¤20.00 | 04/07/2021 |
| BUILDING DISCOUNT 100% | (¤183.17) | 04/07/2021 |
| ELECTRIC FEE | ¤98.17 | 04/07/2021 |
| INSPECTION 40 | ¤40.00 | 04/07/2021 |
| PLAN REVIEW 25 | ¤25.00 | 04/07/2021 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤84.00 |