Permit #2021040483

Permit Details

Status: COED

Parcel Id: 07-11-31-7034-00860-0040
CONDITIONED SPACE: 2552 sqft
GARAGE: 634 sqft
OPENED PORCH (WITH ROOF) : 275 sqft
OPENED PORCH (WITH ROOF) : 35 sqft
Total Square Footage: 3496 sqft
Block: 00860
Subdivision: 2165 - SECTION 34-EASTHAMPTON
Job Phone: 321-610-3924
Location Address: 119 EVANS DR
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 05/04/2021
NOC: RECORDED
Applicant name: KENNETH WAYNE CAMBELL JR
Owner: VINTAGE ESTATE HOMES LLC

Address

4885 NORTH WICKHAM RD

MELBOURNE, FL 32940

Lot: 0040
Contracted Stated Job Value: ¤250,000.00
Job Description: SINGLE FAMILY RESIDENCE
Type: CN

Contractor

MERCEDES PREMIER HOMES LLC
Status Location Address Mailing Address State License Number Phone
CANCEL

4885 N WICKHAM RD

MELBOURNE, FL 32940

SUITE 101

MELBOURNE, FL 32940

CBC058803 (Exp: 08/31/2022) 321-610-3924

Sub Contractors

JEFFREY TROY SABAKA
Status Location Address State License Number Phone Fax
ACTIVE

2191 DEERWOOD ACRES DR

ST AUGUSTINE, FL 32084

CFC1427439 (Exp: 08/31/2026) 904-838-2218 904-819-0965
JOSEPH C WRIGHT
Status Location Address Mailing Address State License Number Phone Fax
ACTIVE

15 HARGROVE LANE

PALM COAST, FL 32137

UNIT 3 D

PALM COAST, FL 32137

EC13003278 (Exp: 08/31/2026) 386-447-9644 386-447-9633
SANTOS L HERNANDEZ
Status Location Address State License Number Phone Fax
ACTIVE

946 SHADDICK DRIVE

ORANGE CITY, FL 32763

CCC1328011 (Exp: 08/31/2026) 386-218-4942 386-218-4937
ZACHARY PETER BOERA
Status Location Address State License Number Phone
CANCEL

7225 SANDSCOVE COURT, SUITE 1

WINTER PARK, FL 32792

CAC1817652 (Exp: 08/31/2022) 407-629-6920

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 01/28/2022 FINAL APPROVED JWALKER
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION Exterior outlets need to have waterproof boxes and water resistant outlets. Front entry light fixture not installed Support the expansion overflow pvc line at the water heater. Seal the penetrations going through the garage ceiling. The duct for the stove hood needs to be sealed. The ceiling where the duct penetrates needs to also be sealed. Please leave the finish cover off for reinspection. Seal the hole in the HVAC closet. Master tub tile has not been grouted. 1/26/22 Exterior outlets and covers have not been correct. One penetration at garage ceiling not sealed.
BLD - BUILDING FINAL 01/27/2022 Disapproved -FEE REQUIRED JWALKER
Note: New inspection due to canceled inspection THIS IS A REINSPECTION Exterior outlets need to have waterproof boxes and water resistant outlets. Front entry light fixture not installed Support the expansion overflow pvc line at the water heater. Seal the penetrations going through the garage ceiling. The duct for the stove hood needs to be sealed. The ceiling where the duct penetrates needs to also be sealed. Please leave the finish cover off for reinspection. Seal the hole in the HVAC closet. Master tub tile has not been grouted. 1/27/22 The exterior outlet next to the A/C condensor has not been changed to a Tamper resistant, Water resistant outlet the, The front entry and to rear outlets were corrected The ceiling penetration in the garage has not been corrected.
BLD - BUILDING FINAL 01/26/2022 CANCELLED BY APPLICANT WEB
Note: THIS IS A REINSPECTION Exterior outlets need to have waterproof boxes and water resistant outlets. Front entry light fixture not installed Support the expansion overflow pvc line at the water heater. Seal the penetrations going through the garage ceiling. The duct for the stove hood needs to be sealed. The ceiling where the duct penetrates needs to also be sealed. Please leave the finish cover off for reinspection. Seal the hole in the HVAC closet. Master tub tile has not been grouted.
BLD - BUILDING FINAL 01/26/2022 Disapproved - NO FEE JWALKER
Note: THIS IS A REINSPECTION Exterior outlets need to have waterproof boxes and water resistant outlets. Front entry light fixture not installed Support the expansion overflow pvc line at the water heater. Seal the penetrations going through the garage ceiling. The duct for the stove hood needs to be sealed. The ceiling where the duct penetrates needs to also be sealed. Please leave the finish cover off for reinspection. Seal the hole in the HVAC closet. Master tub tile has not been grouted. 1/26/22 Exterior outlets and covers have not been correct. One penetration at garage ceiling not sealed.
BLD - BUILDING FINAL 01/25/2022 CANCELLED BY APPLICANT WEB
Note: THIS IS A REINSPECTION
BLD - BUILDING FINAL 01/25/2022 Disapproved - NO FEE JWALKER
Note: Exterior outlets need to have waterproof boxes and water resistant outlets. Front entry light fixture not installed Support the expansion overflow pvc line at the water heater. Seal the penetrations going through the garage ceiling. The duct for the stove hood needs to be sealed. The ceiling where the duct penetrates needs to also be sealed. Please leave the finish cover off for reinspection. Seal the hole in the HVAC closet. Master tub tile has not been grouted.
U -UTILITY RESIDENTIAL FINAL 01/25/2022 FINAL APPROVED JHARDING
Note: THIS IS A REINSPECTION
U -UTILITY RESIDENTIAL FINAL 01/24/2022 CANCELLED BY APPLICANT JHARDING
BLD - BUILDING FINAL 01/24/2022 CANCELLED BY APPLICANT JWALKER
U-CROSS CONNECTION 01/24/2022 APPROVED - AS NOTED JHARDING
Note: No irrigation, no cross connections.
FINAL SURVEY (OFFICE USE ONLY) 01/20/2022 APPROVED RGROSS
ROW FIELD SURVEY /GRADING CERTIFICATION 01/20/2022 APPROVED RGROSS
Note: See note on Final Stormwater.
ROW - STORMWATER FINAL 01/20/2022 APPROVED - AS NOTED RGROSS
Note: Per builder. Sod is scheduled today to be thrown on all bare earth areas.
ROW - FINAL APRON (AFTER POUR) 01/20/2022 APPROVED RGROSS
ROW- PRE-APRON (PRE-POUR) 01/14/2022 APPROVED GBERTOLA
Note: THIS IS A REINSPECTION Culvert elevation is good. However, large 15 x 8 ft high pile of dirt in the pour area from an ongoing pep tank installation. Must reschedule to verify it is all removed and recompacted. 01/14/2022=THIS INSPECTION WAS PASS ON 12/14/2021
TUB SET 12/20/2021 CANCELLED BY APPLICANT WEB
TUB SET 12/20/2021 APPROVED MGIBSON
ELECTRIC - EARLY POWER 12/17/2021 APPROVED - AS NOTED JWALKER
Note: Email FPL 1:22 pm
U - SEWER TIE IN 12/15/2021 APPROVED JWALKER
ROW- PRE-APRON (PRE-POUR) 12/14/2021 APPROVED - AS NOTED RGROSS
Note: THIS IS A REINSPECTION Culvert elevation is good. However, large 15 x 8 ft high pile of dirt in the pour area. Must reschedule to verify it is all removed and recompacted. 12/14/21 - Bolts for the band should face down or be cut off below the top elevation of the rounded culvert for maximum concrete thickness. Being approved as noted that they should be cut before pouring. Thickness of concrete will still be over 5 inches.
ROW- PRE-APRON (PRE-POUR) 12/13/2021 Disapproved - NO FEE RGROSS
Note: Culvert elevation is good. However, large 15 x 8 ft high pile of dirt in the pour area from an ongoing pep tank installation. Must reschedule to verify it is all removed and recompacted.
LATH/BRICK/ WATER BARRIER 11/15/2021 APPROVED JWALKER
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION Metal lath needs to be attached 7" o.c. vertically and horizontally. ASTM C1063 or C1787 R-703.7.1 10/22/21 Above corrections have not been made. 10/26/21 Please have above corrections made before calling in this inspection. 10/28/21 The lath needs to be fastened at 7" o.c. vertically and horizontally Suggest a meeting with contractor. 11/3/21 It has been determined by the building offical that the staples fastened as per ASTM C1063 are sufficent being fastened to the 16" o.c. framing members spaced at 7" apart. The metal lath fasteners installed at the gable ends are not spaced at 16" o.c. and are not fastened to framing members The reason for this is the gable end wall framing is 2' o.c. Have engineer submitt a letter stating as is fastening is a sufficent. Or install framing members at 16" o.c. and install lath fasteners as per ASTM C1063.
LATH/BRICK/ WATER BARRIER 11/03/2021 Disapproved - NO FEE JWALKER
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION Metal lath needs to be attached 7" o.c. vertically and horizontally. ASTM C1063 or C1787 R-703.7.1 10/22/21 Above corrections have not been made. 10/26/21 Please have above corrections made before calling in this inspection. 10/28/21 The lath needs to be fastened at 7" o.c. vertically and horizontally Suggest a meeting with contractor. 11/3/21 It has been determined by the building offical that the staples fastened as per ASTM C1063 are sufficent being fastened to the 16" o.c. framing members spaced at 7" apart. The metal lath fasteners installed at the gable ends are not spaced at 16" o.c. and are not fastened to framing members The reason for this is the gable end wall framing is 2' o.c. Have engineer submitt a letter stating as is fastening is a sufficent. Or install framing members at 16" o.c. and install lath fasteners as per ASTM C1063.
LATH/BRICK/ WATER BARRIER 10/28/2021 Disapproved - NO FEE JWALKER
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION Metal lath needs to be attached 7" o.c. vertically and horizontally. ASTM C1063 or C1787 R-703.7.1 10/22/21 Above corrections have not been made. 10/26/21 Please have above corrections made before calling in this inspection. 10/28/21 The lath needs to be fastened at 7" o.c. vertically and horizontally Suggest a meeting with contractor.
LATH/BRICK/ WATER BARRIER 10/26/2021 Disapproved -FEE REQUIRED JWALKER
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION Metal lath needs to be attached 7" o.c. vertically and horizontally. ASTM C1063 or C1787 R-703.7.1 10/22/21 Above corrections have not been made. 10/26/21 Please have above corrections made before calling in this inspection.
LATH/BRICK/ WATER BARRIER 10/22/2021 Disapproved -FEE REQUIRED JWALKER
Note: THIS IS A REINSPECTION Metal lath needs to be attached 7" o.c. vertically and horizontally. ASTM C1063 or C1787 R-703.7.1 10/22/21 Above corrections have not been made.
PEP TANK INSTALLATION REQUEST 10/21/2021 APPROVED CSTONE
LATH/BRICK/ WATER BARRIER 10/19/2021 Disapproved - NO FEE JWALKER
Note: Metal lath needs to be attached 7" o.c. vertically and horizontally. ASTM C1063 or C1787 R-703.7.1
INSULATION 10/18/2021 APPROVED JWALKER
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION 10/15/21 As noted in the all rough inspection. The metal stud framing needs to grounded. And due to the non continuty of the framing each seprate area of the metal stud walls will need to be grounded.. Ground the HVAC , Dryer ,Water heater etc. 10/18/21 Cheif Building offical stated grounding of interior light gauge metal studs to electrical system is not necessary.
INSULATION 10/15/2021 Disapproved -FEE REQUIRED JWALKER
Note: THIS IS A REINSPECTION 10/15/21 As noted in the all rough inspection. The metal stud framing needs to grounded. And due to the non continuty of the framing each seprate area of the metal stud walls will need to be grounded.. Ground the HVAC , Dryer ,Water heater etc.
INSULATION 10/14/2021 CANCELLED BY APPLICANT JWALKER
INSULATION 10/06/2021 CANCELLED BY INSPECTOR JWALKER
Note: Ground wire to UFER not installed. All metal framing needs to be bonded. All separate metal framing needs to be bonded due to the breaks in the framing. Missing bonding wire at Air Handler. Fill 5' head test.
ALL ROUGH 10/06/2021 APPROVED - AS NOTED JWALKER
Note: Ground wire to UFER not installed. All metal framing needs to be bonded. All separate metal framing needs to be bonded due to the breaks in the framing. Missing bonding wire at Air Handler. Fill 5' head test.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 08/19/2021 APPROVED TSTAUFFACHER
ROOF VALLEY & METAL 08/19/2021 APPROVED TSTAUFFACHER
TIE BEAM / LINTEL 07/14/2021 APPROVED TSTAUFFACHER
Note: THIS IS A REINSPECTION Multiple bar do not meet clearance, marked on plans Bar on right side of home easily removed by hand// epoxy set not compliant with manufactures specs
TIE BEAM / LINTEL 07/13/2021 Disapproved - NO FEE TSTAUFFACHER
Note: Multiple bar do not meet clearance, marked on plans Bar on right side of home easily removed by hand// epoxy set not compliant with manufactures specs R404.1.3.3.7.4Support and cover. Reinforcement shall be secured in the proper location in the forms with tie wire or other bar support system to prevent displacement during the concrete placement operation. Steel reinforcement in concrete cast against the earth shall have a minimum cover of 3 inches (75 mm). Minimum cover for reinforcement in concrete cast in removable forms that will be exposed to the earth or weather shall be 11/2 inches (38 mm) for No. 5 bars and smaller, and 2 inches (50 mm) for No. 6 bars and larger. For concrete cast in removable forms that will not be exposed to the earth or weather, and for concrete cast in stay-in-place forms, minimum cover shall be 3/4 inch (19 mm). The minus tolerance for cover shall not exceed the smaller of one-third the required cover or 3/8 inch (10 mm).
FOUND SURVEY APPROVED (OFFICE) 06/22/2021 APPROVED TBAKER
MONOLITHIC SLAB 06/08/2021 APPROVED TSTAUFFACHER
PLUMBING 1ST ROUGH UNDERGROUND 06/03/2021 APPROVED JGIBSON
GRAVITY SEWER TEST 06/03/2021 APPROVED JGIBSON
WATER METER INSTALLATION REQUEST 05/19/2021 APPROVED CSTONE

Review History

Department Status Date In Date Out
MECH COMPLETE 12/28/2021 12/28/2021
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
ENGIN1 COMPLETE 06/22/2021 06/22/2021
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON COMPLETE 06/22/2021 06/22/2021
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
MECH COMPLETE 04/27/2021 04/28/2021
Note: Released By: CHRIS PISCITELLI - - CPISCITELLI@PALMCOASTGOV.COM
MECH HOLD 04/23/2021 04/26/2021
Note: Held By: CHRIS PISCITELLI - - CPISCITELLI@PALMCOASTGOV.COM Need to change subcontractor to match Energy calcs submitted.
ZON COMPLETE 04/23/2021 04/26/2021
Note: Released By: TRACEY DOAK - (386)986-2473 - TDOAK@PALMCOASTGOV.COM
BLD COMPLETE 04/21/2021 04/21/2021
Note: Released By: JOHN BODEN - (386)986-2624 - JBODEN@PALMCOASTGOV.COM
BLD HOLD 04/09/2021 04/15/2021
Note: 1. Knee wall detail, #0180, page S301, does not call out stud spacing. Please clarify. 2. Provide door and window schedule. 3. Provide wall sheathing nailing patterns. Include size, type of fastener.
CUSVC COMPLETE 04/09/2021 04/13/2021
Note: Released By: HALEIGH HAND - -
ELEC COMPLETE 04/09/2021 04/12/2021
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ENGIN1 COMPLETE 04/09/2021 04/09/2021
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
LOCATE COMPLETE 04/09/2021 04/14/2021
Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM
MECH HOLD 04/09/2021 04/12/2021
Note: Held By: CHRIS PISCITELLI - - CPISCITELLI@PALMCOASTGOV.COM Provide Energy Calcs from 2020 7Th edition code cycle
PLUM COMPLETE 04/09/2021 04/15/2021
Note: Released By: JPI
SW1 COMPLETE 04/09/2021 04/13/2021
Note: Released By: KALEN RUTH - (386)566-1273 - KKRUTH@PALMCOASTGOV.COM
ZON HOLD 04/09/2021 04/14/2021
Note: Held By: TRACEY DOAK - (386)986-2473 - TDOAK@PALMCOASTGOV.COM Please have surveyor move the elevations that are covering the house setbacks on the site plan.
SWALE COMPLETE 04/09/2021 07/06/2021
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
PLAN REVIEW - REVISION ¤32.50 01/31/2022
REINSPECTION RESIDENTIAL ¤40.00 01/31/2022
REINSPECTION RESIDENTIAL ¤40.00 01/31/2022
REINSPECTION RESIDENTIAL ¤40.00 01/31/2022
REINSPECTION RESIDENTIAL ¤40.00 01/31/2022
CONNECTION FEES ¤1,017.83 05/04/2021
CONTRACTOR CHANGE ¤40.00 05/04/2021
BUILDING DISCOUNT 100% (¤1,552.40) 05/04/2021
ELECTRIC FEE ¤253.20 05/04/2021
3% FIRE IMPACT FEE CREDIT (¤11.01) 05/04/2021
IMPACT FEE FIRE ¤367.00 05/04/2021
IMPACT FEE PARKS ¤1,199.12 05/04/2021
IMPACT FEE SCHOOL ¤3,600.00 05/04/2021
IMPACT FEE TRANSPORTATION ¤1,718.00 05/04/2021
MECHANICAL FEE ¤253.20 05/04/2021
WATER -IRRIGATION INSPECTION ¤25.00 05/04/2021
3% PARKS IMPACT FEE CREDIT (¤35.97) 05/04/2021
PLAN CHECK FEE ¤128.80 05/04/2021
PLUMBING FEE ¤253.20 05/04/2021
NEW RESIDENTIAL INSPECTIONS ¤644.00 05/04/2021
SITE PLAN 20 ¤20.00 05/04/2021
SURCHARGE FS 533.721 ¤2.00 05/04/2021
SURCHARGE - FS 468.631 ¤2.00 05/04/2021
STORM WATER PERMIT FEES ¤80.00 05/04/2021
3% TRANS IMPACT FEE CREDIT (¤51.54) 05/04/2021
SEWER CREDIT (¤2,465.75) 05/04/2021
SEWER INSPECTION ¤25.00 05/04/2021
SEWER CAPITAL FACILITY ¤4,664.55 05/04/2021
WATER CAPITAL FACILITY FEE ¤3,424.45 05/04/2021
METER - DEPOSIT ¤60.00 05/04/2021
WATER- TURN ON ¤25.00 05/04/2021
ADMIN FEE ¤20.00 05/04/2021
Fees Total Due: ¤0.00 Total Paid: ¤13,898.18