Permit Details

Status: COED

Parcel Id: 03-12-31-0000-01010-0120
Total Square Footage: 6804 sqft
Block: 01010
Subdivision: -
Job Phone: 407-448-9300
Location Address: 6372 STATE HWY 100 E
Type: BC - BUILDING COMMERCIAL
Issue Date: 09/27/2021
NOC: RECORDED
Applicant name: GARY WAYNE BRIDGES
Owner: BELLA CITA STORAGE LLC

Address

880 BAY ROAD

MOUNT DORA, FL 32757

Lot: 0120
Contracted Stated Job Value: ¤360,000.00
Job Description: BUILDING A - SELF STORAGE FACILITY & OFFICE
Type: CN

Contractor

G&M CONSTRUCTION SERVICES, INC.
Status Location Address State License Number Phone
INACTIVE

PO BOX 2316

ORLANDO, FL 32804

CGC062542 (Exp: 08/31/2022) 407-448-9300

Sub Contractors

MATTHEW JAMES BLANCHARD
Status Location Address State License Number Phone
INACTIVE

PO BOX 932

MT. DORA, FL 32757

EC13009373 (Exp: 08/31/2022) 352-383-4868
JOHN CHARLES GRAY
Status Location Address State License Number Phone Fax
ACTIVE

2707 ANNETTE STREET

FLAGLER BEACH, FL 32136

CFC1425975 (Exp: 08/31/2026) (386)793-3690 (386)439-7585
THOMAS ERIC SWORD
Status Location Address State License Number Phone
CANCEL

10330 PLEASANT VIEW DR

LEESBURG, FL 34788

CAC1814523 (Exp: 08/31/2022) 352-434-7550

Inspection History

Type Request Date Result Inspector
PLUMBING FINAL 06/29/2022 APPROVED MGIBSON
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION NEED TO INSTALL VACUUME BREAKER FOR BOTTOM FED WATER HEATER AND SCHEDULE 40 CAPS ON FUTURE SINK AT FRONT OF BUILDING. SPOKE TO JOHN GREY AND HE ISN'T READY FORINSPECTION YET
BUILDING FINAL 06/29/2022 FINAL APPROVED DCUSHING
FIRE FINAL 06/27/2022 APPROVED RMARTIN
PLUMBING FINAL 06/27/2022 Disapproved - NO FEE MGIBSON
Note: THIS IS A REINSPECTION NEED TO INSTALL VACUUME BREAKER FOR BOTTOM FED WATER HEATER AND SCHEDULE 40 CAPS ON FUTURE SINK AT FRONT OF BUILDING. SPOKE TO JOHN GREY AND HE ISN'T READY FORINSPECTION YET
FIREWALL FRAMING 06/23/2022 APPROVED DCUSHING
FIREWALL FINAL 06/23/2022 FINAL APPROVED DCUSHING
PLUMBING FINAL 06/23/2022 Disapproved - NO FEE MGIBSON
Note: NEED TO INSTALL VACUUME BREAKER FOR BOTTOM FED WATER HEATER AND SCHEDULE 40 CAPS ON FUTURE SINK AT FRONT OF BUILDING.
U - UTILITY COMMERCIAL FINAL 06/23/2022 APPROVED JHARDING
EXTERIOR ARCHITECTURAL FEATURES 06/21/2022 APPROVED JHARDING
FIREWALL PENETRATIONS 06/17/2022 APPROVED DCUSHING
ELECTRIC FINAL 06/07/2022 APPROVED RMARTIN
ELECTRIC - EARLY POWER 05/10/2022 APPROVED - AS NOTED RMARTIN
Note: EMAILED FPL RELEASED POWER 4:00
ELECTRIC - EARLY POWER 05/06/2022 Disapproved - NO FEE JMUNSON
Note: Not ready. Panels need to be finished and completly closed with no openings and labeled.
FIREWALL DRYWALL NAILING 04/29/2022 APPROVED - AS NOTED DCUSHING
Note: THIS IS A REINSPECTION Partial for first layer screw off only Fire Caulk and Rock Wool @ cutouts as discussed w/ super
HVAC FINAL 04/28/2022 FINAL APPROVED CPISCITELLI
FIREWALL DRYWALL NAILING 04/14/2022 PARTIALLY APPROVED LMILLER
Note: Partial for first layer screw off only
INSULATION 04/08/2022 APPROVED - AS NOTED LMILLER
Note: THIS IS A REINSPECTION Need energy calcs on site for inspection, (Per Paul the plans do not call for Foam but Foam was used therefore a revision is needed) Will need Insulation Certificate of unsulation R-rating on site for insppection. Need fire blocking completed 4-8-22 Ok to proceed at contractors risk with wall board, need revision for energy calcs (foam insulation was placed in walls ceiling).
INSULATION 04/06/2022 Disapproved -FEE REQUIRED LMILLER
Note: Need energy calcs on site for inspection, (Per Paul the plans do not call for Foam but Foam was used therefore a revision is needed) Will need Insulation Certificate of unsulation R-rating on site for insppection. Need fire blocking completed
FRAMING 04/04/2022 APPROVED - AS NOTED DCUSHING
Note: THIS IS A REINSPECTION need to pass roof sheathing braces ties prior to this inspection Contractor to provide letter, re: hanger change
FRAMING 03/23/2022 Disapproved - NO FEE LMILLER
Note: need to pass roof sheathing braces ties prior to this inspection
ELECTRIC 1ST ROUGH 03/18/2022 APPROVED - AS NOTED RMARTIN
Note: THIS SHOULD HAVE BEEN 2ND ROUGH, PASSED
PLUMBING 2ND ROUGH 12/29/2021 APPROVED MGIBSON
MONOLITHIC SLAB 12/09/2021 CANCELLED BY INSPECTOR LMILLER
Note: Wrong inspection called in (not needed) (need an Accessory Structure Permit for work performed without a permit)
LATH/BRICK/WATER BARRIER 12/08/2021 PARTIALLY APPROVED LMILLER
Note: 12-08-21... looked at waterpoofing coating only
EXTERIOR WALL SHEATHING / SHEARWALL 12/01/2021 PARTIALLY APPROVED LMILLER
Note: This is for DensGlass screw inspection only. Approved based on site inspection verifying screws are applied in vertical rows 12 inches apart max with max spacing of 6 inches within rows. (approved based on conversations between Building Official and Architect).
ROOF SHEATHING / BRACE / TIE DOWN 11/09/2021 APPROVED - AS NOTED JWALKER
Note: THIS IS A REINSPECTION this was for roof and wall sheathing only per paul 11/9/21 This inspection was for building A exterior metal sheeting. And roof metal. side b near road passed screwing this is the side receiving denz glass. Side a needs to be reispected at HVAC units. Upper panel screwing passed on side A, the upper foam was not installed Roof panel screwing Passed. Parapet screwing needs upper screwing checked before install of finish cap
HVAC ROUGH 11/04/2021 APPROVED - AS NOTED CPISCITELLI
Note: will look at all duct to units and fire damper on final inspection
ROOF SHEATHING / BRACE / TIE DOWN 10/27/2021 PARTIALLY APPROVED LMILLER
Note: this was for roof and wall sheathing only per paul
BLD - SEWER TIE IN 10/15/2021 APPROVED MGIBSON
FOUNDATION SURVEY - OFFICE USE ONLY 10/08/2021 APPROVED DLEAP

Review History

Department Status Date In Date Out
BLD COMPLETE 02/04/2022 02/14/2022
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM
BADMIN COMPLETE 02/02/2022 02/02/2022
Note: Released By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM Held By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM Please rename your files according to our naming convention.
PLENG COMPLETE 10/07/2021 10/07/2021
Note: Released By: DENNIS R. LEAP, P.E. - - DLEAP@PALMCOASTGOV.COM
PLENG HOLD 10/05/2021 10/07/2021
Note: Held By: DENNIS R. LEAP, P.E. - - DLEAP@PALMCOASTGOV.COM 1. Foundation Survey to be signed and sealed. 2.Label plan as Foundation Survey.
ARCHR COMPLETE 09/22/2021 09/27/2021
Note: Released By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM
ELEC COMPLETE 09/22/2021 09/22/2021
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
MECH COMPLETE 09/22/2021 09/23/2021
Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM
BLD COMPLETE 09/22/2021 09/22/2021
Note: Released By: FRED REODICA - (386)986-4734 - FREODICA@PALMCOASTGOV.COM
BADMIN HOLD 06/23/2021 06/23/2021
Note: Held By: SCOTT THOMAS - - STHOMAS@PALMCOASTGOV.COM RENAME TO NOC.PDF
BADMIN COMPLETE 06/23/2021 06/23/2021
Note: Released By: SCOTT THOMAS - - STHOMAS@PALMCOASTGOV.COM
ELEC HOLD 05/10/2021 05/10/2021
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Reference the 2020 Energy code 2. Do not have to submit riser diagram
ARCHR HOLD 05/03/2021 05/06/2021
Note: Held By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM Provide color elevation renderings approved with the DO to note colors being used on the walls.
BLD HOLD 05/03/2021 05/17/2021
Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code-Building 1. Provide complete copy of Geotechnical Investigation Report signed and sealed by a Florida licensed professional engineer. It appears a geotechnical investigation report was not included with the civil plans under the Commercial Site Development Permit. 2. Design professional in responsible charge to fill in steel building design engineer’s "approval’ certification box and sign and date on each plan sheet. As an alternative, these plan sheets can be provided at a later date as a deferred submittal in accordance with FBC-Building Section 107.3.4.1. If requesting these plan sheets to be a deferred submittal, approval blocks will still need to be signed and dated before they are submitted to the Building Department for review and approval and Architectural cover sheet will have to be noted in some manner indicating steel building plans will be provided at a later date as a deferred submittal per Section 107.3.4.1. Please note however, if steel building plans will be submitted later as a deferred submittal, an inspection hold will be placed preventing a framing inspection until deferred submittals have been submitted, reviewed and approved. Please allow ample time for review. 3. Remove all references to "fire barrier" on steel building plans. Walls are actually "fire walls" per FBC-Building Section 706.1 and shall be referred to as fire walls. 4. Steel building design engineer shall certify structural stability of fire walls per Section 706.2 indicating either by written notes on one or more plan sheets indicating firewalls are designed and constructed to allow collapse of the structure on either side without collapse of the fire wall. As an alternative engineer can provide design in accordance with NFPA 221. 5. Steel building plans shall reference the 2020 Florida Building Code Building (2017 edition is referenced). Engineer to remove references to the IBC. 6. Reorganize UL fire wall details on Sheet A801 so that the file is organized to read from top to bottom and left to right from file beginning to file end. As currently printed, file details appear out of order. Please also ensure complete file is provided. Please be advised, the UL (U419) design provided is for a proprietary fire wall; therefore no material substitutions are allowed beyond those called out in the file. IT IS STRONGLY recommended a note or notes be added advising the contractor of the limitations to those proprietary materials listed as deviations from approved materials will not be allowed under any circumstances. 7. Add fire wall door design standard to door schedule or by conspicuous note for doors in firewalls per Section 716.5.6. 8. Change occupancy of meeting room from A-2 to B (or simply leave unlabeled). This room is not an A-2 occupancy per Section 301.1.2 No’s 1 and 2. 9. Provide thermal barrier to separate foam plastic insulation in attic from building interior per Section 2603.4. 10. Provide dimensions (both width and length in the direction of egress) of landings at all exterior doors per Section 1010.1.6. All comments below per the 2020 Florida Building Code-Accessibility 1. Provide maneuvering dimensions of exterior landings at all exterior doors based on side approach to hinge side of pull side of doors per Section 404.2.4 and Table 404.2.4.1. It appears the required dimension of 24 inches extending beyond the latch side has not been provided. It is unclear if the landing provides 48 inches of clearance perpendicular to doorways. 2. Provide maneuvering dimensions at all interior doorways based on forward approach per Section 404.2.4 and Table3 404.2.4.1. It is unclear if maneuvering space of 18 inches is provided beyond the latch side on the pull side of interior doors including bathroom door.
DSD COMPLETE 05/03/2021 05/06/2021
Note: Released By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM
ELEC HOLD 05/03/2021 05/10/2021
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Submit riser diagram showing panel locations, meter locations, breaker sizes and wire sizes. 2. Reference the 2020 Energy code.
FI1 COMPLETE 05/03/2021 05/13/2021
Note: Released By: WILLIAM MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM
MECH HOLD 05/03/2021 05/11/2021
Note: Held By: CHRIS PISCITELLI - - CPISCITELLI@PALMCOASTGOV.COM 1. All codes need to reference 2020 7Th edition- FBC Mechanical, FBC Energy Conservation, and FBC Accessibility 2. Ventialtion calculation needs to reference 2020 7Th edition FBC Mechanical 3. Provide heatload calculation per C403.2.1 FBC Energy Conservation 2020 7th edition
PLUM COMPLETE 05/03/2021 05/17/2021
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM
UD1 COMPLETE 05/03/2021 05/04/2021
Note: Released By: CHRIS JOHNSON - - CJOHNSON@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION - COMMERCIAL ¤60.00 07/06/2022
BUILDING DISCOUNT 100% (¤1,302.00) 09/27/2021
3% FIRE IMPACT FEE CREDIT (¤122.13) 09/27/2021
IMPACT FEE FIRE ¤3,540.00 09/27/2021
IMPACT FEE FIRE ¤531.00 09/27/2021
IMPACT FEE TRANSPORTATION ¤3,418.20 09/27/2021
IMPACT FEE TRANSPORTATION ¤2,706.00 09/27/2021
SITE PLAN 20 ¤20.00 09/27/2021
SURCHARGE FS 533.721 ¤2.00 09/27/2021
SURCHARGE - FS 468.631 ¤2.00 09/27/2021
3% TRANS IMPACT FEE CREDIT (¤183.73) 09/27/2021
ADMINISTRATIVE - COMMERCIAL ¤60.00 09/27/2021
INSPECTION- ELECTRICAL ¤276.00 09/27/2021
INSPECTION - MECHANICAL ¤276.00 09/27/2021
INSPECTION - PLUMBING ¤276.00 09/27/2021
PLAN REVIEW - COMMERCIAL ¤414.00 09/27/2021
Fees Total Due: ¤0.00 Total Paid: ¤9,973.34