I want to search for...
Permit #2021071463
Permit Details
Status: COED
| Parcel Id: 07-11-31-7037-01470-0080 |
| CONDITIONED SPACE: 1510 sqft |
| GARAGE: 403 sqft |
| OPENED PORCH (WITH ROOF) : 240 sqft |
| OPENED PORCH (WITH ROOF) : 32 sqft |
| Total Square Footage: 2185 sqft |
| Block: 01470 |
| Subdivision: 2176 - SECTION 37-LAKEVIEW |
| Job Phone: 386-960-7720 |
| Location Address: 66 LEIDEL DR |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 08/26/2021 |
| NOC: RECORDED |
| Applicant name: LAWRENCE FRED SIETSMA |
| Owner: AVTEC HOMES INC |
|
Address 2405 E GRAVES AVE ORANGE CITY, FL 32763 |
| Lot: 0080 |
| Contracted Stated Job Value: ¤231,865.00 |
| Job Description: Single family Residence |
| Type: CN |
Contractor
AVTEC HOMES INC
| Status | Location Address | State License Number | Phone |
| CANCEL |
2405 E GRAVES AVE ORANGE CITY, FL 32763 |
CRC041905 (Exp: 08/31/2024) | 386-960-7720 |
Sub Contractors
STEVEN JAY SMITH
| Status | Location Address | State License Number | Phone |
| INACTIVE |
104 West Cedar Avenue Orange City, FL 32763 |
EC0001542 (Exp: 08/31/2022) | (386)775-7776 |
DOUGLAS EDWARD RICHARDS
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
108 E INDIANA AVENUE DELAND, FL 32724 |
CCC1328824 (Exp: 08/31/2024) | 386-736-4226 | 386-740-0535 |
RUSSELL J CARTER
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
PO BOX 302 DELAND, FL 32721 |
CFC1425938 (Exp: 08/31/2026) | 386-736-4220 | 386-736-4219 |
BRUCE R BOLTON
| Status | Location Address | Mailing Address | State License Number | Phone | Fax |
| CANCEL |
1982 SR 44 NEW SMYRNA BEACH, FL 32168 |
SUITE 357 NEW SMYRNA BEACH, FL 32168 |
CAC1817407 (Exp: 08/31/2022) | 386-216-5975 | 386-402-4191 |
Inspection History
| Type | Request Date | Result | Inspector |
| BLD - BUILDING FINAL | 05/04/2022 | CANCELLED BY APPLICANT | WEB |
| Note: THIS IS A REINSPECTION MOCP on air handler is 35a there is a 40a installed need to correct, also need to seal opening around carflex electrical conduit at ceiling air handler closet | |||
| BLD - BUILDING FINAL | 05/04/2022 | FINAL APPROVED | RMARTIN |
| Note: New inspection due to canceled inspection THIS IS A REINSPECTION MOCP on air handler is 35a there is a 40a installed need to correct, also need to seal opening around carflex electrical conduit at ceiling air handler closet | |||
| U -UTILITY RESIDENTIAL FINAL | 05/03/2022 | FINAL APPROVED | DHANEY |
| BLD - BUILDING FINAL | 05/03/2022 | Disapproved - NO FEE | RMARTIN |
| Note: MOCP on air handler is 35a there is a 40a installed need to correct, also need to seal opening around carflex electrical conduit at ceiling air handler closet | |||
| FINAL SURVEY (OFFICE USE ONLY) | 04/19/2022 | APPROVED | RGROSS |
| ROW FIELD SURVEY /GRADING CERTIFICATION | 04/19/2022 | APPROVED | RGROSS |
| ROW - STORMWATER FINAL | 04/19/2022 | APPROVED | RGROSS |
| ROW - FINAL APRON (AFTER POUR) | 04/19/2022 | APPROVED | RGROSS |
| ELECTRIC - EARLY POWER | 03/17/2022 | APPROVED - AS NOTED | JMUNSON |
| Note: New inspection due to canceled inspection THIS IS A REINSPECTION 1. Electric load calcs call for a 200 amp main breaker. Breaker and wire needs to be changed out. 2. Branch circuits can not be in the same conduit as the service wires. NEC 2107 230.7 3/16/22 Emailed FPL at 1:17 pm | |||
| ELECTRIC - EARLY POWER | 03/16/2022 | CANCELLED BY APPLICANT | WEB |
| Note: THIS IS A REINSPECTION 1. Electric load calcs call for a 200 amp main breaker. Breaker and wire needs to be changed out. 2. Branch circuits can not be in the same conduit as the service wires. NEC 2107 230.7 | |||
| ELECTRIC - EARLY POWER | 03/08/2022 | Disapproved -FEE REQUIRED | JMUNSON |
| Note: 1. Electric load calcs call for a 200 amp main breaker. Breaker and wire needs to be changed out. 2. Branch circuits can not be in the same conduit as the service wires. NEC 2107 230.7 | |||
| ROW- PRE-APRON (PRE-POUR) | 03/04/2022 | APPROVED - AS NOTED | KRUTH |
| Note: pipe is good at the time of the inspection It is the BUILDER'S RESPONSIBILITY: to recheck elevations and pipe size, to insure that an obstruction does not exist upstream and or downstream, that the culvert pipe is set to and or follows the swale plan, form the driveway to the approved site plan and follow the approved driveway detail sheet provided by the City of Palm Coast. PRIOR to placement of concrete | |||
| U-CROSS CONNECTION | 02/25/2022 | APPROVED - AS NOTED | DHANEY |
| Note: Approved yard/Irr. not installed yet no cross cn . | |||
| U - SEWER TIE IN | 02/25/2022 | APPROVED | MGIBSON |
| GRAVITY SEWER TEST | 02/25/2022 | APPROVED | MGIBSON |
| PEP TANK INSTALLATION REQUEST | 01/28/2022 | APPROVED | CSTONE |
| Note: THIS IS A REINSPECTION ADDED ON 1/19/2022 4:03:26 PM interior and exterior (sheet rock & stucco or siding) | |||
| LATH/BRICK/ WATER BARRIER | 01/19/2022 | APPROVED | FWILLIS |
| INSULATION | 01/18/2022 | APPROVED | FWILLIS |
| PEP TANK INSTALLATION REQUEST | 01/18/2022 | Disapproved - NO FEE | CSTONE |
| Note: interior and exterior (sheet rock & stucco or siding) | |||
| ALL ROUGH | 12/28/2021 | APPROVED | RMARTIN |
| ROOF VALLEY & METAL | 12/20/2021 | APPROVED | FWILLIS |
| WALL SHEATHING | 12/08/2021 | APPROVED | FWILLIS |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 12/08/2021 | APPROVED | FWILLIS |
| TIE BEAM / LINTEL | 11/16/2021 | APPROVED | FWILLIS |
| FOUND SURVEY APPROVED (OFFICE) | 11/09/2021 | APPROVED | TBAKER |
| MONOLITHIC SLAB | 10/26/2021 | APPROVED | FWILLIS |
| Note: THIS IS A REINSPECTION NO COMPACTION TEST POSTED | |||
| MONOLITHIC SLAB | 10/25/2021 | Disapproved - NO FEE | DCUSHING |
| Note: NO COMPACTION TEST POSTED | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 10/11/2021 | APPROVED | MGIBSON |
| WATER METER INSTALLATION REQUEST | 09/27/2021 | APPROVED | CSTONE |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 03/11/2022 | 03/14/2022 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM | |||
| ELEC | HOLD | 03/10/2022 | 03/10/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Plans need to be seperated when uploaded. If only uploading electric plan then that is the only plan you need to upload. 2. Electrican can not over ride engineers load calcs. 3. Electricans load calcs need to be done correctly per NEC 2020. | |||
| ELEC | HOLD | 03/10/2022 | 03/11/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 2. Electrican can not over ride engineers load calcs. 3. Electricans load calcs need to be done correctly per NEC 2020. | |||
| ENGIN1 | COMPLETE | 11/09/2021 | 11/09/2021 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 11/09/2021 | 11/09/2021 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| BADMIN | HOLD | 10/12/2021 | 10/12/2021 |
| Note: Held By: MARGA DEFREITAS - - MDEFREITAS@PALMCOASTGOV.COM you name this Documents Final survey you are not ready for this yet your need is a FOUNDATION SURVEY NOT A FORMBOARD WE DONT DO FORMBOARD SURVEY | |||
| BADMIN | COMPLETE | 10/12/2021 | 10/12/2021 |
| Note: Released By: MARGA DEFREITAS - - MDEFREITAS@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 08/06/2021 | 08/08/2021 |
| Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 07/29/2021 | 08/03/2021 |
| Note: Released By: JPI | |||
| CUSVC | COMPLETE | 07/29/2021 | 08/05/2021 |
| Note: Released By: HALEIGH HAND - - | |||
| ELEC | COMPLETE | 07/29/2021 | 08/02/2021 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ENGIN1 | COMPLETE | 07/29/2021 | 07/29/2021 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| LOCATE | COMPLETE | 07/29/2021 | 08/03/2021 |
| Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM | |||
| MECH | HOLD | 07/29/2021 | 07/30/2021 |
| Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM Energy Calcs need to be signed by the builder | |||
| SW1 | COMPLETE | 07/29/2021 | 08/04/2021 |
| Note: Released By: KALEN RUTH - (386)566-1273 - KKRUTH@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 07/29/2021 | 08/02/2021 |
| Note: Released By: CINDY CHIRI-GONCALVES - - CGONCALVES@PALMCOASTGOV.COM | |||
| SWALE | COMPLETE | 07/29/2021 | 11/01/2021 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 05/05/2022 |
| CONNECTION FEES | ¤1,017.83 | 08/26/2021 |
| BUILDING DISCOUNT 100% | (¤1,174.40) | 08/26/2021 |
| 3% FIRE IMPACT FEE CREDIT | (¤11.01) | 08/26/2021 |
| IMPACT FEE FIRE | ¤367.00 | 08/26/2021 |
| IMPACT FEE PARKS | ¤1,199.12 | 08/26/2021 |
| IMPACT FEE SCHOOL | ¤3,600.00 | 08/26/2021 |
| IMPACT FEE TRANSPORTATION | ¤1,718.00 | 08/26/2021 |
| WATER -IRRIGATION INSPECTION | ¤25.00 | 08/26/2021 |
| 3% PARKS IMPACT FEE CREDIT | (¤35.97) | 08/26/2021 |
| NEW RESIDENTIAL INSPECTIONS | ¤464.00 | 08/26/2021 |
| SITE PLAN 20 | ¤20.00 | 08/26/2021 |
| SURCHARGE FS 533.721 | ¤2.00 | 08/26/2021 |
| SURCHARGE - FS 468.631 | ¤2.00 | 08/26/2021 |
| STORM WATER PERMIT FEES | ¤80.00 | 08/26/2021 |
| 3% TRANS IMPACT FEE CREDIT | (¤51.54) | 08/26/2021 |
| SEWER CREDIT | (¤850.00) | 08/26/2021 |
| SEWER INSPECTION | ¤25.00 | 08/26/2021 |
| SEWER CAPITAL FACILITY | ¤4,664.55 | 08/26/2021 |
| WATER CAPITAL FACILITY FEE | ¤3,424.45 | 08/26/2021 |
| METER - DEPOSIT | ¤60.00 | 08/26/2021 |
| WATER- TURN ON | ¤25.00 | 08/26/2021 |
| ADMINISTRATIVE RESIDENTIAL | ¤20.00 | 08/26/2021 |
| INSPECTION- ELECTRICAL | ¤199.20 | 08/26/2021 |
| INSPECTION - MECHANICAL | ¤199.20 | 08/26/2021 |
| INSPECTION - PLUMBING | ¤199.20 | 08/26/2021 |
| PLAN REVIEW - RESIDENTIAL | ¤92.80 | 08/26/2021 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤15,321.43 |